Servisní linka pro průmyslové snímače
Servisní linka ochrany před výbuchem

Type Y & Z pressurization system 1001C

1001C
  • NFPA 70, NFPA 496, ISA 12.4 standards
  • Optional alarm output indicates air lock failure
  • Type Y system certified for Class II, Division 1 to Division 2
  • Type Z system certified for Class II, Division 2 to nonhazardous
  • Enclosure volume up to 7.08 m3 (250 ft3)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Stáhněte si kompletní katalogový list ve formátu PDF:


Výňatek z katalogového listu: Technická data   1001C

Popis produktu
1001C Series pressurization system
General specifications
Series1001C
SystemType Y Purge , Type Z Purge
Hazardous environmentgas
Electrical specifications
ConnectionTerminal blocks
Output
Output I-WPS-
Output typeSwitch contacts
Contact loading120 VAC @ 15 A
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Pressure requirement5 - 120 psi
(With EPV-4 vent. Systems installed without vent must be equipped with redundant regulator set to 5 psi max.)
Safe pressureSetpoint: 1.0" (25.4 mm)
Flow rate: 0.1 - 3.5 SCFH (2.8 - 99 l /hr)
Ambient conditions
Ambient temperature-29 ... 49 °C (-20.2 ... 120.2 °F)
Mechanical specifications
Connection typeSystem supply fitting: 1/2" tube fitting
Enclosure supply fitting: 1/2" tube fitting
Enclosure reference fitting: 1/4" tube fitting
Switch conduit port size: 1/2" FPT
MaterialRegulator body: zinc w/enamel finish
Regulator handle: polycarbonate
Enclosure pressure gauge: alum. w/enamel finish
Tube fitting: 316 ss forged body
Tubing: 316 ss 1/4" .035 welded
System nameplate: silk screened Lexan® & ss
Fastener hardware: alum. & stainless steel
Mounting plate: 316 14 ga #3 brush ss
EXP pressure switch body: anodized cast aluminum
Enclosure warning nameplate: silk screened ss
Mass1001C-LPS-* 3.2 kg (7 lb)
1001C-WPS-* 5.4 kg (12 lb)
International approvals
FM approvalType Y
LPS: Class II, Division 1, Groups E, F, and G
WPS: Class II, Division 1, Groups E, F, and G

Type Z
LPS: Class II, Division 2, Groups E, F, and G
WPS: Class II, Division 2, Groups E, F, and G
UL approval
cULusType Y
LPS: Class II, Division 1, Groups E, F, and G
WPS: Class II, Division 1, Groups E, F, and G

Type Z
LPS: Class II, Division 2, Groups E, F, and G
WPS: Class II, Division 2, Groups E, F, and G

Classifications

SystemClasscode
ECLASS 13.027180508
ECLASS 12.027180508
ECLASS 11.027180508
ECLASS 10.0.127180508
ECLASS 9.027180508
ECLASS 8.027180508
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121301

Details: 1001C

Product Documentation: 1001C

Výběr jazyka:
Brief InstructionsJazykTyp souboruVelikost souboru
Installation and Operation Manual: Model 1001C Type Y or Z Pressurization System (USA English)ENGPDF2417 KB

Approvals: 1001C

Výběr jazyka:
CertificatesČíslo certifikátuJazykTyp souboruVelikost souboru
Canada, USA FMCoC 3018335ALLPDF433 KB
UL Hazardous LocationE184741 (RFPW, RFPW7)ALLPDF193 KB

Seznamte se s promyšleným způsobem ochrany zařízení v nebezpečném prostředí a nakonfigurujte si vlastní přetlakový systém!