Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Descargue la hoja de datos completa en PDF:
Extracto de la hoja de datos: Información técnica del
LB9029BP12320.1
General specifications |
Suitable components | Bus Coupler LB8106* , LB8107* , LB8108* , LB8109* , LB8122* |
Slots |
Bus coupler | 2 |
Supply | 3 |
I/O modules (single width) | max. 12 |
I/O modules (dual width) | max. 6 |
Supply |
Maximum safe voltage Um | 60 V DC (SELV/PELV) |
Input voltage range | 18 ... 32 V DC (SELV/PELV) |
Redundancy | yes |
Fieldbus connection |
Fieldbus type | PROFIBUS DP/DP-V1, PROFINET or MODBUS RTU , depends on bus coupler |
Redundancy | yes |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Conformity |
Electromagnetic compatibility | NE 21 |
Degree of protection | EN 60529 |
Ambient conditions |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) , 70 °C (non-Ex) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | 95 % non-condensing |
Altitude | max. 2000 m |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 1380 g |
Dimensions | (W x H x D) 440 x 127 x 80 mm (17.3 x 5 x 3.15 inch) , without modules |
| Height | 127 mm |
| Width | 440 mm |
| Depth | 80 mm |
Data for application in connection with hazardous areas |
Certificate | BVS 16 ATEX E 089 X |
| Marking | II 3 G Ex nA IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-15:2010
|
International approvals |
UL approval | E106378 |
| Control drawing | 116-0321 |
IECEx approval | IECEx BVS 16.0047X |
| Approved for | Ex nA IIC T4 Gc |
General information |
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
ECLASS 13.0 | 27210119 |
ECLASS 12.0 | 27210119 |
ECLASS 11.0 | 27210119 |
ECLASS 10.0.1 | 27210119 |
ECLASS 9.0 | 27210119 |
ECLASS 8.0 | 27210119 |
ECLASS 5.1 | 27210119 |
ETIM 9.0 | EC001598 |
ETIM 8.0 | EC001598 |
ETIM 7.0 | EC001598 |
ETIM 6.0 | EC001598 |
ETIM 5.0 | EC001598 |
UNSPSC 12.1 | 39121008 |
Details:
LB9029BP12320.1
Product Documentation:
LB9029BP12320.1
Design / Simulation:
LB9029BP12320.1
Approvals:
LB9029BP12320.1
Productos asociados:
LB9029BP12320.1
Accessories |
|
|
|
Preconfigured enclosures for engineered LB systems, Max. 12 slots for I/O modules, Installation in Zone 2 or safe area, Impact resistance enclosure, IP66, Number of modules: 12, Material: Stainless steel, Redundancy, Fieldbus type: PROFIBUS DP/DP-V1, PROFINET or MODBUS RTU , depends on bus coupler, Redundancypa |
|