Serviceline Industrial Sensors
Serviceline Explosion Protection

Surge Protector F*-LBF-D1.32

FieldConnex® Fieldbus
F*-LBF-D1.32
  • Surge Protector in stainless steel housing
  • Flameproof enclosure (Ex d) protection
  • Surge protection for '+' and '-' fieldbus lead
  • Choice of threads 20 mm or 1/2" NPT
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

PDF 파일로 된 데이타 시트 다운로드:


데이타 시트 발췌: 기술 사양  F*-LBF-D1.32

제품 설명
Surge protector, threaded, for installation via threaded inlet in field housing (Ex d), IP67
General specifications
Design / MountingOutside installation
Installation in hazardous areaZone 1
Electrical specifications
Rated voltage32 V
Nominal discharge current (8/20 µs)
per line10 kA
total10 kA
Max. surge current (8/20 µs)10 kA
Voltage protection level at max. rated current
Line/Line58 V
Line/Earth1700 V
Voltage protection level at 1 kV/µsec
Line/Line50 V
Line/Earth1.2 kV
Reaction time
Line/Linemax. 1 ns
Line/Earthmax. 100 ns
Capacitance
Line/Line25 pF
Line/Earth15 pF
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC/EN 60529
Fieldbus standardIEC 61158-2
Surge protectionIEC 61643-21
Ambient conditions
Ambient temperature-50 ... 80 °C (-58 ... 176 °F)
Storage temperature-50 ... 85 °C (-58 ... 185 °F)
Mechanical specifications
Core cross section1.3 mm2
Housing materialStainless steel 1.4401/316
Degree of protectionIP00/IP67 if correctly installed
Mass160 g
Mountingscrew mounting
Data for application in connection with hazardous areas
EU-type examination certificateKEMA 04 ATEX 2318 X
MarkingEx-Hexagon II 2G Ex d IIC T6...T5 Gb
Maximum values
Rated voltage32 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2018 , EN 60079-1:2007
International approvals
IECEx approvalIECEx KEM 09.0067X
Approved forEx d IIC T6...T5 Gb
Certificates and approvals
Marine approvalDNV A-14038
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.019170104
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC002584
ETIM 8.0EC002584
ETIM 7.0EC002584
ETIM 6.0EC002584
ETIM 5.0EC001604
UNSPSC 12.139121610

Details: F*-LBF-D1.32

Informative Literature: F*-LBF-D1.32

Language Selection:
Literature언어파일 타입파일 크기
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F*-LBF-D1.32

Language Selection:
Safety and Security Documentation언어파일 타입파일 크기
Instruction manualENGPDF153 KB
Manuals
ManualENGPDF232 KB

Design / Simulation: F*-LBF-D1.32

Language Selection:
CAD언어파일 타입파일 크기
CAD 3-D / CAD 3-DALLSTP102 KB

Approvals: F*-LBF-D1.32

Language Selection:
Certificates인증서 번호언어파일 타입파일 크기
Brasil TUV Rheinland BrazilTÜV 13.1161 XALLPDF1773 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe KEMA ATEX Category 2 G Ex dKEMA 04 ATEX 2318XALLPDF1534 KB
KEMA IECEx Certificate of ConformityIECEx KEM 09.0067XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-0512CENGENGPDF1142 KB

관련문서: F*-LBF-D1.32

Accessory of
FieldConnex® Fieldbus, Fieldbus barrier, module for DIN rail mounting, 8 ... 12 outputs Ex ia IIC, FISCO and Entity, Advanced fault isolation and diagnostics at the spur, FieldBarrier in Zone 1/Div. 2, Instruments in Zone 0...1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Device coupler location: Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …