ファクトリーオートメーション(FA)
プロセスオートメーション(PA)

HART Termination Board HiSHPMM/64/CONA-01

HiSHPMM/64/CONA-01
  • 64-channel
  • 24 V DC supply
  • Connection of two Multiplexers to HART enabled Honeywell TDC 3000 FTA's
  • Redundant power supply connections
  • Dual RS 485 connections
  • HART loop connection via four 20-pin flat ribbon connectors
  • Compact design

注: Pepperl+Fuchs GmbH(旧社名)で発行された証明書・適合宣言書などすべての製品関連文書は、Pepperl+Fuchs AG(新社名)にそのまま適用されます。

データシート(PDF):


技術データ  HiSHPMM/64/CONA-01

Supply
Rated voltage24 V DC
Fusing2 A , 5 x 20 mm (0.2 x 0.8 inch)
Power dissipation0.7 W , with Multiplexer
Reverse polarity protectionyes
HART signal channels (intrinsically safe)
HART signal channels
Number of channels64 unbalanced signal loops
Redundancy
Supplyyes
Galvanic isolation
HART signal channels30 V DC
Ambient conditions
Ambient temperature-20 ... 55 °C (-4 ... 131 °F)
Relative humidity5 ... 90 %, non-condensing
Mechanical specifications
Core cross section2.5 mm2 (16 AWG)
ConnectionHART loop interface: connectors depending on version
RS-485 interface: removable screw terminals
power: removable screw terminals
Massapprox. 500 g
Dimensions152 x 121 x 142 mm (6 x 4.75 x 5.6 inch) (W x H x D) , depth including module assembly with HiDMux2700
Height121 mm
Width152 mm
Depth142 mm
MountingDIN rail mounting
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210190
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127242690
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: HiSHPMM/64/CONA-01

Product Documentation: HiSHPMM/64/CONA-01

Language Selection:
Manuals言語ファイルタイプファイルサイズ
Manual DTM description HiDMux2700ENGPDF2278 KB
Manual HiDMux2700ENGPDF8581 KB

関連製品: HiSHPMM/64/CONA-01

Accessory of

32-channel, 24 V DC supply, HART field device input (revision 5 to 7), RS-485 interface, Up to SIL 3 acc. to IEC/EN 61508pa