Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Stáhněte si kompletní katalogový list ve formátu PDF:
Popis produktu |
---|
Switch cabinet module 2 analog Inputs |
General specifications | ||
---|---|---|
Node type | Standard node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 | |
MTBF | 154 a | |
Indicators/operating means | ||
LED FAULT | Fault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault |
|
LED INT | Internal input supply active; LED green | |
LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address 0 or peripheral error |
|
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED IN | status of input signal; LED yellow off: not active on: signal within measuring range flashing: signal outside of measuring range |
|
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 70 mA (without sensors) / max. 200 mA | |
Protection class | III | |
Current consumption | IAUX ≤ 650 mA | |
Surge protection | UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) | |
Input | ||
Number/Type | 2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V |
|
Supply | From AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX) | |
Current loading capacity | ≤ 100 mA from AS-Interface; overload and short-circuit resistant ≤ 600 mA From auxiliary voltage UAUX (AUX switch position) , overload and short-circuit protected |
|
Input resistance | current input: max. 70 Ω voltage input: 100 kΩ |
|
Accuracy | 0.1 % of input signal range at 25 °C (298 K) | |
Resolution | 15 Bit | |
Temperature influence | 0.0025 %/K of input signal range | |
Output | ||
Temperature influence | 1 µA/K or 0,3 mV/K | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.3.D | |
IO code | 7 | |
ID code | 3 | |
ID1 code | F | |
ID2 code | D | |
Data bits (function via AS-Interface) | The transfer of the data value is based on AS-Interface Profile 7.3. | |
Parameter bits (programmable via AS-i) | function | |
P0 | 50/60 Hz filter P0=1, enabled P0=0, disabled |
|
P1 | projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected |
|
P2 | Indication of the peripheral fault by exceeding measuring range P2=1, peripheral fault is reported P2=0, peripheral fault is not reported |
|
P3 | P3=1, normal operating mode P3=0, both channels in current mode and without recognition of wire breakage |
|
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 |
|
Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
|
Material | ||
Housing | PA 66-FR | |
Mass | 110 g | |
Dimensions | ||
Height | 100 mm | |
Width | 18.9 mm | |
Length | 124 mm | |
Mounting | DIN mounting rail | |
Note | Max. length of jumpers = 5 cm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242601 |
ECLASS 12.0 | 27242601 |
ECLASS 11.0 | 27242601 |
ECLASS 10.0.1 | 27242601 |
ECLASS 9.0 | 27242601 |
ECLASS 8.0 | 27242601 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001596 |
ETIM 8.0 | EC001596 |
ETIM 7.0 | EC001596 |
ETIM 6.0 | EC001596 |
ETIM 5.0 | EC001596 |
UNSPSC 12.1 | 39121535 |
Brief Instructions | Jazyk | Typ souboru | Velikost souboru |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 133 KB | |
Manuals | |||
Manual VBA-2E-KE5-IJL/UJL | ENG | 1586 KB |
CAD | Jazyk | Typ souboru | Velikost souboru |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 19087 KB |
Certificates | Číslo certifikátu | Jazyk | Typ souboru | Velikost souboru |
---|---|---|---|---|
US CA UL | E223772 | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 128901 | ALL | 134 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-3534A | ALL | 108 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
Bezplatně ke stažení: Oficiální zpráva o komunikačních protokolech založených na protokolu TCP (PDF)
Tato zdarma poskytovaná oficiální zpráva ve formátu PDF porovnává různé komunikační protokoly založené na protokolu TCP (AMQP, OPC UA, MQTT, REST API), které si našly cestu vzhůru a jsou považovány za faktory umožňující používat IIoT a realizovat průmysl 4.0. Získejte zdarma soubor ke stažení hned teď!
Spínací modul rozvaděče KE5 s rozhraním AS-Interface – Jednoduchá manipulace a vylepšená správa
Unikátní design pouzdra nového spínacího modulu rozvaděče KE5 umožňuje jeho jasnou viditelnost a zjednodušuje montáž, zapojení a údržbu uvnitř rozvaděčů a rozbočovačů.