Ipari érzékeléstechika
+36 88 545 902
+36 88 560 472
Leválasztók, jelátalakítók
+36 88 545 902
+36 88 560 472

Timer, Counter KC-LCD-48-1R-230VAC

KC-LCD-48-1R-230VAC
  • Counter/Timer
  • Adding/subtracting via 2 separate inputs
  • Batch controller with 1 pre-selection
  • Easy-to-read, 2-line LCD display with symbols for indicated pre-selection and output status
  • Display range and preselection range from -999999 up to 999999
    Overflow will be evaluated correctly up to 1 decade
  • PNP and NPN sensors can be connected
  • Degree of protection IP65 (front only)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  KC-LCD-48-1R-230VAC

Termék leírása
LCD batch controller with 1 relay output and 230 VAC supply voltage
General specifications
Pre-selectionsingle
Data storage> 10 years, EEPROM
Programmingkeypad-driven menu
Indicators/operating means
Type2-line, 2 x 6-digit LC display with leading sign
Display valuedigit height 9 mm
Pre-selectiondigit height 7 mm
Key interlockvia "high" potential at "LOCK" input
Decimal point0 to max 5 fractional digits
Scale factor0.0001 ... 99.9999
Resetmanually or external
Electrical specifications
FusingT 0.1 A
Operating voltage230 V AC
Power consumptionmax. 6.5 VA
Input
ConnectionCounter inputs: A and B
Control/reset inputs: LOCK, RESET
Signal voltage
High3.5 ... 30 V DC
Low0 ... 2 V DC
Counting frequency30 Hz / 5 kHz
Minimum pulse durationControl/reset inputs: static / 1 ms
Impedance10 kOhm
Count modes
Pulse counterCounting with counting direction (cnt.dir),
difference counting (up.dn),
up/down counting (quad),
TimerTime measurement via GATE input (FrErun),
counter input A: Start, counter input B: Stop (InpA.InpB.),
counter input B: Start/Stop (InpB.InpB.),
Output
Relaychangeover contact
Switching voltagemax. 250 V AC / 110 V DC
Switching currentmax. 3 A AC/DC, min. 30 mA DC,
Switching powermax. 750 VA / 90 W
Mechanical life2 x 107 switching cycles
Electrical life5 x 104 cycles at 3 A
Response time< 15 ms pulse counter
< 10 ms time counter
Sensor supply14.4 ... 27.6 V DC
max. 50 mA at 230 VAC
Compliance with standards and directives
Directive conformity
Low Voltage Directive 2006/95/ECEN 61010-1:2001; protection class: 2
EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 50295:1999
Standard conformity
Emitted interferenceDIN EN 55011:2009, Class B
Mech. capacityEN 60068-2-6:2008
10 … 55 Hz / 1 mm / XYZ
30 min in each direction
Shock and impact resistanceEN 60068-2-27:1995
100 G / 2 ms / XYZ
3 times in each direction
Ambient conditions
Ambient temperature-10 ... 50 °C (14 ... 122 °F)
Storage temperature-25 ... 75 °C (-13 ... 167 °F)
Relative humidity≤ 93 % at 40 °C
(noncondensing)
Altitude0 ... 2000 m
Pollution degree2
Mechanical specifications
Degree of protectionIP65 (front)
Massapprox. 230 g
Dimensions48 mm x 48 mm x 109.8 mm

Classifications

SystemClasscode
ECLASS 13.027210301
ECLASS 12.027210301
ECLASS 11.027210301
ECLASS 10.0.127210301
ECLASS 9.027210301
ECLASS 8.027210301
ECLASS 5.127210301
ETIM 9.0EC002300
ETIM 8.0EC002300
ETIM 7.0EC002300
ETIM 6.0EC002300
ETIM 5.0EC000677
UNSPSC 12.141111902

Details: KC-LCD-48-1R-230VAC

Product Documentation: KC-LCD-48-1R-230VAC

Nyelvválasztás:
Brief InstructionsNyelvFájltípusFájlméret
Operating Instructions KC-LCD-48-1R-* / Bedienungsanleitung KC-LCD-48-1R-*ALLPDF2263 KB

Approvals: KC-LCD-48-1R-230VAC

Nyelvválasztás:
Declaration of ConformityTanúsítvány sz.NyelvFájltípusFájlméret
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2895BALLPDF110 KB