Opis produktu |
---|
Gateway module for fieldbus power hub for PROFINET to PROFIBUS PA communication |
General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Supply | ||
Rated voltage | 19.2 ... 35 V SELV/PELV | |
Rated current | typ. 135 mA | |
Power dissipation | approx. 3.5 W | |
Fieldbus connection | ||
Number of segments | 4 | |
Number of devices per segment | max. 32 | |
Fieldbus type | PROFIBUS PA | |
Ethernet Interface | ||
Number of ports | 2 | |
Protocol | PROFINET | |
Ethernet Interface | Connector plug , 2x RJ45 | |
Transfer rate | 100 MBit/s | |
Redundancy | Ring (MRP) , System S2 | |
Indicators/operating means | ||
LED ETH1 LINK 2 | green: link status | |
LED ETH1 ACT | yellow: activity status | |
LED ETH2 LINK | green: link status | |
LED ETH2 ACT | yellow: activity status | |
LED ERR | red 2 Hz flashing: Ethernet error | |
LED Seg 1...4 | red 2 Hz flashing: PA error, red and LED DP/ERR red: MAU error | |
LED PWR | green: Power on | |
LED DP/ERR | red 2 Hz flashing: DP error ; red: Hardware error | |
LED Red. | yellow: redundant operation primary device ; yellow 2 Hz flashing: synchronization or redundancy not available | |
Galvanic isolation | ||
CH/PROFIBUS DP | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
PROFIBUS DP/Supply | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
CH/CH | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
CH/Ethernet | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
All circuits/FE | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
Ethernet/Supply | functional insulation acc. to IEC 61010, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) vertically mounted , -40 ... 70 °C (-40 ... 158 °F) horizontally mounted | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | 250 g | |
Dimensions | ||
Height | 106 mm | |
Width | 40 mm | |
Depth | 128 mm | |
Mounting | motherboard mounting | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 15 ATEX 7735 X | |
Marking | II 3 G Ex ec IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 | |
International approvals | ||
IECEx approval | IECEx TUR 16.0007X | |
Approved for | Ex ec IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | pending | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242610 |
ETIM 9.0 | EC001600 |
ETIM 8.0 | EC001600 |
ETIM 7.0 | EC001600 |
ETIM 6.0 | EC001600 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
The PROFINET to PROFIBUS PA gateway integrates communication of 4 PA segments into PROFINET I/O systems. The gateway is part of the FieldConnex ® Power Hub system. The gateway operates with power supply modules connected to the same or a separate motherboard.
The gateway provides a PA master for each segment and thus enables short bus cycle times.
One single gateway supports S2 system redundancy and ring redundancy.
A complete toolchain supports the engineering for system integration. A gateway device type manager (DTM) and a webserver enable access to both status and diagnostics of the gateway. The gateway DTM enables communication for parameterization, diagnostics, and status information to PROFIBUS PA devices through vendors’ DTMs. A library of STEP 7 software modules for integration into Siemens PCS7 is available.
The PROFINET gateway is an ideal solution for new plants and for upgrading existing PROFIBUS PA installations from PROFIBUS DP to PROFINET.
Literature | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB | |
Application Report - Fieldbus Power Supply Compatible with Process Industry Applications | ENG | 229 KB | |
FieldConnex® PROFINET/PROFIBUS-PA Gateway Driver Library for PCS7, flyer | ENG | 437 KB |
Product information | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Software Licence Information | ENG | 241 KB | |
Brief Instructions | |||
Firmware release information | ENG | 55 KB | |
Safety and Security Documentation | |||
Instrukcja obsługi | POL | 163 KB | |
Manuals | |||
PROFINET Manual for use with HD2-FB*, MB-FB*.GEN, MBHD-FB*.GEN, MBHD-FB-D-4R.GEN, MB-FB-GT, MB-FB-GTR | ENG | 4416 KB | |
Software Information | |||
Release Notes - DTM Collection FieldConnex | ENG | 203 KB | |
Release Notes for Pepperl+Fuchs PROFINET GSD-Generator for PROFINET PA Segment Coupler HD2-GTR-4PA.PN | ENG | 194 KB | |
EULA Pepperl+Fuchs Discovery and Configuration Tool | ENG | 57 KB | |
End-user software license agreement (EULA) PROFINET GSD Generator for HD2-GTR-4PA.PN | ENG | 41 KB |
Certificates | Nr. certyfikatu | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|---|
Canada FM | FM19CA0106X | ALL | 1000 KB | |
China SITIIAS CCC Ex Certificate | 2020322310003529 (Singapore) | ALL | 1094 KB | |
Europe TUV Rheinland ATEX Category 3 | TÜV 15 ATEX 7735X | ALL | 185 KB | |
TUV Rheinland IECEx Certificate of Conformity Zone 2 | IECEx TUR 16.0007X | ALL | LINK | --- |
US FM | FM19US0204X | ALL | 936 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2643B | ALL | 1040 KB |
Device Description Files/Drivers | Informacja o wersji | Typ pliku | Rozmiar pliku |
---|---|---|---|
PROFINET GSD Generator for HD2-GTR-4PA.PN / PROFINET GSD-Generator für HD2-GTR-4PA.PN | 1.0.5.2968 | ZIP | 1667 KB |
DTM Collection FieldConnex / DTM Collection FieldConnex | 1.9.0.2268 | ZIP | 35363 KB |
Firmware | |||
Firmware / Firmware | ZIP | 4626 KB | |
Software Tools | |||
Pepperl+Fuchs Discovery and Configuration Tool (PFDCT) / Pepperl+Fuchs Discovery and Configuration Tool (PFDCT) | 2.4.0.412 | ZIP | 4773 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|
Usługa informacyjna RSS do aktualizacji PANOS
Otrzymuj najnowsze informacje o nowych aktualizacjach oprogramowania PANOS, czyli systemu operacyjnego do przełączników Ethernet-APL: Dzięki naszemu kanałowi RSS będziesz otrzymywać powiadomienia e-mail na swoją skrzynkę poczty przychodzącej po każdym wypuszczeniu nowej aktualizacji.