General specifications |
Signal type | Analog output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Systematic capability (SC) | SC 3 |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 19 ... 30 V DC |
Ripple | ≤ 10 % |
Rated current | ≤ 45 mA at 24 V |
Power dissipation | ≤ 1 W at 20 mA and 500 Ω load |
Power consumption | ≤ 1 W |
Input |
Connection side | control side |
Connection | terminals 7-, 8+, (9+); 10-, 11+, (12+) |
Input signal | 4 ... 20 mA , limited to approx. 30 mA |
Input voltage | open loop voltage of the control system ≤ 30 V |
Voltage drop | approx. 6 V at 20 mA |
Input resistance | field wiring open circuit : > 100 kΩ field wiring < 50 Ω : > 100 kΩ when using terminals 1, 2 and 4, 5 |
Output |
Connection side | field side |
Connection | terminals 1+, 2-; 4+, 5- terminals 3+, 2-; 6+, 5- (no short circuit detection) |
Voltage | ≥ 13 V at 20 mA |
Current | 4 ... 20 mA |
Load | 100 ... 650 Ω , for terminals 1, 2; 4, 5 0 ... 550 Ω , for Terminals 2, 3; 5, 6 |
Ripple | 20 mV rms |
Line fault detection | breakage, load > 100 kΩ, short-circuit, load < 50 Ω |
Fault indication output |
Output type | open collector transistor (internal fault bus) |
Transfer characteristics |
Deviation | at 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis |
| Influence of ambient temperature | < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
Rise time | 10 to 90 % ≤ 10 ms |
Galvanic isolation |
Input/Output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/input | functional insulation, rated insulation voltage 50 V AC |
Indicators/settings |
Display elements | LEDs |
Labeling | space for adhesive label at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
Degree of protection | IEC 60529 |
Protection against electrical shock | UL 61010-1:2012 |
Ambient conditions |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 135 g |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 124 mm |
| Width | 20 mm |
| Depth | 115 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | BAS 00 ATEX 7240 X |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Output | Ex ia, Ex iaD |
| Voltage | 25.2 V |
| Current | 93 mA |
| Power | 585.3 mW |
| Internal capacitance | 1.05 nF |
| Internal inductance | 0 |
Supply | |
| Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) |
Input | |
| Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) |
Certificate | FIDI 22 ATEX 0002 X |
| Marking | II 3G Ex ec IIC T4 Gc |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018 |
International approvals |
UL approval | E106378 |
| Control drawing | 116-0345 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx BAS 04.0014X |
| IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |