Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
A teljes adatlap letöltése PDF formátumban:
Termék leírása |
---|
KE switch cabinet module 4 inputs (PNP) |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.0 | |
UL File Number | E223772 | |
Indicators/operating means | ||
LED FAULT | Fault display; Red LED red: Communication fault or address is 0 red, flashing: Overload, internal input supply |
|
LED INT | Internal input supply active; LED green | |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
|
LED IN | switching state (input); 4 LED yellow | |
Electrical specifications | ||
Auxiliary voltage (input) | 12 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 30 mA (without sensors) / max. 180 mA | |
Protection class | III | |
Surge protection | UEXT, Ue: Over voltage category III, safe isolated power supplies (PELV) | |
Input | ||
Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC | |
Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) | |
Voltage | 21 ... 31 V DC (INT) | |
Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) | |
Input current | ≤ 9 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 (Type 2) | |
0 (unattenuated) | ≤ 3 mA | |
1 (attenuated) | ≥ 5 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2:2004 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-0.A.0 | |
IO code | 0 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 0 | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | not used | |
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
|
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
|
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | removable terminals rated connection capacity: rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2 for multiple-wire connection with two wires of equal cross-section: flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2 |
|
Material | ||
Housing | PA 66-FR | |
Mass | 150 g | |
Dimensions | ||
Height | 99 mm | |
Width | 22.5 mm | |
Length | 102 mm | |
Mounting | DIN mounting rail | |
Tightening torque of clamping screws | 0.5 Nm ... 0.6 Nm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
The AS-Interface I/O module VBA-4E-KE-ZEJQ is a control cabinet module with 4 inputs. The housing is only 22.5 mm wide and takes up little space in the control cabinet. The module is mounted by snapping onto the 35-mm DIN rail in compliance with EN 50022. The connection is made via plug-in terminals. Four-terminal blocks (black) are used for the inputs. The connection of AS Interface is via a 2-terminal block yellow.
The supply to the inputs and the connected sensors can be fed either from the internal supply of the module (from the AS-Interface) or via an external voltage source. A switch located on the side of the module changes the supply source. The choice of internal input supply is displayed via the LED INT. The LED IN display the current switching status of the relevant inputs.
Note:
Filters that suppress pulses with a duration of 2 ms or less at the inputs can be connected via the parameter P1.
Parameter P2 activates the synchronous mode. A signal indicating an overload of the internal input supply is transmitted to the AS-Interface master via the 'peripheral fault' function. Communication via the AS-Interface continues even if a peripheral fault is set.
Brief Instructions | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 578 KB |
CAD | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 112 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Tanúsítvány sz. | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|---|
Canada UL cUL | E106378 cUL (QUZW7) | ALL | LINK | --- |
USA UL | E106378 UL (QUZW) | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 86703 | ALL | 367 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-1009C | ALL | 115 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
AS-Interfész KE5 kapcsolószekrény modul – Egyszerű kezelés és továbbfejlesztett kezelhetőség
Az új KE5 kapcsolószekrény modul egyedülálló házkialakítása jó láthatóságot biztosít, valamint leegyszerűsíti a felszerelést, vezetékezést és a szekrényeken belüli karbantartást.