General specifications |
Signal type | Digital Input |
Supply |
Connection | terminals 23, 24 |
Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz |
Rated current | approx. 130 mA |
Power dissipation | 2.2 W / 3.5 VA |
Power consumption | 2.5 W / 4 VA |
Interface |
Programming interface | programming socket |
Input |
Connection side | field side |
Connection | input I: terminals 1+, 3- input II: terminals 4+, 6- input III: terminals 13+, 14- (control input 1) input IV: terminals 15+, 14- (control input 2) |
Input I, II | 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact |
| Open circuit voltage/short-circuit current | 8.2 V / 10 mA |
| Switching point/switching hysteresis | logic 1: > 2.5 mA ; logic 0: < 1.9 mA |
| Pulse duration | min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs |
| Input frequency | rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz |
| Line fault detection | breakage I ≤ 0.15 mA; short-circuit I > 4 mA |
Input III, IV | |
| Active/Passive | I > 4 mA (for min. 100 ms) / I < 1.5 mA |
| Open circuit voltage/short-circuit current | 18 V / 5 mA |
Output |
Connection side | control side |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 19+, 20- output IV: terminals 21+, 20- output V: terminals 7-, 8+ |
Output I, II | signal, relay |
| Contact loading | 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A |
| Mechanical life | 5 x 107 switching cycles |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Output III and IV | signal , electronic output, passive |
| Contact loading | 40 V DC |
| Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current ≤ 10 µA) |
Output V | analog |
| Current range | 0 ... 20 mA or 4 ... 20 mA |
| Open loop voltage | max. 24 V DC |
| Load | max. 650 Ω |
| Fault signal | downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) |
Programming interface | |
| Connection | programming socket |
| Interface | RS 232 |
Transfer characteristics |
Input I and II | |
| Measuring range | 0.001 ... 1000 Hz |
| Resolution | slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz |
| Accuracy | slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz |
| Measuring time | frequency measurement: < 100 ms |
| Influence of ambient temperature | 0.003 %/K (30 ppm) |
Output I, II | |
| Response delay | ≤ 200 ms |
Output V | |
| Resolution | < 10 µA |
| Accuracy | < 30 µA |
| Influence of ambient temperature | 0.005 %/K (50 ppm) |
Galvanic isolation |
Input I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input III, IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I, II/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Mutual output I, II, III | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Mutual output I, II, IV | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output III, IV/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output III, IV/input III, IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Output III, IV/V | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Output V/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Interface/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Interface/output III, IV | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Indicators/settings |
Display elements | LEDs , display |
Control elements | Control panel |
Configuration | via operating buttons via PACTware |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2006 |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Input | EN 60947-5-6:2000 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | 300 g |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2 |
| Height | 119 mm |
| Width | 40 mm |
| Depth | 115 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |