Servisní linka pro průmyslové snímače
Servisní linka ochrany před výbuchem

SMART Transmitter Power Supply HiC2027

HiC2027
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Input for 2-wire SMART transmitters and current sources
  • Signal splitter (1 input and 2 outputs)
  • Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V
  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Stáhněte si kompletní katalogový list ve formátu PDF:


Výňatek z katalogového listu: Technická data   HiC2027

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage20 ... 30 V DC bus powered via Termination Board
Ripplewithin the supply tolerance
Rated current≤ 90 mA
Power dissipationapprox. 1.4 W at 20 mA transfer current, 250 Ω in both outputs
Power consumption2 W
Input
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-): sink
SL2: 1a(+), 1b(-), 7a(-): source
Input signal0/4 ... 20 mA
Voltage dropSL2: 1a(+), 1b(-), 7a(-): ≤ 6.1 V at 20 mA
Short-circuit currentSL2: 5a(+), 5b(-): 25 mA
Input resistanceSL2: 5a(+), 5b(-): max. 500 Ω (BRAIN)
(250 Ω load)
Available voltageSL2: 5a(+), 5b(-): ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-), channel 1: source and sink
SL1: 10a(+), 9a(-), channel 2: source and sink
Loadchannel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
Output signal0/4 ... 20 mA or 0/1 ... 5 V
Ripplemax. 50 µA rms
Transfer characteristics
DeviationIout < 20 µA (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V
Influence of ambient temperaturecurrent output: 0.25 µA/K
voltage output: 80 µV/K
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB)
Settling time6 ms
Rise time/fall time2 ms
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLED
Control elementsDIP switch
Factory settingoutput: current source
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 105 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 2 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 13 ATEX 0075 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
InputEx ia
Supply
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
EquipmentSL2: 5a(+), 5b(-)
Voltage25.2 V
Voltage28.2 V
Current93 mA
Power656 mW
Internal capacitance12 nF
Internal inductance0 mH
EquipmentSL2: 1a(+), 1b(-), 7a(-)
Voltage30 V
Current115 mA
Power700 mW
Voltage5 V
Current6.8 mA
Power1.6 mW
Internal capacitance12 nF
Internal inductance0 mH
Output
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateBASEEFA 13 ATEX 0076 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0349 (cULus)
IECEx approval
IECEx certificateIECEx BAS 13.0042X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2027

Product Documentation: HiC2027

Výběr jazyka:
Safety and Security DocumentationJazykTyp souboruVelikost souboru
Návod k poużitíCZEPDF164 KB
Functional Safety ManualENGPDF1950 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2027

Výběr jazyka:
CADJazykTyp souboruVelikost souboru
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---

Approvals: HiC2027

Výběr jazyka:
CertificatesČíslo certifikátuJazykTyp souboruVelikost souboru
Baseefa ATEX Category (M1) ATEX Category (1) GDBaseefa 13 ATEX 0075XALLPDF2118 KB
Baseefa ATEX Category 3 GBaseefa 13 ATEX 0076XALLPDF1482 KB
China SITIIAS CCC Ex Certificate2020322316001405 (Singapore)ALLPDF1332 KB
IECEx Certificate of ConformityIECEx BAS 13.0042XALLLINK---
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20140616 - E106378 RepRef 20140426ALLPDF428 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 21UKEX2941XALLPDF166 KB
Worldwide exida Functional Safety AssessmentP+F 0905-035-R1-C R044 Assessment Report HiC2027 V1 R1ALLPDF831 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF62 KB
Instruction leaflet / Beipackzettel   ALLPDF138 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0471FALLPDF54 KB

Související produkty: HiC2027

Accessory of
System board for Schneider Electric, Tricon CX series by Triconex, For 16-channel universal I/O card 3902(A)X, For 16 modules, Recommended modules: HiC2027 (AI), HiC2027ES (AI), HiC2821 (DI), HiC2831R4 (DI), HiC2841 (DI), HiC2853R4 (DI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: screw terminals, black, Non-hazardous area: Sub-D connector (male), 50-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Universal, Manufacturer: Triconexpa
System board for Schneider Electric, Tricon CX series by Triconex, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2027 (AI), HiC2027ES (AI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: screw terminals, black, Non-hazardous area: ELCO socket, 56-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CX, Safety Integrity Level (SIL): SIL 3pa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.