Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
De complete datasheet als PDF downloaden:
Productbeschrijving |
---|
Ethernet IO-Link master with PROFINET S2 redundancy |
General specifications | ||
---|---|---|
UL File Number | E223772 | |
Functional safety related parameters | ||
MTTF | 582 a | |
Indicators/operating means | ||
LED indication | see manual | |
Rotary switch | Setting the fieldbus protocol | |
Electrical specifications | ||
Rated operating voltage | 18 ... 30 V | |
Nominal voltage | 24 V DC | |
Current consumption | typ. 200 mA | |
Current loading capacity | Max. 2 x 16 A per module (Loop-through current via L-coded power supply) Total current: max. 9 A per module |
|
Galvanic isolation | between US and UL | |
Interface 1 | ||
Interface type | Industrial Ethernet | |
Physical | M12, D-coded | |
Protocol | PROFINET IO with media redundancy protocol (MRP) and S2 system redundancy. EtherNet/IP with Device Level Ring (DLR) | |
Transfer rate | 10/100 Mbps | |
Inputs/Outputs | ||
Number/Type | 4 x IO-Link Class A (X1 – X4) 4 x IO-Link Class B (X5 – X8) Configurable as: max. 8 IO-Link and 4 digital inputs and outputs max. 12 digital inputs and 4 digital outputs max. 12 digital outputs and 4 digital inputs short-circuit protected |
|
Sensor supply | max. 500 mA per port (X1 - X8) via L+ (pin 1) | |
Output current | max. 500 mA per port (X1 - X8) Via C/Q (pin 4) In addition, a maximum of 2 A per port (X5 – X8) Via UAux (pin 2) |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | Type 1 according to IEC 61131-2 | |
Emitted interference | EN 61000-6-4:2007+A1:2011 | |
Noise immunity | EN 61000-6-2:2005 | |
Shock resistance | EN 61131-2:2004 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Cold start temperature | -40 °C (-40 °F) | |
Relative humidity | max. 95 % | |
Altitude | 0 ... 2000 m | |
Shock and impact resistance | 50 g, 11 ms, all axes | |
Vibration resistance | 15 g at 5 - 500 Hz | |
Pollution degree | 3 | |
Mechanical specifications | ||
Contact elements | PA | |
Degree of protection | IP65 / IP67 / IP69K | |
Connection | Power Supply M12, L-coded Fieldbus M12, D-coded Inputs/Outputs M12, A-coded |
|
Material | ||
Contacts | CuSn, gold-plated CuNi, gold-plated |
|
Housing | Diecast zinc | |
Seal | FKM | |
Mass | 500 g | |
Tightening torque, fastening screws | 1 Nm | |
Tightening torque, cable gland | 0.6 Nm | |
Dimensions | ||
Height | 200 mm | |
Width | 59.6 mm | |
Length | 21 mm | |
Construction type | Field housing | |
Tightening torque of clamping screws | 0.5 Nm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242608 |
ECLASS 12.0 | 27242608 |
ECLASS 11.0 | 27242608 |
ECLASS 10.0.1 | 27242608 |
ECLASS 9.0 | 27242608 |
ECLASS 8.0 | 27242608 |
ECLASS 5.1 | 27242608 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
Literature | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
Application Report - Industrial Communication - IO-Link Master - CNC Machines | ENG | 757 KB | |
Product Information - Ethernet IO Modules with IO-Link Master | ENG | 499 KB |
Safety and Security Documentation | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
Safety Datasheet / Sicherheitsdatenblatt | ALL | 383 KB | |
Manuals | |||
Manual | ENG | 4600 KB |
CAD | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 12400 KB |
CAE | |||
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 71 KB |
Certificates | Certificaatnummer | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|---|
Canada, USA UL | CoC E223772 RptRef E223772-20170316 | ALL | 240 KB | |
PNO Certificate of Conformity | Z12767 | ALL | 86 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-3185CHOL | HOL | 195 KB | |
UK Declaration of Conformity (P+F) | TDOC-7493_ENG | ENG | 172 KB |
Device Description Files/Drivers | Vrijgave-informatie | Bestandstype | Bestandsgrootte |
---|---|---|---|
Description files for use with Ethernet/IP Protocol and RSLogix 5000 / Studio 5000 V20 or higher / Beschreibungsdateien für EtherNet/IP und RSLogix 5000 / Studio 5000 | 05/2019 | ZIP | 13620 KB |
EtherNet/IP EDS-Files / EtherNet/IP EDS-Dateien | 04/2019 | ZIP | 73 KB |
PROFINET GSDML-Files / PROFINET GSDML-Dateien | 03/2020 | ZIP | 17 KB |
Commissioning IO-Link-Parameterization for TIA Portal V15 / Inbetriebnahme IO-Link-Parametrierung für TIA Portal V15 | 2019-06 | ZIP | 1409 KB |
Simplified AOIs (Add On Instructions) for Rockwell Automation Studio 5000. Read and Write a single parameter on an ICE1, ICE2, ICE11 or Allen Bradley IO-Link masters / Inbetriebnahmedatei_a | 2.0 Dec 19, 2023 | ZIP | 56091 KB |
Software Tools | |||
IOLM (IO-Link Master Description) for the IO-Link Device Tool from TMG TE / IOLM (IO-Link Master Description) für das IO-Link Device Tool von TMG TE | 2019-11 | ZIP | 63 KB |
Accessory of | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|