Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
A teljes adatlap letöltése PDF formátumban:
Termék leírása |
---|
Surge protector, pluggable module for spur installation on segment protector |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Installation in hazardous area | Zone 1 / Div. 1 | |
Fieldbus connection | ||
Self current consumption | max. 6 mA (for version SCP-LBF-IA1.36.IE.1) , max. 0 mA (for version SCP-LBF-IA1.36.IE.0) | |
Indicators/operating means | ||
LED ERR | green flashing: status OK , red flashing: maintenance required (for version SCP-LBF-IA1.36.IE.1) | |
Electrical specifications | ||
Rated voltage | 36 V | |
Rated current | 250 mA | |
Voltage protection level | ||
Line/Line | max. 50 V category B2 10/700 µsec , 25 A max. 53 V category C1 8/20 µsec , 150 A max. 55 V category C2 8/20 µsec , 150 A max. 46 V category C3 1 kV/µsec , 10 A |
|
Line/Earth | max. 980 V category B2 10/700 µsec , 50 A per line max. 800 V category C1 8/20 µsec , 50 A per line max. 1450 V category C2 8/20 µsec , 5 kA per line max. 1200 V category C3 1 kV/µsec , 50 A per line max. 980 V category D1 10/350 µsec , 500 A per line |
|
Screen/Shield indirectly grounded (via GDT) | max. 500 V category B2 10/700 µsec , 100 A max. 600 V category C1 8/20 µsec , 500 A max. 700 V category C2 8/20 µsec , 10 kA max. 550 V category C3 1 kV/µsec , 100 A max. 570 V category D1 10/350 µsec , 1 kA |
|
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Screen/Shield-Earth | max. 100 ns | |
Overstressed fault mode | according IEC 61643-21 line inoperable mode 2 | |
Impulse durability | ||
Per line | 5 kA category C2 8/20 µsec | |
Screen/Shield indirectly grounded (via GDT) | 1 kA category D1 10/350 µsec 10 kA category C2 8/20 µsec |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NAMUR NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | ≤ 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | 45 g | |
Grounding | M4 screw and external grounding rail | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | SIRA 12 ATEX 2128X | |
Marking | II 1G Ex ia IIC T4 | |
Voltage | 24 V | |
Current | 500 mA | |
Internal capacitance | 2 nF | |
Internal inductance | 0.1 µH | |
Certificate | SIRA 12 ATEX 4176X | |
Marking | II 3G Ex nAc IIC T4 , II 3G Ex ic IIC T4 | |
Voltage | 33 V | |
Current | 600 mA | |
Internal capacitance | 2 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
Supplementary information | FISCO field device | |
International approvals | ||
CSA approval | CoC 2595441 | |
Control drawing | 116-0365 | |
Approved for | Class I, Division 1, Groups A, B, C, D T4 Class I, Zone 0, Ex ia IIC T4 Class I, Zone 2, Ex ic IIC T4 Class I, Zone 0, AEx ia IIC T4 Class I, Zone 2, AEx ic IIC T4 Class I, Division 2, Groups A, B, C, D T4 Class I, Zone 2, Ex nL IIC T4 Class I, Zone 2, Ex na IIC T4 Class I, Zone 2, AEx nAc IIC T4 |
|
IECEx approval | IECEx SIR 12.0051X | |
Approved for | Ex ia IIC T4 | |
Certificates and approvals | ||
Marine approval | DNV A-14038 | |
General information | ||
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 19170104 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC002584 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121610 |
This fieldbus surge protector is in accordance with IEC 61158-2 and mounts on the spur connector of FieldConnex ® device couplers, protecting them. It directs power surges to earth via gas discharge tubes. It is certified intrinsically safe for circuits in hazardous areas up to Zone 0/Div. 1 and for DART fieldbus. The surge protector is installed in Zone 1 … 2 or Div. 1 … 2.
Integrated diagnostics (option) continuously monitor wear caused by surges. The end of the useful life and thus the need for exchange is indicated in two ways: via an LED and in the control room via the FieldConnex ® Advanced Diagnostics software.
Installation on the spur connector is without additional wiring even as retrofit. A single grounding bar connects surge protectors mounted side by side to a common grounding point.
Literature | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
Használati útmutató | HUN | 222 KB |
CAD | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|
CAD 2-D / CAD 2-D | ALL | ZIP | 236 KB |
CAD 3-D / CAD 3-D | ALL | STP | 2088 KB |
Certificates | Tanúsítvány sz. | Nyelv | Fájltípus | Fájlméret |
---|---|---|---|---|
Brasil TUV Rheinland Brazil | TÜV 14.1589 X | ALL | 1153 KB | |
Canada, USA CSA Ex i and Ex n | CSA 13.2595441X | ALL | 114 KB | |
China SITIIAS CCC Ex Certificate | 2020322304003528 (Singapore) | ALL | 1024 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe CSA ATEX Category 1 G | Sira 12 ATEX 2128X | ALL | 215 KB | |
Europe CSA ATEX Category 3 G II 3 G | Sira 12 ATEX 4176X | ALL | 228 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/5866 (P506129) | ALL | 100 KB | |
Sira IECEx Certificate of Conformity | IECEx SIR 12.0051X | ALL | LINK | --- |
Control Drawings | ||||
Control drawing CSA / Control drawing CSA | ALL | 92 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-0814CHUN | HUN | 1142 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
Matching System Components | ||||||
|
||||||
|
RSS információs szolgáltatás a PANOS frissítésekkel kapcsolatban
Bármikor tájékozódhat, ha az Ethernet-APL switch-ekoperációs rendszerének, a PANOS-nak új szoftverfrissítése jelenik meg: Az RSS-hírcsatornával azonnal kap egy e-mailes értesítést a postaládájába, miután egy frissítés megjelent.