Wsparcie Czujników Przemysłowych
Wsparcie Ochrony przed wybuchem

Inductive sensor NJ4-12GM-N-5M

NJ4-12GM-N-5M
  • 4 mm non-flush
  • Usable up to SIL 2 acc. to IEC 61508
  • NAMUR output
  • 5 meter connection cable
  • Stainless steel housing


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  NJ4-12GM-N-5M

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance4 mm
Installationnon-flush
Assured operating distance0 ... 3.24 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 1500 Hz
Hysteresis3 %
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected≤ 1 mA
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
MTTFd11774 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
StandardsEN IEC 60947-5-2
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx PTB 11.0037X
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level MbIECEx PTB 11.0037X
ATEX approval
Equipment protection level GaPTB 00 ATEX 2048 X
Equipment protection level GbPTB 00 ATEX 2048 X
Equipment protection level DaPTB 00 ATEX 2048 X
UL approvalcULus Listed, General Purpose
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0452
CCC approval
Hazardous Location2020322315002255
CML approvalon request
ANZEx18.3018X
KCC approval
Hazardous Location19-AV4BO-0227
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typecable
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP67
Cable
Cable diameter4.8 mm ± 0.2 mm
Bending radius> 10 x cable diameter
MaterialPVC
Core cross section0.34 mm2
Length5 m
Dimensions
Length33 mm
Diameter12 mm
General information
Scope of delivery2 self locking nuts in scope of delivery
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NJ4-12GM-N-5M

Product Documentation: NJ4-12GM-N-5M

Language Selection:
Product informationJęzykTyp plikuRozmiar pliku
Technical informationENGPDF161 KB
Brief Instructions
Mounting Instruction locking nut / Montageanleitung, Muttern mit SperrverzahnungALLPDF1117 KB
Safety and Security Documentation
Instrukcja obsługiPOLPDF247 KB

Design / Simulation: NJ4-12GM-N-5M

Language Selection:
CADJęzykTyp plikuRozmiar pliku
CAD 3-D / CAD 3-DALLSTP27 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ64 KB

Approvals: NJ4-12GM-N-5M

Language Selection:
CertificatesNr. certyfikatuJęzykTyp plikuRozmiar pliku
Australia AU Test Safe Group IANZEx 18.3018XALLPDF4026 KB
BR Brasil TUV Rheinland Brazil Ex ia Ex ibTÜV 13.1123 XALLPDF1438 KB
Canada USA UL Hazardous LocationE501628:1:2ALLPDF410 KB
Canada USA UL Ordinary LocationUL-US-2019259-3 / UL-CA-2015551-3ALLPDF288 KB
China SITIIAS CCC Ex Certificate2020322315002255 (Bintan)ALLPDF3704 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePTB 00 ATEX 2048 XALLPDF12880 KB
Japan CML Ex iaCML 23JPN2306XALLPDF307 KB
KR KOSHA Ex ia09-AV4BO-0225/0226/0227ALLPDF304 KB
Pepperl+Fuchs Declaration of Conformity Functional SafetyPF13CERT1624BALLPDF1518 KB
United Kingdom CML UKEX Category I M2 UKEX Category II 2 G UKEX Category II 1 D UKEX Category II 1 GCML 21UKEX21166XALLPDF541 KB
Worldwide PTB IECEx iaIECEx PTB 11.0037XALLLINK---
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF286 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-5068AALLPDF1335 KB
UK Declaration of Conformity (P+F)TDOC-6556AENGENGPDF1328 KB

Produkty powiązane: NJ4-12GM-N-5M

Accessories

Mounting flange, 12 mmfa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont z technologią aktywnego ekranowania

Czujniki indukcyjne VariKont z technologią aktywnego ekranowania zapewniają duże odległości przełączania, niezależnie od warunków instalacji i otaczającego materiału. Skorzystaj z prostszej konstrukcji sprzętu i obniżonych kosztów!

Indukcyjne czujniki bezpieczeństwa SIL 2 PL d

Dzięki temu, że indukcyjne czujniki bezpieczeństwa SIL 2/PL d nie mają martwej strefy, przesyłanie danych może odbywać się bez minimalnej odległości między czujnikiem a obiektem docelowym. Odkryj ofertę zoptymalizowaną pod kątem wymagających środowisk.