Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Stáhněte si kompletní katalogový list ve formátu PDF:
Popis produktu |
---|
G20 module 4 inputs/3 outputs |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 "For use in NFPA 79 Applications only" | |
MTBF | 110 a | |
Indicators/operating means | ||
LED FAULT | Fault indication; red LED Red: communication error or address is 0 Flashing red: overload at motor supply or overload at outputs, or external auxiliary voltage UAUX not present |
|
LED PWR | AS-Interface voltage; green LED Green: voltage OK Flashing green: address is 0 or overload at motor supply, or overload at outputs, or external auxiliary voltage UAUX not present |
|
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED IN | switching state (input); 4 LED yellow | |
LED OUT | Switching state (output); 3 LED yellow | |
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 35 mA | |
Input | ||
Number/Type | 4 Inputs (PNP), DC | |
Supply | from external auxiliary voltage UAUX | |
Input current | ≤ 8 mA (limited internally) | |
Switching point | according to DIN EN 61131-2 0 (undamped) ≤ 0.5 mA 1 (damped) ≥ 2.0 mA |
|
Signal delay | < 1 ms (input/AS-Interface) | |
Output 1 | ||
Number/Type | 3 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Current | 500 mA per output | |
Voltage | ≥ (UAUX - 0.5 V) | |
Output 2 | ||
Number/Type | Motor supply | |
Supply | from external auxiliary voltage UAUX | |
Current | TB < 40 °C: 2 A continuously, 5 A briefly (< 0.5 s) TB < 60 °C: 2 A continuously, 3 A briefly (< 0.5 s) |
|
Voltage | ≥ (UAUX - 0.5 V) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Input | EN 61131-2:2007 | |
Emitted interference | EN 61000-6-4:2007 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.A.E | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | E | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
|
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
|
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
|
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP54 according to EN 60529 | |
Connection | AS-Interface, AUX: Insulation piercing technology Yellow flat cable/black flat cable Inputs/outputs: 8-pin M8 round plug connector, bushing contacts, screw-locking Motor supply: 4-pin M12 round plug connector, bushing contacts, screw-locking, T-coded |
|
Mass | 260 g | |
Dimensions | ||
Height | 27.5 mm | |
Width | 152 mm | |
Length | 53.3 mm | |
Mounting | 2 clips with ∅ 8 mm drill hole | |
Cable length | 1 m | |
Note | The flat cable routing is designed for 100 actuation cycles |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Brief Instructions | Jazyk | Typ souboru | Velikost souboru |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 557 KB |
CAE | Jazyk | Typ souboru | Velikost souboru |
---|---|---|---|
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 364 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
Bezplatně ke stažení: Oficiální zpráva o komunikačních protokolech založených na protokolu TCP (PDF)
Tato zdarma poskytovaná oficiální zpráva ve formátu PDF porovnává různé komunikační protokoly založené na protokolu TCP (AMQP, OPC UA, MQTT, REST API), které si našly cestu vzhůru a jsou považovány za faktory umožňující používat IIoT a realizovat průmysl 4.0. Získejte zdarma soubor ke stažení hned teď!
Spínací modul rozvaděče KE5 s rozhraním AS-Interface – Jednoduchá manipulace a vylepšená správa
Unikátní design pouzdra nového spínacího modulu rozvaděče KE5 umožňuje jeho jasnou viditelnost a zjednodušuje montáž, zapojení a údržbu uvnitř rozvaděčů a rozbočovačů.