General specifications |
Node type | Standard node |
AS-Interface specification | V3.0 |
Required gateway specification | ≥ V2.0 |
Profile | S-7.0 |
| IO code | 7 |
| ID code | 0 |
| ID1 code | F |
| ID2 code | E |
UL File Number | E223772 |
Indicators/operating means |
LED PWR/FAULT | dual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply or outputs |
LED AUX | ext. auxiliary voltage UAUX ; LED green |
LED IN | switching state (input); 4 LED yellow |
LED OUT | Switching state (output); 4 LED yellow |
Electrical specifications |
Auxiliary voltage (output) | 24 V DC ± 15 % PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 30 mA (without sensors) / max. 230 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
Supply | from AS-Interface |
Voltage | 21 ... 31 V |
Current loading capacity | ≤ 200 mA (TB ≤ 40 °C), ≤ 160 mA (TB ≤ 60 °C), short-circuit protected |
Input current | ≤ 9 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
| 0 (unattenuated) | ≤ 3 mA |
| 1 (attenuated) | ≥ 5 mA |
Output |
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof |
Supply | from external auxiliary voltage UAUX |
Voltage | ≥ (UAUX - 0.5 V) |
Current | 1 A per output, 4 A total |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
Standard conformity |
Degree of protection | EN 60529:2000 |
Fieldbus standard | EN 62026-2:2013 |
Input | EN 61131-2:2007 |
Emitted interference | EN 61000-6-4:2007 |
AS-Interface | EN 62026-2:2013 |
Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 |
Ambient conditions |
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
Altitude | ≤ 2000 m above MSL |
Pollution degree | 3 |
Mechanical specifications |
Degree of protection | IP65 |
Connection | cable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs:M12 x 1.5 cable glands and cage tension spring terminals |
Material | |
| Housing | PA 6 GF30 |
Mass | 350 g |
Tightening torque, housing screws | 0.8 Nm |
Dimensions | |
| Height | 71 mm |
| Width | 90 mm |
| Length | 102 mm |
Mounting | DIN rail or screw mounting |