Inductive sensor NCB8-18GM40-N0-10M-OG

NCB8-18GM40-N0-10M-OG
  • 8 mm flush
  • NAMUR output
  • Polarity reversal protected
  • Stainless steel housing


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Pobierz pełną kartę katalogową w formie pliku PDF:


Dane techniczne  NCB8-18GM40-N0-10M-OG

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance8 mm
Installationflush
Assured operating distance0 ... 6.48 mm
Actual operating distance7.2 ... 8.8 mm typ. 8 mm
Reduction factor rAl 0.39
Reduction factor rCu 0.36
Reduction factor r304 0.71
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 1500 Hz
Hysteresis1 ... 15 % typ. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detectedmin. 2.2 mA
Measuring plate detected≤ 1 mA
Switching state indicatorall direction LED, yellow
Functional safety related parameters
MTTFd2660 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN IEC 60947-5-2
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx PTB 11.0037X
Equipment protection level GbIECEx PTB 11.0037X
Equipment protection level DaIECEx PTB 11.0037X
Equipment protection level MbIECEx PTB 11.0037X
ATEX approval
Equipment protection level GaPTB 00 ATEX 2048 X
Equipment protection level GbPTB 00 ATEX 2048 X
Equipment protection level DaPTB 00 ATEX 2048 X
CML approvalon request
ANZEx18.3018X
Ambient conditions
Ambient temperature-25 ... 80 °C (-13 ... 176 °F)
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Mechanical specifications
Connection typecable PUR (halogen-free) , 10 m blue , Oil resistant , Flame-retardant as per IEC 60332-1
Mud-resistant according to IEC61892-4, appendix D
Flexible at temperatures as low as -40 °C
Core cross section2x 1 mm2 , black
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP66 / IP67
Cable
Wire end ferrulesyes
Bending radius> 5 x cable diameter
MaterialPUR
Length10 m
Dimensions
Length40 mm
Diameter18 mm
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NCB8-18GM40-N0-10M-OG

Product Documentation: NCB8-18GM40-N0-10M-OG

Language Selection:
Safety and Security DocumentationJęzykTyp plikuRozmiar pliku
Instrukcja obsługiPOLPDF246 KB

Approvals: NCB8-18GM40-N0-10M-OG

Language Selection:
CertificatesNr. certyfikatuJęzykTyp plikuRozmiar pliku
Australia AU Test Safe Group IANZEx 18.3018XALLPDF4026 KB
BR Brasil TUV Rheinland Brazil Ex ia Ex ibTÜV 13.1123 XALLPDF1438 KB
Canada USA UL Ordinary LocationUL-US-2019259-3 / UL-CA-2015551-3ALLPDF288 KB
EU PTB ATEX ia 2G, 1G, 1D s. certificatePTB 00 ATEX 2048 XALLPDF12880 KB
Japan CML Ex iaCML 23JPN2306XALLPDF307 KB
United Arab Emirates SGS Ex ia24-06-114914/E24-06-118752/NB0002ALLPDF849 KB
United Kingdom CML UKEX Category I M2 UKEX Category II 2 G UKEX Category II 1 D UKEX Category II 1 GCML 21UKEX21166XALLPDF541 KB
Worldwide PTB IECEx iaIECEx PTB 11.0037XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-5066BALLPDF1326 KB
UK Declaration of Conformity (P+F)TDOC-6554AENGENGPDF1319 KB

Produkty powiązane: NCB8-18GM40-N0-10M-OG

Accessories

Universal mounting bracket for cylindrical sensors with a diameter of 5 ... 30 mmfa

Mounting flange, 18 mm, Retainer for all cylindrical sensors with M18 thread, Simple installation and exact setting, Large sensing range (max. 20 mm)fa
Mounting Bracket with swivel nutfa
Plastic mounting adapter, 18 mmfa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont z technologią aktywnego ekranowania

Czujniki indukcyjne VariKont z technologią aktywnego ekranowania zapewniają duże odległości przełączania, niezależnie od warunków instalacji i otaczającego materiału. Skorzystaj z prostszej konstrukcji sprzętu i obniżonych kosztów!

Indukcyjne czujniki bezpieczeństwa SIL 2 PL d

Dzięki temu, że indukcyjne czujniki bezpieczeństwa SIL 2/PL d nie mają martwej strefy, przesyłanie danych może odbywać się bez minimalnej odległości między czujnikiem a obiektem docelowym. Odkryj ofertę zoptymalizowaną pod kątem wymagających środowisk.