General specifications |
Node type | A/B node |
AS-Interface specification | V3.0 |
Required gateway specification | ≥ V2.1 |
Profile | S-0.A.2 |
| IO code | 0 |
| ID code | A |
| ID1 code | 7 |
| ID2 code | 2 |
UL File Number | E223772 |
Indicators/operating means |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor supply |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
LED IN | switching state (input); 4 LED yellow |
Electrical specifications |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 40 mA (without sensors) / max. 240 mA |
Protection class | III |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral |
Input |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
Supply | from AS-Interface |
Voltage | 21 ... 31 V |
Current loading capacity | ≤ 200 mA, overload and short-circuit protected |
Input current | ≤ 8 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
| 0 (unattenuated) | ≤ 2 mA |
| 1 (attenuated) | ≥ 6 mA |
Signal delay | < 1 ms (input/AS-Interface) |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 62026-2:2013 |
Standard conformity |
Degree of protection | EN 60529:2000 |
Fieldbus standard | EN 62026-2:2013 |
Input | EN 61131-2 |
Emitted interference | EN 61000-6-4:2007 |
AS-Interface | EN 62026-2:2013 |
Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Altitude | ≤ 2000 m above MSL |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Pollution degree | 3 |
Mechanical specifications |
Degree of protection | IP67 |
Connection | cable piercing method flat cable yellow inputs: M12 round connector |
Material | |
| Housing | PBT |
Mass | 200 g |
Tightening torque, cable gland | 0.4 Nm |
Dimensions | |
| Height | 35 mm |
| Width | 57.4 mm |
| Length | 118 mm |
Mounting | Mounting plate |