Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
A teljes adatlap letöltése PDF formátumban:
Termék leírása |
---|
G11 analog module, 2 analog inputs |
General specifications | ||
---|---|---|
Node type | Standard node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
Profile | S-7.3.D | |
IO code | 7 | |
ID code | 3 | |
ID1 code | F | |
ID2 code | D | |
UL File Number | E223772 | |
Indicators/operating means | ||
LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
|
LED ANALOG | status of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range |
|
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED INT/EXT | status display input supply; LED green green: input supply from AS-Interface off: input supply from auxiliary voltage |
|
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 60 mA (without sensors) / max. 200 mA | |
Protection class | III | |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) | |
Input | ||
Number/Type | 2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V Pt100: -200 ... 850 °C |
|
Supply | from AS-Interface (switch position INT, default settings) or auxiliary voltage UEXT (switch position EXT) | |
Current loading capacity | ≤ 140 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA from external auxiliary voltage UAUX , overload and short-circuit protected |
|
Input resistance | current input: max. 70 Ω voltage input: 100 kΩ |
|
Measuring current | for Pt100: approx. 1 mA | |
Accuracy | Voltage/current: 0.1% of accumulated value Pt100: 0.1% of indicated temperature [°C] + 0.3 °C |
|
Resolution | 16 Bit / 1 µA (current input) or 16 bit / 1 mV (voltage input) or 16 Bit / 0.1°C (temperature input) |
|
Temperature influence | Voltage/current: 20 ppm/K Pt100: (10 ppm of indicated temperature [°C] + 0.003 °C)/K |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2:2007 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 3 | |
Mechanical specifications | ||
Degree of protection | IP68 / IP69K | |
Connection | AS-Interface/UAUX: cable piercing method, flat cable yellow/flat cable black Inputs: M12 round connector |
|
Material | ||
Housing | PBT PC | |
Mounting screw | Stainless steel 1.4305 / AISI 303 | |
Mass | 200 g | |
Tightening torque, housing screws | 1.8 Nm | |
Tightening torque, cable gland | 0.4 Nm | |
Dimensions | ||
Height | 35 mm | |
Diameter | 85 mm | |
Mounting | Mounting plate |
System | Classcode |
---|---|
ECLASS 13.0 | 27242601 |
ECLASS 12.0 | 27242601 |
ECLASS 11.0 | 27242601 |
ECLASS 10.0.1 | 27242601 |
ECLASS 9.0 | 27242601 |
ECLASS 8.0 | 27242601 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001596 |
ETIM 8.0 | EC001596 |
ETIM 7.0 | EC001596 |
ETIM 6.0 | EC001596 |
ETIM 5.0 | EC001596 |
UNSPSC 12.1 | 39121535 |
The VBA-2E-G11-I/U/PT100-* analog module has two analog inputs which can be current input (4 mA to 20 mA), voltage input (0 to 10 V) or resistance thermometer input (-200 to 850 °C).
The power supply to the measurement value generators takes place depending on the position of the internal slide switch, via AS-Interface or through auxiliary voltage. The choice of input supply is displayed via the INT/EXT LED.
Measured value conversion and data transfer is provided asynchronously according to the AS-Interface profile 7.3. The resolution of the analog values is 16 bit with a value range of 4000 to 20000 (current input), 0 to 10000 (voltage input) and - 200 °C to 850 °C (resistance thermometer input). Network interference can be eliminated with a configurable filter (50 Hz/60 Hz) in the A/D converter.
Note:
An overload of the internal input supply is also reported to the AS-Interface master via the 'peripheral fault' function. Communication via the AS-Interface continues.
Literature | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Application Report - Automating Material Handling Systems for Airports with AS-Interface | ENG | 272 KB |
Brief Instructions | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 679 KB | |
Manuals | |||
Manual VBA-2E-G11-I/U/PT100-* | ENG | 2561 KB |
CAD | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 4756 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Tanúsítvány sz. | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|---|
Canada, USA UL | CoC 20141115-E223772 | ALL | 342 KB | |
EU Ecolab Material Resistance | ECOLAB | ALL | 1797 KB | |
Worldwide AS-International Association AS-Interface | 94201 | ALL | 376 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2931B | ALL | 119 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
AS-Interfész KE5 kapcsolószekrény modul – Egyszerű kezelés és továbbfejlesztett kezelhetőség
Az új KE5 kapcsolószekrény modul egyedülálló házkialakítása jó láthatóságot biztosít, valamint leegyszerűsíti a felszerelést, vezetékezést és a szekrényeken belüli karbantartást.