General specifications |
Signal type | Digital Output |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 18 ... 30 V DC |
Power consumption | max. 3.5 W at 45 mA output current |
Input |
Connection side | control side |
Connection | terminals 7, 8, 9 |
Test pulse length | max. 2 ms from DO card |
Signal level | loop powered 1-signal: 18 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 20 mA (minimum load current DO card) |
Inrush current | ≤ 200 mA after 100 µs |
Output |
Connection side | field side |
Connection | channel 1: terminals 1+, 2-, 3- channel 2: terminals 4+, 5-, 6- |
Internal resistor | 276 Ω |
Current | 45 mA |
Voltage | ≥ 10 V |
Current limit | 45 mA |
Open loop voltage | min. 23.6 V |
Load | nominal 0.05 ... 20 kΩ , valid range for line fault detection (LFD) |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Line fault detection | |
| Test current | max. 350 µA , calculated by ILFD = 3.3 V / (10 kΩ + RLoad) |
Galvanic isolation |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Power supply/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2017 , EN IEC 61326-1:2021 (industrial locations) , EN IEC 61326-3-2:2018 For further information see system description. |
Ambient conditions |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | FIDI 21 ATEX 0091 X |
| Marking | II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Output | Ex ia |
| Voltage | 25.2 V |
| Current | 93 mA |
| Power | 586 mW (linear characteristic) |
Supply | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Input | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Collective error message | |
| Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) |
Galvanic isolation | |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms |
| Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 |
International approvals |
UL approval | E106378 |
| Control drawing | 116-0488 |
IECEx approval | |
| IECEx certificate | IECEx FIDI 21.0009X |
| IECEx marking | Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |