Atendimento ao Cliente da Divisão de Sensores Industriais
Rede de Atendimento - Divisão de Proteção Contra Explosão

AS-Interface I/O module VBA-3E3A-G20-ZEL/E2L-P1

VBA-3E3A-G20-ZEL/E2L-P1
  • A/B node with extended addressing possibility for up to 62 nodes
  • Inputs for 3-wire sensors
  • Power supply of the inputs and outputs from the external auxiliary voltage
  • Connection of actuators and sensors via cable outputs with M8 connectors
  • Communication monitoring
  • Function display for bus, external auxiliary voltage, in- and outputs
  • Cable piercing method with gold plated contact pins

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Faça o download das folhas de dados em PDF:


Folhas de dados: Dados técnicos do  VBA-3E3A-G20-ZEL/E2L-P1

Descrição do Produto
G20 module for digital inputs/outputs, 3 inputs and 3 outputs
General specifications
Node typeA/B node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
ProfileS-7.A.E
IO code7
ID codeA
ID1 code7
ID2 codeE
UL File NumberE223772 "For use in NFPA 79 Applications only"
MTBF110 a
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0 or overload of sensor power supply or overload of outputs or external auxiliary voltage UAUX missing
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 3 LED yellow
LED OUTSwitching state (output); 3 LED yellow
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 35 mA
Input
Number/Type3 Inputs for 3-wire sensors (PNP), DC
Supplyfrom external auxiliary voltage UAUX
Current loading capacity500 mA , overload and short-circuit protected
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2
0 (undamped) ≤ 0.5 mA
1 (damped) ≥ 2.0 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type3 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Voltage≥ (UAUX - 0.5 V)
Current2 A per output
TB ≤ 40 °C: 6 A total
TB ≤ 60 °C: OUT1+OUT2 max. 3 A, OUT3 max. 2 A
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP54 according to EN 60529
ConnectionAS-Interface, AUX: Insulation piercing technology
Yellow flat cable/black flat cable
Inputs/outputs: M8 round plug connector in accordance with EN 61076-2-104
Inputs: LF004-GS1-A (4-pin, bushing contacts, screw lock, A-coded)
Matching connector: LM004-Gx1-A or similar
Outputs: NF003-SS1-A (3-pin, bushing contacts, snap lock, A-coded)
Matching connector: NM003-Sx1-A or similar
Mass260 g
Dimensions
Height27.5 mm
Width131.5 mm
Length54 mm
Mounting2 clips with ∅ 8 mm drill hole
Cable length1 m
NoteThe flat cable routing is designed for 100 actuation cycles

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-3E3A-G20-ZEL/E2L-P1

Informative Literature: VBA-3E3A-G20-ZEL/E2L-P1

Selecione o Idioma:
LiteratureIdiomaTipo de ArquivoTamanho do Arquivo
Portfolio overview G20 modules / Portfolio-Übersicht G20-ModuleALLPDF121 KB

Product Documentation: VBA-3E3A-G20-ZEL/E2L-P1

Selecione o Idioma:
Brief InstructionsIdiomaTipo de ArquivoTamanho do Arquivo
Instruction leaflet / BeipackzettelALLPDF225 KB

Design / Simulation: VBA-3E3A-G20-ZEL/E2L-P1

Selecione o Idioma:
CADIdiomaTipo de ArquivoTamanho do Arquivo
CAD 3-D / CAD 3-DALLSTP1720 KB

Approvals: VBA-3E3A-G20-ZEL/E2L-P1

Selecione o Idioma:
CertificatesNúmero do CertificadoIdiomaTipo de ArquivoTamanho do Arquivo
US CA ULCoC UL-US-L223772-13-82803102-1ALLPDF175 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4822CALLPDF109 KB

Software: VBA-3E3A-G20-ZEL/E2L-P1

Selecione o Idioma:
Device Description Files/DriversInformaçõesTipo de ArquivoTamanho do Arquivo
Add-On Instructions for RSLogix/Studio 5000 / Add-On-Befehle für RSLogix/Studio 50004/2020ZIP23385 KB

Produtos Relacionados: VBA-3E3A-G20-ZEL/E2L-P1

Accessories

AS-Interface Handheld with accessoryfa
Adapter cable G20 module/hand-held programming devicefa
Mounting aidfa
Voltage limiter G10fa
Download gratuito: Documento técnico: protocolos de comunicação baseados em TCP (PDF)

Este documento técnico gratuito em PDF compara os diferentes protocolos de comunicação baseados em TCP (AMQP, OPC UA, MQTT, REST API) que alcançaram muito sucesso e hoje são considerados os ativadores da Internet Industrial das Coisas e da Indústria 4.0. Faça o download gratuito agora mesmo!

Módulo do gabinete do interruptor KE5 da Interface AS – Manuseio simples e capacidade de gerenciamento aprimorada

O design exclusivo do invólucro do novo módulo de gabinete do interruptor KE5 permite uma visibilidade distinta e simplifica a montagem, o cabeamento e a manutenção dentro dos gabinetes do interruptor e caixas de junção.

Linha de Produtos Interface AS

Conheça nossa linha completa de produtos Interface AS.