General specifications |
Node type | A/B node |
AS-Interface specification | V2.1 |
Required gateway specification | ≥ V2.1 |
UL File Number | E223772 |
Indicators/operating means |
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of sensor power supply or outputs |
LED PWR | AS-Interface voltage; LED green |
LED AUX | ext. auxiliary voltage UAUX ; LED green |
LED IN | switching state (input); 2 LED yellow |
LED OUT | Switching state (output); 2 LED yellow |
Electrical specifications |
Auxiliary voltage (output) | 20 ... 30 V DC PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 40 mA (without sensors) / max. 140 mA |
Protection class | III |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) |
Input |
Number/Type | 2 inputs for 2- or 3-wire sensors (PNP), DC option 1 input for 4-wire sensor (PNP), DC |
Supply | from AS-Interface |
Voltage | 21 ... 31 V |
Current loading capacity | ≤ 100 mA (TB ≤ 40 °C), ≤ 75 mA (TB ≤ 60 °C), overload-proof and short-circuit protected |
Input current | ≤ 8 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
| 0 (unattenuated) | ≤ 2 mA |
| 1 (attenuated) | ≥ 4 mA |
Output |
Number/Type | 2 electronic outputs, PNP overload and short-circuit proof |
Supply | from external auxiliary voltage UAUX |
Voltage | ≥ (UAUX - 0.5 V) |
Current | 1 A per output |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001 |
Standard conformity |
Degree of protection | EN 60529:2000 |
Input | EN 61131-2:2007 |
Emitted interference | EN 61000-6-4:2001 |
AS-Interface | EN 62026-2:2013 |
Noise immunity | EN 61000-6-2:2001 |
Programming instructions |
Profile | S-B.A.2 |
IO code | B |
ID code | A |
ID1 code | 7 |
ID2 code | 2 |
Data bits (function via AS-Interface) | InputOutput |
| D0 | - OUT1 |
| D1 | - OUT2 |
| D2 | IN3 - |
| D3 | IN4 - |
Parameter bits (programmable via AS-i) | function |
| P0 | not used |
| P1 | not used |
| P2 | not used |
| P3 | not used |
Ambient conditions |
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
Altitude | ≤ 2000 m above MSL |
Pollution degree | 3 |
Mechanical specifications |
Degree of protection | IP67 |
Connection | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
Material | |
| Housing | PBT |
Mass | 100 g |
Tightening torque, cable gland | 0.4 Nm |
Mounting | Mounting plate |