Ipari érzékeléstechika
+36 88 545 902
+36 88 560 472
Leválasztók, jelátalakítók
+36 88 545 902
+36 88 560 472

Power Supply PS1000-A6-24.5

PS1000-A6-24.5
  • 100 V AC to 240 V AC wide-range input
  • Output 24 V DC, 5 A, 120 W, 1-phase
  • Housing width 32 mm
  • Efficiency up to 94.3 %
  • Minimal inrush current surge
  • DC OK relay contact
  • Suitable for Zone 2/Div. 2 mounting

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  PS1000-A6-24.5

Electrical specifications
Efficiency93.6 % at 120 V AC
94.3 % at 230 V AC
Power dissipation8.2 W at 120 V AC
7.3 W at 230 V AC
Input
Voltage range100 ... 240 V AC (-15 %/+10 %), 50 ... 60 Hz (±6 %)
110 ... 150 V DC (±20 %)
Current1.09 A at 120 V AC
0.6 A at 230 V AC
1.21 A at 110 V DC
for lower output currents see technical information
Inrush current5 A peak at 120 V AC and ambient temperature 40 °C (104 °F)
6 A peak at 230 V AC and ambient temperature 40 °C (104 °F)
or
ambient temperature 25 °C (77 °F)
Capacity factor0.98 at 120 V AC
0.91 at 230 V AC
Output
Rated voltage24 V DC
Voltage range24 ... 28 V DC
factory setting: 24.1 V
Rated current5 A
Current6 ... 5.1 A at ambient temperature < 45 °C (113 °F)
5 ... 4.3 A at ambient temperature 60 °C (140 °F)
3.8 ... 3.2 A at ambient temperature 70 °C (158 °F)
linear power derating see technical information
Power120 W
Ripplemax. 50 mV pp
Hold-up time35 ms at 120 V AC
35 ms at 230 V AC
Overload behaviorcontinuous current at output voltage > 13 V DC
Hiccup behaviour at output voltage < 13 V DC
Short-circuit currenttyp. 15 A for 12 ms or 3 A rms continuous current
Voltage limitationtyp. 30.5 V DC
max. 32 V DC
Fault indication output
Connectionterminals 13, 14
Output typerelay contact DC OK
- contact is closed if the output voltage is > 90 % of the adjusted output voltage
Contact loadingmax. 60 V DC/0.3 A ; 30 V DC/1 A ; 30 V AC/0.5 A resistive load
min. 1 mA at 5 V DC
Galvanic isolation
Input/OutputSELV/PELV
Indicators/settings
Display elementsLED green: status DC OK
- LED lights up if the output voltage is > 90 % of the adjusted output voltage
Control elementspotentiometer
Configurationsetting of the output voltage via potentiometer
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUIEC/EN 61000-6-1 , IEC/EN 61000-6-2 , IEC/EN 61000-6-3 , IEC/EN 61000-6-4 , IEC/EN 61000-3-2 ,
IEC/EN 61000-3-3
Low voltage
Directive 2014/35/EUEN 61010-1
RoHS
Directive 2011/65/EU (RoHS)IEC/EN 63000:2019
Conformity
Degree of protectionEN 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F) , see technical information
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity5 ... 95 %, noncondensing
Shock resistance20 g , 11 ms or 30 g , 6 ms
Vibration resistance2 ... 17.8 Hz : ± 1.6 mm , 17.8 ... 500 Hz : 2 g
Mechanical specifications
Housing materialaluminum alloy , galvanized steel
Degree of protectionIP20
Connection
Input/Outputscrew terminals
conductor cross section: max. 6 mm2 (AWG 20-10)
cable diameter: max. 2.8 mm, wire end ferrules included
stripped insulation length: 7 mm
tightening torque: max. 1 Nm
Relay contact outputspring terminals with push-in connection technology
conductor cross section: max. 1.5 mm2 (AWG 24-16)
cable diameter: max. 1.6 mm, wire end ferrules included
stripped insulation length: 7 mm
Massapprox. 440 g  
Dimensions32 x 124 x 102 mm (W x H x D) , without DIN mounting rail
Height124 mm
Width32 mm
Depth102 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
ATEX approval
ATEX certificateEPS 19 ATEX 1201 X
ATEX markingEx-Hexagon II 3G Ex ec nC II T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-15:2010
International approvals
UL approvalE350173 , E223176
IECEx approval
IECEx certificateIECEx EPS 20.0058X
IECEx markingEx ec nC IIC T4 Gc
StandardsIEC 60079-0:2017 , IEC 60079-7:2017 , IEC 60079-15:2017
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.019209090
ECLASS 12.019209290
ECLASS 11.019209290
ECLASS 10.0.119209290
ECLASS 9.019209290
ECLASS 8.019209290
ECLASS 5.127242392
ETIM 9.0EC002542
ETIM 8.0EC002542
ETIM 7.0EC002542
ETIM 6.0EC002542
ETIM 5.0EC002542
UNSPSC 12.139121004

