Servisní linka pro průmyslové snímače
Servisní linka ochrany před výbuchem

AS-Interface sensor/actuator module VAA-4E4A-G12-ZAL/EA2L

VAA-4E4A-G12-ZAL/EA2L
  • One-piece housing with stainless steel base
  • Installation without tools
  • Metal threaded inserts with SPEEDCON technology
  • Flat cable connection with cable piercing technique, variable flat cable guide
  • Red LED per channel, lights up in the event of output overload
  • Communication monitoring, configurable
  • Inputs for 2-, 3-, and 4-wire sensors
  • DIN rail mounting
  • AS-Interface certificate

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Stáhněte si kompletní katalogový list ve formátu PDF:


Výňatek z katalogového listu: Technická data   VAA-4E4A-G12-ZAL/EA2L

Popis produktu
G12 flat module, 4 inputs (PNP) and 4 electronic outputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
ProfileS-7.F
IO code7
ID codeF
ID1 codeF
ID2 codeE
UL File NumberE223772
Indicators/operating means
LED FAULTerror display; LED red
red: communication error or address is 0
red flashing: overload of sensor power supply or outputs
LED PWRAS-Interface voltage; green LED
green: voltage OK
flashing green: address 0
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INswitching state (input); 4 LED yellow
LED OUTSwitching status (output); 4 yellow/red LEDs
Yellow: output active
Red: output overload
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) derived from mains up to 300 V AC line-to-neutral
Input
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
option 2 inputs for 4-wire sensors (PNP), DC
Supplyfrom external auxiliary voltage UAUX
Current loading capacity≤ 600 mA overload and short-circuit resistant
Input current≤ 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)≤ 2 mA
1 (attenuated)≥ 6 mA
Signal delay< 1 ms (input/AS-Interface)
Output
Number/Type4 electronic outputs, PNP, overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Voltage≥ (UAUX - 0.5 V)
Current2 A per output
6 A total (TB ≤ 40 °C)
4 A total (TB ≤ 70 °C)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
InputEN 61131-2
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005 EN 62026-2:2013
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Altitude≤ 2000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions 3 shocks
10 g, 16 ms in 6 spatial directions 1000 shocks
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree3
Mechanical specifications
Degree of protectionIP67
ConnectionCable piercing method
flat cable yellow/flat cable black
inputs/outputs: M12 round connector
Material
HousingPBT
Mass230 g
Tightening torque, cable gland0.4 Nm
Dimensions
Height35 mm
Width57.4 mm
Length151.6 mm
MountingMounting plate

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VAA-4E4A-G12-ZAL/EA2L

Product Documentation: VAA-4E4A-G12-ZAL/EA2L

Výběr jazyka:
Product informationJazykTyp souboruVelikost souboru
Label form / BeschriftungsformularALLPDF316 KB
Brief Instructions
Instruction leaflet / BeipackzettelALLPDF1008 KB
Mounting Instruction G12 ModulesENGPDF176 KB

Design / Simulation: VAA-4E4A-G12-ZAL/EA2L

Výběr jazyka:
CADJazykTyp souboruVelikost souboru
CAD 3-D / CAD 3-DALLSTP5376 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VAA-4E4A-G12-ZAL/EA2L

Výběr jazyka:
CertificatesČíslo certifikátuJazykTyp souboruVelikost souboru
Canada, USA ULCoC 20141115-E223772ALLPDF342 KB
Worldwide AS-International Association80101ALLPDF593 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0978DALLPDF118 KB

Související produkty: VAA-4E4A-G12-ZAL/EA2L

Accessories

AS-Interface Handheld with accessoryfa

Blind plug for M12 socketsfa

Adapter cable module/hand-held programming devicefa
lock for G12 modulefa
Bezplatně ke stažení: Oficiální zpráva o komunikačních protokolech založených na protokolu TCP (PDF)

Tato zdarma poskytovaná oficiální zpráva ve formátu PDF porovnává různé komunikační protokoly založené na protokolu TCP (AMQP, OPC UA, MQTT, REST API), které si našly cestu vzhůru a jsou považovány za faktory umožňující používat IIoT a realizovat průmysl 4.0. Získejte zdarma soubor ke stažení hned teď!

Spínací modul rozvaděče KE5 s rozhraním AS-Interface – Jednoduchá manipulace a vylepšená správa

Unikátní design pouzdra nového spínacího modulu rozvaděče KE5 umožňuje jeho jasnou viditelnost a zjednodušuje montáž, zapojení a údržbu uvnitř rozvaděčů a rozbočovačů.

AS-Interface – sortiment

Seznamte se s kompletním sortimentem našich produktů AS-Interface.