Serviceline Industriële Sensoren
Telefoon +32 3 644 25 00
Serviceline Explosiebeveiliging
Telefoon +32 3 644 25 00

Power Supply PS1000-A6-12.16

PS1000-A6-12.16
  • 100 V AC to 240 V AC wide-range input
  • Output 12 V DC, 16 A, 192 W, 1-phase
  • Housing width 39 mm
  • Efficiency up to 94.3 %
  • Minimal inrush current surge
  • Remote control for ON/OFF
  • DC OK relay contact
  • Suitable for Zone 2/Div. 2 mounting

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  PS1000-A6-12.16

Electrical specifications
Efficiency92.8 % at 120 V AC
94.3 % at 230 V AC
Power dissipation14.9 W at 120 V AC
11.6 W at 230 V AC
Input
Voltage range100 ... 240 V AC (-15 %/+10 %), 50 ... 60 Hz (±6 %)
110 ... 150 V DC (±20 %)
Current1.74 A at 120 V AC
0.92 A at 230 V AC
1.9 A at 110 V DC
for lower output currents see technical information
Inrush current6 A peak at 120 V AC and ambient temperature 40 °C (104 °F)
9 A peak at 230 V AC and ambient temperature 40 °C (104 °F)
Capacity factor0.99 at 120 V AC
0.96 at 230 V AC
Remote controlterminals 15-, 16+
remote control for ON/OFF
Output
Rated voltage12 V DC
Voltage range12 ... 15 V DC
factory setting: 12 V
Rated current16 A
Current19.2 ... 15.4 A at ambient temperature < 45 °C (113 °F)
16 ... 12.8 A at ambient temperature 60 °C (140 °F)
12 ... 9.6 A at ambient temperature 70 °C (158 °F)
linear power derating see technical information
Power192 W
Ripplemax. 50 mV pp
Hold-up time50 ms at 120 V AC
50 ms at 230 V AC
Overload behaviorcontinuous current : output voltage > 6.5 V DC
intermittent current : output voltage < 6.5 V DC
Short-circuit currenttyp. 55 A for up to 12 ms, load impedance < 30 mΩ
Voltage limitationtyp. 18.2 V DC
max. 19 V DC
Fault indication output
Connectionterminals 13, 14
Output typerelay contact DC OK
- contact is closed if the output voltage is > 90 % of the adjusted output voltage
Contact loadingmax. 60 V DC/0.3 A ; 30 V DC/1 A ; 30 V AC/0.5 A resistive load
min. 1 mA at 5 V DC
Galvanic isolation
Input/OutputSELV/PELV
Indicators/settings
Display elementsLED green: status DC OK
- LED lights up if the output voltage is > 90 % of the adjusted output voltage
Control elementspotentiometer
Configurationsetting of the output voltage via potentiometer
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUIEC/EN 61000-6-1 , IEC/EN 61000-6-2 , IEC/EN 61000-6-3 , IEC/EN 61000-6-4 , IEC/EN 61000-3-2 ,
IEC/EN 61000-3-3
Low voltage
Directive 2014/35/EUEN 61010-1
RoHS
Directive 2011/65/EU (RoHS)IEC/EN 63000:2019
Conformity
Degree of protectionEN 60529
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F) , see technical information
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity5 ... 95 %, noncondensing
Shock resistance20 g , 11 ms or 30 g , 6 ms
Vibration resistance2 ... 17.8 Hz : ± 1.6 mm , 17.8 ... 500 Hz : 2 g
Mechanical specifications
Housing materialaluminum alloy , galvanized steel
Degree of protectionIP20
Connection
Input/Outputscrew terminals
conductor cross section: max. 6 mm2 (AWG 20-10)
cable diameter: max. 2.8 mm, wire end ferrules included
stripped insulation length: 7 mm
tightening torque: max. 1 Nm
Relay contact outputspring terminals
conductor cross section: max. 1.5 mm2 (AWG 24-16)
cable diameter: max. 1.6 mm, wire end ferrules included
stripped insulation length: 7 mm
Remote controlspring terminals
conductor cross section: max. 1.5 mm2 (AWG 24-16)
cable diameter: max. 1.6 mm, wire end ferrules included
stripped insulation length: 7 mm
Massapprox. 600 g  
Dimensions39 x 124 x 117 mm (W x H x D) , without DIN mounting rail
Height124 mm
Width39 mm
Depth117 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
ATEX approval
ATEX certificateEPS 15 ATEX 1101 X
ATEX markingEx-Hexagon II 3G Ex ec nC II T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-7:2015+A1:2018 , EN 60079-15:2010
International approvals
UL approvalE223176
IECEx approval
IECEx certificateIECEx EPS 20.0055X
IECEx markingEx ec nC IIC T4 Gc
StandardsIEC 60079-0:2017 , IEC 60079-7:2017 , IEC 60079-15:2017
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027040790
ECLASS 12.027040790
ECLASS 11.027040790
ECLASS 10.0.127040790
ECLASS 9.027040790
ECLASS 8.027049090
ECLASS 5.127049090
ETIM 9.0EC002542
ETIM 8.0EC002542
ETIM 7.0EC002542
ETIM 6.0EC002542
ETIM 5.0EC002542
UNSPSC 12.139121004

Details: PS1000-A6-12.16

Informative Literature: PS1000-A6-12.16

Taalkeuze:
LiteratureTaalBestandstypeBestandsgrootte
Product Information - PS1000 for Global Use up to Zone 2/Div. 2ENGPDF577 KB

Product Documentation: PS1000-A6-12.16

Taalkeuze:
Product informationTaalBestandstypeBestandsgrootte
Technical informationENGPDF3044 KB
Safety and Security Documentation
Instruction manual / BetriebsanleitungALLPDF243 KB
Instruction manual / BetriebsanleitungALLPDF307 KB

Design / Simulation: PS1000-A6-12.16

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP6575 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ195 KB

Approvals: PS1000-A6-12.16

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Bureau Veritas IECEx Certificate of ConformityIECEx EPS 20.0055XALLLINK---
China SITIIAS CCC Ex Certificate2023122303116292 (Mannheim)ALLPDF529 KB
DNV GL MarineTAA0000316ALLPDF179 KB
Europe Bureau Veritas ATEX Category 3 GEPS 15 ATEX 1 101 XALLPDF1071 KB
US CA ULCoC E223176 RptRef E223176-20070416ALLPDF444 KB
USA CSA Hazardous LocationCoC 80059966ALLPDF68 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-4785ALLPDF73 KB
EU Declaration of Conformity (P+F)TDOC-4785AHOLHOLPDF183 KB

Aanverwante producten: PS1000-A6-12.16

Accessories
12 V DC to 28 V DC input, 2 inputs with 1 output, Output 24 V DC, 40 A, Housing width 36 mm, Built-in decoupling mosfets for 1+1 and N+1 redundancy, Only 72 mV voltage drop at 20 A output current, Only 1.7 W loss at 2 x 10 A and 5.9 W at 2 x 20 A input current, Reverse input polarity protection, Suitable for Zone 2/Div. 2 mounting, Device type: device for DIN rail mounting, Function: Redundancy Module, Voltage range: 12 ... 28 V DCpa