Inductive sensor NJ15-30GK50-A2

NJ15-30GK50-A2
  • 15 mm non-flush

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  NJ15-30GK50-A2

General specifications
Switching functioncomplementary
Output typePNP
Rated operating distance15 mm
Installationnon-flush
Output polarityDC
Assured operating distance0 ... 12.15 mm
Actual operating distance13.5 ... 16.5 mm typ. 15 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.38
Reduction factor r304 0.71
Reduction factor rBrass 0.45
Output type4-wire
Nominal ratings
Operating voltage10 ... 60 V
Switching frequency0 ... 300 Hz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionpulsing
Voltage drop≤ 2.8 V
Voltage drop at IL
Voltage drop IL = 10 mA, switching element on0.9 ... 2.4 V typ. 1.7 V
Voltage drop IL = 20 mA, switching element on0.9 ... 2.4 V typ. 1.7 V
Voltage drop IL = 50 mA, switching element on0.9 ... 2.5 V typ. 1.7 V
Voltage drop IL = 100 mA, switching element on1 ... 2.6 V typ. 1.8 V
Voltage drop IL = 200 mA, switching element on1.2 ... 2.8 V typ. 2 V
Operating current0 ... 400 mA
Off-state current0 ... 0.5 mA typ. 0.01 mA
No-load supply current≤ 9 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1120 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
StandardsEN IEC 60947-5-2
Approvals and certificates
UL approvalcULus Listed, General Purpose
CCC approvalCertified by China Compulsory Certification (CCC)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross section0.75 mm2
Housing materialPBT
Sensing facePBT
Degree of protectionIP68
Dimensions
Length50 mm
Diameter30 mm

Classifications

SystemClasscode
ECLASS 13.027274001
ECLASS 12.027274001
ECLASS 11.027270101
ECLASS 10.0.127270101
ECLASS 9.027270101
ECLASS 8.027270101
ECLASS 5.127270101
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NJ15-30GK50-A2

Product Documentation: NJ15-30GK50-A2

Taalkeuze:
Product informationTaalBestandstypeBestandsgrootte
Installation conditionsENGPDF1054 KB

Design / Simulation: NJ15-30GK50-A2

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP55 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ66 KB

Approvals: NJ15-30GK50-A2

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Canada USA UL Ordinary LocationUL-US-L87056-11-41301991-3 / UL-CA-L87056-31-41301991-3ALLPDF1806 KB
China CQC CCC2024010305676439ALLPDF1077 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2837BALLPDF1218 KB
UK Declaration of Conformity (P+F)TDOC-6061_ENGENGPDF1285 KB

Aanverwante producten: NJ15-30GK50-A2

Accessories

Mounting flange, 30 mmfa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont met Active Shielding Technology

De inductieve VariKont-sensoren met Active Shielding Technology bieden grote schakelafstanden, ongeacht de montageomstandigheden of omgevingsinvloeden. Haal voordeel uit vereenvoudigd installatieontwerp en beperkte kosten!

Inductive Safety Sensors SIL 2 PL d

Gezien de SIL 2-/PL d-geclassificeerde inductieve veiligheidssensoren geen dode zone hebben, kan de gegevensoverdracht worden gewaarborgd zonder handhaving van een minimumafstand tussen sensor en doel. Ontdek onze geoptimaliseerde portfolio voor zware industriële omgevingen.