Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
De complete datasheet als PDF downloaden:
Electrical specifications | ||
---|---|---|
Operating voltage | 690 V max. | |
Rated impulse withstand voltage | 6 kV | |
Rated frequency | 50/60 Hz | |
Short circuit current limitation | recommended: 25 A : 35 A, gG 40 A : 63 A, gG |
|
Operating current | 25 A max. or 40 A max. | |
Terminal capacity | see data table | |
Rated insulation voltage | 800 V | |
Function | switch disconnector | |
Color | black and red-yellow | |
Contact configuration | see data table | |
Switching configuration | 2 position changeover with left OFF | |
Usage category | see data table | |
Number of poles | see data table | |
Auxiliary contacts | see data table | |
Auxiliary contacts usage category | see data table | |
Operator action | engage - engage | |
Lockable | in 'OFF' position threefold padlockable | |
Labeling | 0 - I | |
Mechanical specifications | ||
Enclosure range | see table | |
Enclosure cover | fully detachable | |
Cover fixing | stainless steel A4 (V4A) hexagonal head screws or stainless steel combination Phillips and slotted screw | |
Screws | M6 | |
Number | 4 | |
Tightening torque | 3.5 Nm | |
Cover seal | foamed silicone | |
Safety | cover detachable only when operator in 'ON' position with SAF.* variants | |
Degree of protection | IP66 | |
Cable entry | see data table | |
Defined entry area | face B | |
Material | ||
Enclosure | carbon loaded, antistatic glass-fiber reinforced polyester (GRP) or AISI 316L, (1.4404) stainless steel | |
Finish | inherent color black or brushed | |
Mass | see data table | |
Dimensions | see data table | |
Tightening torque | ||
Nut torque at enclosure (SW1) | see datasheets of cable glands | |
Mounting | see data table | |
Grounding | GRP none as standard stainless steel M6 internal/external brass nickel-plated grounding bolt |
|
Ambient conditions | ||
Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | CML 16 ATEX 3009X | |
Marking | II 2 GD Ex db eb IIC T* Gb Ex tb IIIC T** °C Db T4/T130 °C @ Ta +55 °C |
|
International approvals | ||
IECEx approval | IECEx CML 16.0008X | |
UKCA approval | CML 22 UKEX 2550X | |
ECAS approval | 22-10-53256/E22-09-052316/NB0002 | |
IA approval | MASC S/18-0003X | |
CCC approval | 2020322304002545 | |
Conformity | ||
Degree of protection | EN 60529 | |
Usage category | IEC / EN 60947 | |
CE marking | 0080 or 0102, see type label | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27144052 |
ECLASS 12.0 | 27144052 |
ECLASS 11.0 | 27144052 |
ECLASS 10.0.1 | 27144052 |
ECLASS 9.0 | 27144052 |
ECLASS 8.0 | 27144052 |
ECLASS 5.1 | 27370401 |
ETIM 9.0 | EC000522 |
ETIM 8.0 | EC000522 |
ETIM 7.0 | EC000522 |
ETIM 6.0 | EC000522 |
ETIM 5.0 | EC000522 |
UNSPSC 12.1 | 39121314 |
Brief Instructions | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|
Brief Instructions - Switch Disconnectors Ex e / Safety Switches Ex e - DIS* / SAF* | ENG | 754 KB |
Certificates | Certificaatnummer | Taal | Bestandstype | Bestandsgrootte |
---|---|---|---|---|
CML IECEx Certificate of Conformity | IECEx CML 16.0008X | ALL | LINK | --- |
China SITIIAS CCC Ex Certificate | 2020322304002545 (Pepperl+Fuchs SE,Mannheim) | ALL | 13190 KB | |
ECASEx | 24-02-102377/E22-12-059623/NB0002 | ALL | 850 KB | |
Europe CML ATEX | CML 16ATEX3009X | ALL | 298 KB | |
UK-Type Examination Certificate | CML 22UKEX2550X | ALL | 264 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-3235B | ALL | 254 KB |