G2 flat module 4 inputs and 2 electronic outputs |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V2.1 | |
Required gateway specification | ≥ V2.1 | |
UL File Number | E223772 | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of outputs |
|
LED PWR | AS-Interface voltage; LED green | |
LED AUX | ext. auxiliary voltage UAUX ; LED green | |
LED IN | switching state (input); 4 LED yellow | |
LED OUT | Switching state (output); 2 LED yellow | |
Electrical specifications | ||
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 30 mA | |
Protection class | III | |
Current loading capacity | 2 A (IAUX) | |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) | |
Input | ||
Number/Type | 4 inputs for mechanical contacts or 3-wire sensors (PNP), DC | |
Supply | from external auxiliary voltage UAUX | |
Input current | 3 mA (typically) | |
Switching point | according to DIN EN 61131-2 (type 1) | |
0 (unattenuated) | ≤ 0.5 mA | |
1 (attenuated) | ≥ 2 mA | |
Signal delay | < 2 ms (input/AS-Interface) | |
Signal frequency | ≤ 250 Hz | |
Output | ||
Number/Type | 2 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Voltage | ≥ (UAUX - 0.5 V) | |
Current | 1 A per output , 2 A per module | |
Usage category | DC-13 | |
Galvanic isolation | ||
Input/Output | none | |
Input/AS-Interface | Basic insulation, rated insulation voltage 120 V DC | |
Output/AS-Interface | Basic insulation, rated insulation voltage 120 V DC | |
Directive conformity | ||
Electromagnetic compatibility | observe notices on the certificate of conformity. | |
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Galvanic isolation | EN 60947-1:2007 | |
Degree of protection | EN 60529:2000 | |
Mech. capacity | EN 60068-2-6:2008, EN 60068-2-27:1995 | |
Input | EN 61131-2:2007 | |
Usage category | EN 60947-5-1:2005 | |
Emitted interference | EN 61000-6-4:2001 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61326-1:2006 | |
Programming instructions | ||
Profile | S-7.A.E | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | E | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | not used | |
P1 | not used | |
P2 | not used | |
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 3 | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Connection | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
|
Material | ||
Housing | PBT | |
Mass | approx. 100 g | |
Tightening torque, cable gland | 0.4 Nm | |
Mounting | Mounting plate |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
The VBA-4E2A-G2-XE/E2 is an AS-Interface I/O module with 4 inputs and 2 electronic outputs. Mechanical contacts (for example buttons) or 3-wire sensors (PNP) can be connected to the inputs. The outputs are electronic outputs designed for a load of 1 A per output. The sensors and actuators connected to the module input and output must receive power externally through an auxiliary power source.
The IP67 flat module is ideally suited for use in the field. An addressing socket is built into the module.
The connection to the sensors/actuators is made by a M12 x 1 rounded connector. An LED is available on the top of the module to display the current switching state for each channel. There is also an LED for monitoring AS-Interface communication and to display whether the module has 0 as an address. One LED indicates when the AS-Interface voltage is applied, while a second one indicates external power supply.
In the standard configuration, the base (mounting plate) of the U-G3FF is used to connect the yellow AS-Interface flat cable and the black flat cable of the external auxiliary power. This lower section allows for contact with the flat cable from both sides.
It is also possible to feed in the external auxiliary voltage with the M12 x 1 rounded connectors. In this case, the seal included in the base of the U-G3FF should be placed in the cage for the black flat cable to ensure protection type IP67.
The device includes communication monitoring, which switches power off to the outputs if no communication takes place on the AS-Interface line for more than 40 ms.
An output overload is reported by the "periphery error" to the AS-Interface master. Communication over the AS-Interface remains in effect.
Brief Instructions | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 188 KB |
CAD | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 149 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Nr. certyfikatu | Język | Typ pliku | Rozmiar pliku |
---|---|---|---|---|
Canada, USA UL | CoC 20141115-E223772 | ALL | 342 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-1018C | ALL | 118 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
Accessories | ||||||
|
||||||
|
Moduł KE5 do szaf sterowniczych AS-Interface — łatwa obsługa i zarządzanie