Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Stáhněte si kompletní katalogový list ve formátu PDF:
Popis produktu |
---|
AS-Interface scanner for CompactLogix or MicroLogix 1500 PLC |
General specifications | ||
---|---|---|
AS-Interface specification | V3.0 | |
PLC-Functionality | none | |
Description | AS-Interface scanner for CompactLogix or MicroLogix 1500 PLC | |
Functional safety related parameters | ||
MTTFd | 140 a at 30 °C | |
Indicators/operating means | ||
Display | LC display | |
LED SYS | LED green: Power on | |
LED OK | LED green: AS-Interface network running normally; LED green flashing: Configuration mode; LED red flashing: Peripheral fault; LED red: Configuration error; |
|
LED AS-i ACTIVE | LED green: AS-Interface running normally | |
LED PWR | LED green: Power on | |
LED PRG ENABLE | autom. programming; LED green | |
LED PRJ MODE | projecting mode active; LED yellow | |
LED U AS-i | AS-Interface voltage; LED green | |
Switch SET | Selection and setting of a slave address | |
Button MODE | Mode selection PRJ-operation/save configuration/cursor | |
Electrical specifications | ||
Insulation voltage | ≥ 500 V | |
Capacity factor | Power supply rating of 4 Cannot be farther then 4 cards from main processor or power supply |
|
Rated operating voltage | from backplane | |
Rated operating current | 100 mA from AS-Interface 450 mA from backplane |
|
Interface | ||
Protocol | MicroLogix 1500 or CompactLogix backplane | |
Interface 2 | ||
Interface type | RS 232, serial | |
Connection | ||
AS-Interface | double row terminals, removable | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Electromagnetic compatibility | EN 61000-6-2:2005, EN 61000-6-4:2001, EN 50295:1999 | |
Degree of protection | EN 60529:2000 | |
AS-Interface | EN 62026-2:2013 | |
Shock resistance | EN 61131-2 | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | 420 g | |
Construction type | Mounting into the backplane of a MicroLogix 1500 or CompactLogix PLC |
System | Classcode |
---|---|
ECLASS 13.0 | 27242607 |
ECLASS 12.0 | 27242607 |
ECLASS 11.0 | 27242607 |
ECLASS 10.0.1 | 27242607 |
ECLASS 9.0 | 27242607 |
ECLASS 8.0 | 27242607 |
ECLASS 5.1 | 27242607 |
ETIM 9.0 | EC001603 |
ETIM 8.0 | EC001603 |
ETIM 7.0 | EC001603 |
ETIM 6.0 | EC001603 |
ETIM 5.0 | EC001603 |
UNSPSC 12.1 | 39121535 |
Manuals | Jazyk | Typ souboru | Velikost souboru |
---|---|---|---|
Manual AS-Interface 3.0 Command Interface | ENG | 3265 KB | |
Manual AS-Interface scanner card for MicroLogic 1500 or CompactLogix PLCs | ENG | 5309 KB |
CAD | Jazyk | Typ souboru | Velikost souboru |
---|---|---|---|
DWG CAD files for VBG-MLX/CPLX AS-i card / CAD 2-D | ALL | ZIP | 214 KB |
Device Description Files/Drivers | Informace o uvolnění | Typ souboru | Velikost souboru |
---|---|---|---|
EDS_a / EDS_a | 04/2012 | ZIP | 2 KB |
Software Tools | |||
Example projects, Add-on Instructions, and Description Files for Allen Bradley PLCs and RSLogix 5000 / Software Tool_a | Sep 2013 | ZIP | 4998 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
Bezplatně ke stažení: Oficiální zpráva o komunikačních protokolech založených na protokolu TCP (PDF)
Tato zdarma poskytovaná oficiální zpráva ve formátu PDF porovnává různé komunikační protokoly založené na protokolu TCP (AMQP, OPC UA, MQTT, REST API), které si našly cestu vzhůru a jsou považovány za faktory umožňující používat IIoT a realizovat průmysl 4.0. Získejte zdarma soubor ke stažení hned teď!