Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
A teljes adatlap letöltése PDF formátumban:
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 360 Ω | |
Series resistance | max. 380 Ω | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2; 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6; 7, 8 | |
Working voltage | ||
Supply loop | max. 7.7 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Relative humidity | max. 75 % , without condensation | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 116 mm (0.5 x 4.5 x 4.6 inch) (W x H x D) | |
Height | 115 mm | |
Width | 12.5 mm | |
Depth | 116 mm | |
Construction type | modular terminal housing , see system description | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
Voltage | 8.7 V | |
Current | 25 mA | |
Power | 50 mW | |
Supply | ||
Maximum safe voltage | 250 V | |
Series resistance | min. 352.8 Ω | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx BAS 09.0142 IECEx BAS 17.0091X |
|
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27211016 |
ECLASS 12.0 | 27211016 |
ECLASS 11.0 | 27211016 |
ECLASS 10.0.1 | 27219001 |
ECLASS 9.0 | 27219001 |
ECLASS 8.0 | 27219001 |
ECLASS 5.1 | 27210702 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC002653 |
UNSPSC 12.1 | 39121018 |
The Zener Barrier prevents the transfer of unacceptably high energy from the safe area into the hazardous area.
The zener diodes in the Zener Barrier are connected in the reverse direction. The breakdown voltage of the diodes is not exceeded in normal operation. If this voltage is exceeded, due to a fault in the safe area, the diodes start to conduct, causing the fuse to blow. The Zener Barrier has alternating polarities, i. e. interconnected zener diodes are employed and one side is grounded. The Zener Barrier can be used for both alternating voltage signals and direct voltage signals.
This high power version has a smaller serial resistance and therefore provides higher voltage to the field device.
Depending on the application, increased or decreased intrinsic safety parameters apply for serial or parallel connection. For the detailed parameters refer to the Zener Barrier certificate. Application examples can be found in the system description of the Zener Barriers.
Safety and Security Documentation | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Használati útmutató | HUN | 229 KB | |
Functional Safety Manual | ENG | 1972 KB | |
Manuals | |||
System Manual | ENG | 1203 KB |
CAD | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 951 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
EPLAN macros Z-System devices (EMA) / EPLAN-Makros Geräte Z-System (EMA) | ALL | ZIP | 2338 KB |
Certificates | Tanúsítvány sz. | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|---|
Baseefa IECEx Certificate of Conformity | IECEx BAS 17.0091X | ALL | LINK | --- |
Baseefa IECEx Certificate of Conformity | IECEx BAS 09.0142 | ALL | LINK | --- |
Brasil TUV Rheinland Brazil | TÜV 14.0362 | ALL | 1465 KB | |
China SITIIAS CCC Ex Certificate | 2020322316002775 (Bintan) | ALL | 21091 KB | |
DNV Marine | TAA00001WX | ALL | 106 KB | |
Europe Baseefa Group I (M1) ATEX Category (1) GD | BAS 01 ATEX 7005 | ALL | 8525 KB | |
Europe TUV Nord II 3 G ATEX Category 3 G | TÜV 99 ATEX 1484X | ALL | 1460 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/6091 (P576843) | ALL | 105 KB | |
Japan TIIS | TC22539 | ALL | 1794 KB | |
Korea KOSHA | 09-AV4BO-0228/0229/0230 | ALL | 717 KB | |
SIMTARS IECEx Certificate of Conformity | IECEx SIM 06.0012X | ALL | LINK | --- |
South Africa MASC | MASC MS/17-0887 | ALL | 799 KB | |
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378 | CoC 20190321 - E106378 RepRef 19960425 | ALL | 252 KB | |
USA FM | FM 17 US 0370 | ALL | 416 KB | |
USA UL | E106378 UL (QUZW) | ALL | LINK | --- |
Worldwide Pepperl+Fuchs Functional Safety Assessment | CERT-5207 | ALL | 575 KB | |
Control Drawings | ||||
Control drawing UL / Control drawing UL | ALL | 170 KB | ||
Control drawing FM / Control drawing FM | ALL | 167 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-0060EHUN | HUN | 196 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-5844 | ALL | 98 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|