General specifications |
Node type | Standard node |
AS-Interface specification | V2.1 |
Required gateway specification | ≥ V2.0 |
Profile | S-7.0 |
| IO code | 7 |
| ID code | 0 |
| ID1 code | F |
| ID2 code | E |
UL File Number | E106378 |
Indicators/operating means |
LED FAULT | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply |
LED INT | Internal input supply active; LED green |
LED PWR | AS-Interface voltage; LED green |
LED IN | switching state (input); 4 LED yellow |
LED OUT | Switching state (output); 4 LED yellow |
Electrical specifications |
Auxiliary voltage (input) | 12 ... 30 V DC PELV |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface |
Rated operating current | ≤ 35 mA (no sensors)/max. 210 mA |
Surge protection | O1 ... O4: Over voltage category II UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) |
Input |
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC |
Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) |
Voltage | 21 ... 31 V DC (INT) |
Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) |
Input current | ≤ 8 mA (limited internally) |
Switching point | according to DIN EN 61131-2 (Type 2) |
| 0 (unattenuated) | ≤ 2 mA |
| 1 (attenuated) | ≥ 4 mA |
Signal delay | < 2 ms (input/AS-Interface) |
Output |
Number/Type | 4 relay outputs, normally open |
Supply | none |
Nominal load | |
| Per contact | 2 A / 30 V DC (acc. UL max. 24 V DC); 2 A / 253 V AC |
| Per module | 8 A |
Control circuit | ≤ 8 mA per relay (from AS-Interface) |
Switching delay | < 10 ms (AS-Interface/contact) |
Usage category | DC-13 and AC-14 |
Switching | |
| Mechanical | 5 x 106 |
| Electrical | 0.2 x 106 (250 V AC, 2 A, cos φ = 0.4) |
Galvanic isolation |
Input/Output | safe isolation, rated insulation voltage 300 V AC |
Input/AS-Interface | Switch position INT: None Switch position EXT: reinforced insulation, rated insulation voltage 66 V DC |
Output/Output | basic insulation, rated insulation voltage 300 V AC |
Output/AS-Interface | safe isolation, rated insulation voltage 300 V AC |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61326:2003 |
Low voltage | |
| Directive 73/23/EEC | EN 60947-1:2007 |
Standard conformity |
Galvanic isolation | EN 60664-1:2007 |
Electromagnetic compatibility | NAMUR NE 21: 1998-08 |
Degree of protection | EN 60529:2000 |
Fieldbus standard | EN 62026-2:2013 |
AS-Interface | EN 62026-2:2013 |
Ambient conditions |
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Relative humidity | 85 % , noncondensing |
Climatic conditions | For indoor use only |
Altitude | ≤ 2000 m above MSL |
Pollution degree | 2 |
Mechanical specifications |
Degree of protection | IP20 |
Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 |
Material | |
| Housing | PA 66-FR |
Mass | 170 g |
Dimensions | |
| Height | 99 mm |
| Width | 22.5 mm |
| Length | 102 mm |
Mounting | DIN mounting rail |
Tightening torque of clamping screws | 0.5 Nm ... 0.6 Nm |