Serviceline Industriële Sensoren
Telefoon +32 3 644 25 00
Serviceline Explosiebeveiliging
Telefoon +32 3 644 25 00

Fieldbus Diagnostic Handheld FDH-1

FieldConnex® Fieldbus
FDH-1
  • Comprehensive diagnostics for the fieldbus physical layer
  • Handheld with display and integrated expert system
  • Fieldbus interface Ex ia, FISCO, Entity, and DART
  • For commissioning, online monitoring and troubleshooting
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Multi-language support
  • Operation in Zone 1/Class I, Div. 1
  • Choice of power options for different operating modes
  • PC software for enhanced interface and data backup

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  FDH-1

Productbeschrijving
Fieldbus diagnostic handheld for comprehensive diagnostics of the fieldbus physical layer
General specifications
Design / MountingHandheld/mobile
Installation in hazardous areaZone 1 / Div. 1
Supply
ConnectionFieldbus , Battery , 9V 6LR61 block, type alkaline, carbon-zinc, lithium iron disulfide, nickel-cadmium, nickel-metal hydride, or rechargeable lithium , USB
Fieldbus connection
Fieldbus typeFOUNDATION Fieldbus/PROFIBUS PA
Rated voltage8.5 ... 35 V
Rated current... 10 mA , if bus powered
Indicators/operating means
DisplayLC display
KeypadMembrane 8 keys
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Software
LanguagesEnglish (default), German (optional), Portuguese (optional),
Ambient conditions
Ambient temperature-20 ... 50 °C (-4 ... 122 °F)
Storage temperature-20 ... 70 °C (-4 ... 158 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Mechanical specifications
Connection typeFieldbus: Cable with test clips and cable with test plugs, 2.5 mm
Trigger output: Cable with 2 banana plugs
USB: Square type B socket
Degree of protectionIP44
Mass500 g
Data for application in connection with hazardous areas
EU-type examination certificateZELM 14 ATEX 0531
MarkingEx-Hexagon II 2(1) G Ex ib [ia Ga] IIC T4 Gb ,
Ex-Hexagon II 3(1) G Ex ic [ia Ga] IIC T4 Gc ,
Ex-Hexagon II 3 G Ex ic IIC T4 Gc ,
Ex-Hexagon II (1) D [Ex ia IIIC Da] ,
Ex-Hexagon II (3) D [Ex ic IIIC Dc]
Bus
TypeFieldbus
Type of protectionia, ib
Internal capacitance< 1.8 nF
Internal inductance< 1.5 µH
Voltage Ui30 V
Bus
TypeFieldbus
Type of protectionic
Internal capacitance< 1.8 F
Internal inductance< 1.5 µH
Voltage Ui35 V
Outputs
TypeTrigger output
Maximum safe voltage140 V
Interface
TypeUSB interface
Maximum safe voltage253 V
Voltage Ui6 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012
International approvals
CSA approvalCSA 16.70029275
Approved forClass I, Division 2, Groups A, B, C, D, T4
Associated equipment for Class I, Division 1, Groups A, B, C, D
Associated equipment for Class II, Division 1, Groups E, F, G
Associated equipment for Class III, Division 1
IECEx approvalIECEx ZLM 14.0012
Approved forEx ib [ia Ga] IIC T4 Gb ,
Ex ic [ia Ga] IIC T4 Gc ,
Ex ic IIC T4 Gc ,
[Ex ia IIIC Da] ,
[Ex ic IIIC Dc]
General information
Scope of deliveryFDH-1 incl. carrying case, fieldbus connection cable, USB 2.0 cable, FDH-1 Manager software
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.027242692
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC001604
ETIM 8.0EC001604
ETIM 7.0EC001604
ETIM 6.0EC001604
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: FDH-1

Informative Literature: FDH-1

Taalkeuze:
LiteratureTaalBestandstypeBestandsgrootte
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: FDH-1

Taalkeuze:
Safety and Security DocumentationTaalBestandstypeBestandsgrootte
HandleidingHOLPDF225 KB
Manuals
ManualENGPDF15354 KB
Software Information
Release NoteENGPDF409 KB

Approvals: FDH-1

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Canada, USA CSACSA 16.70029275ALLPDF162 KB
China SITIIAS CCC Ex Certificate2020322310003511 (Singapore)ALLPDF1165 KB
Europe ZELM ATEXZELM 14 ATEX 0531ALLPDF778 KB
Worldwide ZELM IECEx Certificate of ConformityIECEx ZLM 14.0012ALLLINK---
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF281 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-1076DALLPDF1041 KB

Software: FDH-1

Taalkeuze:
Software ToolsVrijgave-informatieBestandstypeBestandsgrootte
FDH-1 Manager / FDH-1 Manager1.0.3.1144ZIP52320 KB

Van beslissing over planning, installatie en indienstname tot gebruik en onderhoud: Ontdek hoe u het beste uit uw veldbusinfrastructuur kunt halen…

De Fieldbus Diagnostic Handheld FDH-1

Haal het hoogste rendement uit uw veldbusinstallatie met de nieuwe Fieldbus Diagnostic Handheld FDH-1