Details: PS1000-A6-24.5

Function

The device is used to supply field devices with 24 V DC and 5 A.

The device has a power reserve of 20 % included, which may even be used continuously at temperatures up to +45 °C.

The output voltage can be adjusted via a potentiometer. The device status is indicated by an LED.

The device has a relay contact output for remote monitoring.

The device is mounted on a 35 mm DIN mounting rail according to EN 60715.

Informative Literature: PS1000-A6-24.5

Nyelvválasztás:
LiteratureNyelvFájltípusFájlméret
Product Information - PS1000 for Global Use up to Zone 2/Div. 2ENGPDF577 KB

Product Documentation: PS1000-A6-24.5

Nyelvválasztás:
Product informationNyelvFájltípusFájlméret
Technical informationENGPDF2970 KB
Safety and Security Documentation
Instruction manual / BetriebsanleitungALLPDF243 KB
Instruction manual / BetriebsanleitungALLPDF348 KB

Design / Simulation: PS1000-A6-24.5

Nyelvválasztás:
CADNyelvFájltípusFájlméret
CAD 3-D / CAD 3-DALLSTP3858 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ178 KB

Approvals: PS1000-A6-24.5

Nyelvválasztás:
CertificatesTanúsítvány sz.NyelvFájltípusFájlméret
Bureau Veritas IECEx Certificate of ConformityIECEx EPS 20.0058XALLLINK---
Canada US ULUL E350173 (NRAD/NRAD7)ALLPDF83 KB
Europe Bureau Veritas ATEX Category 3 GEPS 19 ATEX 1 201XALLPDF786 KB
US CA ULCoC E223176 RptRef E223176-20070416ALLPDF444 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4784ALLPDF83 KB
EU Declaration of Conformity (P+F)TDOC-4784AHUNHUNPDF186 KB

Kapcsolódó termékek: PS1000-A6-24.5

Kit
IIoT Starter Kit with IP20 EtherNet/IP Masterfa
IIoT Starter Kit with IP67 EtherNet/IP Masterfa
IIoT Starter Kit with IP20 PROFINET Master fa
IIoT Starter Kit with IP67 PROFINET Masterfa
Accessories

EtherNet/IP IO-Link master with 8 inputs/outputsfa

Distance sensor, Medium design with versatile mounting options, Space-saving distance sensors in small standardized design, Multi Pixel Technology (MPT) - exact and precise signal evaluation, IO-Link interface for service and process datafa
Data carrierfa
Female cordset single-ended M12 straight L-coded, 5-pin, PUR cable grey, UL approvedfa
Ethernet bus cable RJ45 to RJ45 PROFINET-coded, 4-pin, PUR cable green, Cat5e, shielded, drag chain suitablefa
HF RFID read/write device with IO-Link in accordance with ISO 15693fa
Reduction factor 1, magnetic field resistant, Switching function: Normally open/closed (NO/NC) programmable, Output type: PNP, Rated operating distance: 4 mm (factory setting), Installation: flush, Output polarity: DC, Output type: 3-wire, Thread mold: M12, Construction type: Cylindrical, thread, Series: Cylindrical type, Operating voltage: 10 ... 30 V DC, Switching frequency: 0 ... 2000 Hz (switch point mode)
0 ... 125 Hz (window mode, switch point mode with stability alarm), Type of voltage: DCfa
24 V DC to 28 V DC input, 2 inputs with 1 output, Output 24 V DC, 20 A, Housing width 32 mm, Built-in decoupling mosfets for 1+1 and N+1 redundancy, Automatic load sharing, Reverse input polarity protection, Easy wiring: distribution terminal for negative pole included, Redundancy status indicator, Suitable for Zone 2/Div. 2 mounting, Device type: device for DIN rail mounting, Function: Redundancy Module, Voltage range: 24 ... 28 V DCpa