General specifications |
Node type | A/B node |
AS-Interface specification | V2.1 |
Required gateway specification | ≥ V2.1 |
UL File Number | E223772 |
Indicators/operating means |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of outputs |
LED PWR | AS-Interface voltage; LED green |
LED AUX | ext. auxiliary voltage UAUX ; LED green |
LED IN | switching state (input); 4 LED yellow |
LED OUT | Switching state (output); 2 LED yellow |
Electrical specifications |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 30 mA |
Protection class | III |
Current loading capacity | 2 A (IAUX) |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input |
Number/Type | 4 inputs for mechanical contacts or 3-wire sensors (PNP), DC |
Supply | from external auxiliary voltage UAUX |
Input current | 3 mA (typically) |
Switching point | according to DIN EN 61131-2 (type 1) |
| 0 (unattenuated) | ≤ 0.5 mA |
| 1 (attenuated) | ≥ 2 mA |
Signal delay | < 2 ms (input/AS-Interface) |
Signal frequency | ≤ 250 Hz |
Output |
Number/Type | 2 electronic outputs, PNP, overload and short-circuit proof |
Supply | from external auxiliary voltage UAUX |
Voltage | ≥ (UAUX - 0.5 V) |
Current | 1 A per output , 2 A per module |
Usage category | DC-13 |
Galvanic isolation |
Input/Output | none |
Input/AS-Interface | Basic insulation, rated insulation voltage 120 V DC |
Output/AS-Interface | Basic insulation, rated insulation voltage 120 V DC |
Directive conformity |
Electromagnetic compatibility | observe notices on the certificate of conformity. |
| Directive 2014/30/EU | EN 62026-2:2013 |
Standard conformity |
Galvanic isolation | EN 60947-1:2007 |
Degree of protection | EN 60529:2000 |
Mech. capacity | EN 60068-2-6:2008, EN 60068-2-27:1995 |
Input | EN 61131-2:2007 |
Usage category | EN 60947-5-1:2005 |
Emitted interference | EN 61000-6-4:2001 |
AS-Interface | EN 62026-2:2013 |
Noise immunity | EN 61326-1:2006 |
Programming instructions |
Profile | S-7.A.E |
IO code | 7 |
ID code | A |
ID1 code | 7 |
ID2 code | E |
Data bits (function via AS-Interface) | InputOutput |
| D0 | IN1 O1 |
| D1 | IN2 O2 |
| D2 | IN3 - |
| D3 | IN4 - |
Parameter bits (programmable via AS-i) | function |
| P0 | not used |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Ambient conditions |
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
Altitude | ≤ 2000 m above MSL |
Pollution degree | 3 |
Mechanical specifications |
Degree of protection | IP67 |
Connection | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
Material | |
| Housing | PBT |
Mass | approx. 100 g |
Tightening torque, cable gland | 0.4 Nm |
Mounting | Mounting plate |