Switch Amplifier HiC2822

HiC2822
  • 2-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Dry contact or NAMUR inputs
  • 2 relay contact outputs
  • Line fault detection (LFD)
  • Reversible mode of operation
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  HiC2822

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current≤ 30 mA
Power dissipation≤ 600 mW
Power consumption≤ 600 mW
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-)
Rated valuesacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.7 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Output
Connection sidecontrol side
ConnectionSL1: 8a, 7a; 10a, 9a
Output Isignal ; relay
Output IIsignal ; relay
Contact loading50 V DC / 0.5 A
Minimum switch current2 mA / 24 V DC
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Mechanical life107 switching cycles
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Switching frequency≤ 10 Hz
Galvanic isolation
Output/power supplybasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Output/Outputbasic insulation acc. to EN 50178, rated insulation voltage of 50 V AC
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Galvanic isolationEN 50178:1997
Electromagnetic compatibilityEN IEC 61326-3-2:2018 , NE 21:2012
For further information see system description.
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 110 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1 and 2 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 06 ATEX 0093 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage10.5 V
Current17.1 mA
Power45 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Contact loading50 V DC / 0.5 A
Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
CertificatePF 08 CERT 1047 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing16-534FM-12 (cFMus)
UL approvalE106378
Control drawing116-0434
IECEx approval
IECEx certificateIECEx BAS 06.0026X
IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2822

Function

This isolated barrier is used for intrinsic safety applications.

The device transfers digital signals ( NAMUR sensors/mechanical contacts) from the explosion-hazardous area to the non-explosion-hazardous area.

Each input controls a relay contact output for the non-explosion-hazardous area load.

Via switches the mode of operation can be reversed and the line fault detection can be switched off.

During a fault state, the relays revert to the de-energized state and LEDs indicate the fault according to NAMUR NE 44. A separate fault bus is available. This fault bus can be monitored if the termination board supports a module fault detection.

This device mounts on a HiC termination board.

Product Documentation: HiC2822

Nyelvválasztás:
Safety and Security DocumentationNyelvFájltípusFájlméret
Használati útmutatóHUNPDF169 KB
Functional Safety ManualENGPDF771 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2822

Nyelvválasztás:
CADNyelvFájltípusFájlméret
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiC2822

Nyelvválasztás:
CertificatesTanúsítvány sz.NyelvFájltípusFájlméret
Baseefa IECEx Certificate of ConformityIECEx BAS 06.0026XALLLINK---
Canada FMFM19CA0065XALLPDF374 KB
China SITIIAS CCC Ex Certificate2020322316001448 (Singapore)ALLPDF1078 KB
Europe Baseefa ATEX Category (M1) ATEX Category (1) GDBaseefa 06 ATEX 0093XALLPDF1225 KB
Europe Pepperl+Fuchs ATEX Category 3 G CertificatePF 08 CERT 1047 XALLPDF212 KB
Pepperl+Fuchs Functional Safety AssessmentPF 12 CERT 2161ALLPDF64 KB
South Africa MASCMASC MS/17-2381XALLPDF745 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20170516 - E106378 RepRef 20170516ALLPDF253 KB
USA FMFM19US0122XALLPDF346 KB
United Arab Emirates SGS Gulf Limited ECASEx24-02-101829/E24-02-105322/NB0002ALLPDF602 KB
exida Functional Safety AssessmentP+F 1109-099-C R026 V1R0ALLPDF464 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF92 KB
Instruction leaflet / Beipackzettel   ALLPDF80 KB
Control drawing FM / Control drawing FM   ALLPDF112 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0927DALLPDF50 KB

Kapcsolódó termékek: HiC2822

Accessory of

System board for Schneider, Foxboro FBM series, For 16 modules, For 32-channel DI card FBM217, 24 V DC supply, Recommended modules: HiC2822 (DI), HiC2842 (DI), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Foxboro, Control system type: FBMpa
System board for Yokogawa CENTUM VP, For 32-channel DI card ADV151, For 16 modules, Recommended modules: HiC2822 (DI), HiC2842 (DI), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Yokogawa, Control system type: CENTUM VPpa
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel DI card 3506X, For 16 modules, 24 V DC supply, Recommended modules: HiC2822 (DI), HiC2842 (DI), Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Input, Manufacturer: Triconex, Control system type: Tricon CXpa
Funkcionális biztonság központ a Pepperl+Fuchs-nál

Több száz SIL/PL értékeléssel ellátott termék, ingyenes eszközök és prospektusok egy helyen: a „Funkcionális biztonság központ” a legjobb kiindulópont biztonsági funkciók kivitelezéséhez.

K-System by Pepperl+Fuchs: Globally certified protection for people, plants, and the environment!

The largest portfolio of its kind: K-System components and systems are established in process industries around the world. Learn more!