General specifications | ||
---|---|---|
Construction type | device with rope probe | |
Series | LHCS | |
Supply | ||
Rated voltage | versions for safe area: 11.5 ... 35 V DC, HART, 2-wire 9 ... 32 V DC, PROFIBUS PA version for hazardous area see safety information (SI) |
|
Input | ||
Measured variable | hydrostatic pressure , relative pressure | |
Measuring range | 0.1 ... 10 bar max. turn down: 100:1 |
|
Output | ||
Output signal | 4 ... 20 mA with superimposed digital communication protocol HART 6.0, 2-wire digital communication signal PROFIBUS PA (Profile 3.02) |
|
Communication | 4 ... 20 mA HART (standard) PROFIBUS PA (option) |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 , EN 61326-2-5:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Measurement accuracy | ||
Accuracy | reference accuracy: 0.2 % (standard), 0.1 % (platinum) The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and non-reproducibility acc. to IEC 60770. The data refer to the calibrated span. |
|
Long-term drift | up to 0.05 % of upper range limit (URL)/year up to 0.125 % of upper range limit (URL)/5 years |
|
Operating conditions | ||
Process conditions | ||
Process temperature | PE cable: -10 ... 70 °C (14 ... 158 °F) FEP cable: -10 ... 80 °C (14 ... 176 °F) |
|
Ambient conditions | ||
Ambient temperature | PE cable: -40 ... 70 °C (-40 ... 158 °F) FEP cable: -40 ... 80 °C (-40 ... 176 °F) with display -20 ... 70 °C (-4 ... 158 °F) |
|
Storage temperature | PE cable: -40 ... 70 °C (-40 ... 158 °F) FEP cable: -40 ... 80 °C (-40 ... 176 °F) |
|
Mechanical specifications | ||
Degree of protection | IP66, NEMA 4X IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep) IP69K (with separate housing and FEP cable) |
|
Connection | gland M20 thread M20, G1/2, NPT1/2 device plug M12 HAN7D Harting connector, angled valve connector acc. ISO 4400, cable 5 m |
|
Material | process connections: AISI 316L (1.4435 or 1.4404), Alloy C276 (2.4819) housing: - die-cast aluminum with protective powder-coating on polyester base, housing F31 - stainless steel AISI 316L (1.4404), housing F15 rope: PE cable or FEP cable process isolating diaphragm: Alloy C276 (2.4819), Rhodium Gold Alloy C276, Platinum Gold Alloy C276 sealing measuring cell: welded measuring cell or FKM Viton, EPDM, Kalrez |
|
Process connection | threads ISO 228: G1-1/2, threads ANSI: NPT1/2 flanges EN 1092-1: DN 40 ... DN 100, flanges ANSI 16.5: 2 ... 4 in, flanges JIS B2220 |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | see instruction manuals (SI) | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2009 | |
International approvals | ||
FM approval | see instruction manuals (SI) | |
CSA approval | see instruction manuals (SI) | |
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
Drinking water approval | NSF61 approval | |
Overspill protection | see approval (ZE) | |
General information | ||
Supplementary documentation | technical information (TI) manuals, brief instructions (BA, KA) instruction manuals (SI) control drawings (ZD) approval (ZE) |
|
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Designation | see technical information (TI) |
System | Classcode |
---|---|
ECLASS 13.0 | 27200516 |
ECLASS 12.0 | 27200516 |
ECLASS 11.0 | 27200516 |
ECLASS 10.0.1 | 27200516 |
ECLASS 9.0 | 27200516 |
ECLASS 8.0 | 27200516 |
ECLASS 5.1 | 27200516 |
ETIM 9.0 | EC001447 |
ETIM 8.0 | EC001447 |
ETIM 7.0 | EC001447 |
ETIM 6.0 | EC001447 |
ETIM 5.0 | EC001447 |
UNSPSC 12.1 | 41111950 |
Product information | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|
TI00437O, Technical Information LHCR, LHCS | ENG | 3317 KB | |
Brief Instructions | |||
KA1033O, brief instructions LHCR-51, LHCS-51 4 mA ... 20 mA HART | ENG | 1701 KB | |
KA1034O, brief instructions LHCR-51, LHCS-51 PROFIBUS PA | ENG | 5195 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 1273 KB | |
SI00477O, Instruction manual LHCR-51, LHCS-51 | ENG | 850 KB | |
SI00494O, Instruction manual LHCR-51, LHCS-51 | ENG | 858 KB | |
SI478O, Instruction manual LHCR-51, LHCS-51 | ENG | 498 KB | |
SI493O, Instruction manual LHCR-51, LHCS-51 | ENG | 496 KB | |
Manuals | |||
BA382O, Manual LHC-M51, PPC-M51 4 mA ... 20 mA HART | ENG | 2974 KB | |
BA383O, Manual LHC-M51, PPC-M51 PROFIBUS PA | ENG | 2820 KB |
CAD | Idioma | Tipo de archivo | Tamaño |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 1572 KB |
CAD 3-D additional / CAD 3-D additional | ALL | STP | 647 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
¿Busca un producto específico con calificación SIL/PL? Pruebe nuestra herramienta de selección, que le ofrece una visión general de los dispositivos con evaluación de seguridad, incluyendo tanto el nivel de integridad de seguridad (Safety Integrity Level, SIL) como el nivel de rendimiento (Performance Level, PL).