Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
A teljes adatlap letöltése PDF formátumban:
General specifications | ||
---|---|---|
Signal type | Analog input | |
Operation time | MTBF: 353 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F) |
|
Supply | ||
Connection | Power Bus or terminals 1-, 2+ | |
Rated voltage | 16.8 ... 31.2 V DC | |
Power dissipation | 0.7 W | |
Power consumption | 0.8 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 5, 6, 7, 8 | |
PTC | type KT, KTY, ST | |
Measuring current | approx. 200 µA | |
Types of measuring | 2-, 3-, 4-wire connection | |
Lead resistance | ≤ 100 Ω per line | |
Measurement loop monitoring | sensor breakage, lead breakage, short circuit | |
RTD | type Pt100, Pt200, Pt500, Pt1000 (EN 60751:1995) type Ni100, Ni200, Ni500, Ni1000 (DIN 43760) |
|
Measuring current | approx. 200 µA | |
Types of measuring | 2-, 3-, 4-wire connection | |
Lead resistance | max. 100 Ω per line | |
Measurement loop monitoring | sensor breakage, lead breakage, short circuit | |
Thermocouples | type B, E, J, K, N, S, T (IEC 584-1:1995) type L, U (DIN 43710:1985) type C, D (ASTM E988) |
|
Cold junction compensation | external (Pt100) and internal , manually | |
Lead resistance | max. 10 kΩ | |
Measurement loop monitoring | sensor breakage, lead breakage | |
Resistor | ||
Measuring range | 0 ... 5 kΩ | |
Potentiometer | 0.2 ... 50 kΩ | |
Types of measuring | 3-wire connection | |
Voltage | -100 ... 100 mV -1000 ... 1000 mV |
|
Input resistance | ≥ 1 MΩ | |
Output | ||
Connection side | control side | |
Connection | terminals 3-, 4+ | |
Analog voltage output | 0/1 ... 5 V , 0/2 ... 10 V , load ≥ 2 kΩ | |
Analog current output | 0/2 ... 10 mA, 0/4 ... 20 mA, load ≤ 600 Ω | |
Ripple | ≤ 10 mV eff | |
Fault signal | downscale or upscale | |
Transfer characteristics | ||
Accuracy | max. 0.1 % of full-scale value | |
Measuring time | ≤ 300 ms | |
Deviation | ||
RTD | < 0.1 K/0.05 % of the measured value | |
Thermocouples | < 0.3 K/0.1 % of the measured value | |
Voltage | < 0.1 % of the measured value | |
Potentiometer | < 0.02 % of the measured value | |
Influence of ambient temperature | < 100 ppm/K of full-scale value | |
Galvanic isolation | ||
Output/power supply | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Input/Other circuits | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min | |
Indicators/settings | ||
Control elements | DIP switch keys |
|
Configuration | via DIP switches via keys via software |
|
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | EN 61010-1:2010 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
Mass | approx. 70 g | |
Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1 | |
Height | 97 mm | |
Width | 6.2 mm | |
Depth | 107 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | DEMKO 16 ATEX 1750X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 | |
IECEx approval | ||
IECEx certificate | IECEx UL 16.0116X | |
IECEx marking | Ex nA IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210129 |
ECLASS 12.0 | 27210129 |
ECLASS 11.0 | 27210129 |
ECLASS 10.0.1 | 27210129 |
ECLASS 9.0 | 27210129 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27210107 |
ETIM 9.0 | EC002919 |
ETIM 8.0 | EC002919 |
ETIM 7.0 | EC002919 |
ETIM 6.0 | EC002919 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
This signal conditioner provides the galvanic isolation between field circuits and control circuits.
The device has an input for signals of the following field devices:
- resistance thermometers
- thermocouples
- PTC thermistors
- potentiometers
- voltage sources
- field device with its own characteristic
The device provides the following standard signals at the output:
- 0/2 mA ... 10 mA signal
- 0/4 mA ... 20 mA signal
- 0/1 V ... 5 V signal
- 0/2 V ... 10 V signal
This device has an integrated cold junction compensation. You can also implement external cold junction compensation.
A fault is signalized by LEDs.
The device is easily configured by the use of DIP switches.
The Teach-In function can be used to teach in the potentiometer start value and end value.
The device can be powered via terminals or Power Bus.
Literature | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Application Report - Sand Trap and Preliminary Sedimentation Stage | ENG | 448 KB | |
Product Overview SC-System | ENG | 456 KB | |
Tender text | |||
Tender text | ENG | D81 | 8 KB |
Brief Instructions | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Brief instructions | ENG | 282 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 136 KB | |
Manuals | |||
System Manual | ENG | 2706 KB |
CAD | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 4814 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 97 KB |
EPLAN macros SC-System devices (EDZ) / EPLAN-Makros SC-System-Geräte (EDZ) | ALL | ZIP | 4082 KB |
Certificates | Tanúsítvány sz. | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|---|
Canada UL cUL | E106378 cUL (QUZW7) | ALL | LINK | --- |
Europe DEMKO ATEX Category 3 G | DEMKO 16 ATEX 1750X | ALL | 1876 KB | |
UL Non-Sparking nA IECEx Certificate of Conformity | IECEx UL 16.0116X | ALL | LINK | --- |
USA UL | E106378 UL (QUZW) | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-0534EHUN | HUN | 180 KB |
Device Description Files/Drivers | Megjelenési információ | Fájltípus | Fájlméret |
---|---|---|---|
DTM for S1SD-1TI-1U / DTM für S1SD-1TI-1U | ZIP | --- | |
Software Tools | |||
Configuration software for SC-System: SC-Config / Konfigurations Software für SC-System: SC-Config | 3.4.0 | ZIP | --- |
PACTware 4.1 SP6 / PACTware 4.1 SP6 | 4.1.0.53 | ZIP | 43327 KB |
PACTware 5.0 / PACTware 5.0 | 5.0.5.31 | ZIP | 44203 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|