Servisní linka pro průmyslové snímače
Servisní linka ochrany před výbuchem

Frequency Converter with Trip Values KFU8-UFC-Ex1.D

KFU8-UFC-Ex1.D
  • 1-channel isolated barrier
  • Universal usage at different power supplies
  • Input for NAMUR sensors or dry contacts
  • Input frequency 1 mHz ... 5 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Stáhněte si kompletní katalogový list ve formátu PDF:


Výňatek z katalogového listu: Technická data   KFU8-UFC-Ex1.D

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 23, 24
Rated voltage20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Power dissipation/power consumption≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
ConnectionInput I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input Isensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Pulse duration> 50 µs
Input frequency0.001 ... 5000 Hz
Line fault detectionbreakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input IIstartup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/PassiveI > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current18 V / 5 mA
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
Output I, IIsignal, relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output IIIelectronic output, passive
Contact loading40 V DC
Signal level1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Output IVanalog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Transfer characteristics
Input I
Measuring range0.001 ... 5000 Hz
Resolution0.1 % of the measurement value , ≥ 0.001 Hz
Accuracy0.1 % of the measurement value , > 0.001 Hz
Measuring time< 100 ms
Influence of ambient temperature0.003 %/K (30 ppm)
Output I, II
Response delay≤ 200 ms
Output IV
Resolution< 10 µA
Accuracy< 20 µA
Influence of ambient temperature0.005 %/K (50 ppm)
Galvanic isolation
Input I/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III/start-up overridebasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III/IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Start-up override/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/output IIIbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Height119 mm
Width40 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 99 ATEX 1471
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Supply
Maximum safe voltage253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Input Iterminals 1+, 3-: Ex ia
Voltage Uo10.1 V
Current Io13.5 mA
Power Po34 mW (linear characteristic)
Input IIterminals 13+, 14- non-intrinsically safe
Maximum safe voltage Um40 V (Attention! The rated voltage can be lower.)
Output I, IIterminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
Contact loading253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
Output IIIterminals 19+, 20- non-intrinsically safe
Maximum safe voltage Um40 V (Attention! Um is no rated voltage.)
Output IVterminals 8+, 7- non-intrinsically safe
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
InterfaceRS 232
Maximum safe voltage40 V (Attention! Um is no rated voltage.)
Galvanic isolation
Input I/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012
International approvals
FM approval
Control drawing16-538FM-12
IECEx approval
IECEx certificateIECEx TUN 04.0007
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210128
ECLASS 12.027210128
ECLASS 11.027210128
ECLASS 10.0.127210128
ECLASS 9.027210128
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC002918
ETIM 8.0EC002918
ETIM 7.0EC002918
ETIM 6.0EC002918
ETIM 5.0EC002475
UNSPSC 12.139121007

Details: KFU8-UFC-Ex1.D

Informative Literature: KFU8-UFC-Ex1.D

Výběr jazyka:
LiteratureJazykTyp souboruVelikost souboru
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Frequency Converter Prevents OverloadingENGPDF466 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFU8-UFC-Ex1.D

Výběr jazyka:
Brief InstructionsJazykTyp souboruVelikost souboru
Operator card KF**-UFC-**1.D / Bedienkarte KF**-UFC-**1.DALLPDF849 KB
Safety and Security Documentation
Návod k poużitíCZEPDF160 KB
Functional Safety ManualENGPDF2055 KB
Manuals
ManualENGPDF1757 KB
ManualENGPDF3685 KB
Installation and configuration guide Device Type Manager (DTM)ENGPDF8665 KB

Design / Simulation: KFU8-UFC-Ex1.D

Výběr jazyka:
CADJazykTyp souboruVelikost souboru
CAD 3-D / CAD 3-DALLSTP2721 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ77 KB

Approvals: KFU8-UFC-Ex1.D

Výběr jazyka:
CertificatesČíslo certifikátuJazykTyp souboruVelikost souboru
Australia Test SafeANZEx 17.3006XALLPDF6788 KB
Brasil TUV Rheinland BrazilTÜV 14.0357ALLPDF1122 KB
Canada FMFM22CA0016XALLPDF364 KB
China SITIIAS CCC Ex Certificate2020322316001449 (Singapore)ALLPDF1320 KB
DNV MarineTAA00001WXALLPDF106 KB
Europe TUV Nord ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GTÜV 99 ATEX 1471ALLPDF682 KB
India PESO (India) CCOEA/P/HQ/KA/104/5784 (P478911)ALLPDF75 KB
Japan TIISTC15707ALLPDF1853 KB
Korea KOSHA10-AV4BO-0503ALLPDF263 KB
Korea KOSHA20-AV4BO-0676ALLPDF783 KB
South Africa MASCMASC MS/17-0881ALLPDF700 KB
USA FMCoC 3009603ALLPDF40 KB
Ukraine SERTIS ExSC 21.0646 XALLPDF12351 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 22UKEX2510ALLPDF140 KB
Worldwide TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0007ALLLINK---
exida Functional Safety AssessmentP+F 04/03-15 R016ALLPDF337 KB
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF156 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2760AALLPDF80 KB

Software: KFU8-UFC-Ex1.D

Výběr jazyka:
Device Description Files/DriversInformace o uvolněníTyp souboruVelikost souboru
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 21.4.110.77ZIP---
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB
PACTware 5.0 / PACTware 5.05.0.5.31ZIP44203 KB
PACTware 6.X / PACTware 6.X6.1ZIP335938 KB

Související produkty: KFU8-UFC-Ex1.D

Matching System Components
Device DTM, For K-, E- and H-System, Frame application, like e. g. PACTware, must be installed separatelypa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Isolated USB interface cable, Used with K-, E- and H-System devices, Used with PACTwarepa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Accessories
1-channel, Dry contact input, For line fault detection (LFD)pa
1-channel, Precision resistor, Conversion of 0 mA ... 20 mA/0 V ... 5 Vpa
1-channel, Precision resistor, Conversion of 4 mA ... 20 mA/2 V ... 10 Vpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Centrum funkční bezpečnosti od společnosti Pepperl+Fuchs

Stovky produktů s vyhodnocením SIL/PL, bezplatné nástroje a brožury na jednom místě: centrum funkční bezpečnosti je vaším výchozím bodem, když potřebujete implementovat bezpečnostní funkce.

K-System by Pepperl+Fuchs: Globally certified protection for people, plants, and the environment!

The largest portfolio of its kind: K-System components and systems are established in process industries around the world. Learn more!