Solenoid Driver HiC2877

HiC2877
  • 1-channel isolated barrier
  • 24 V DC supply (bus or loop powered)
  • Output 40 mA at 11.2 V DC, 55 mA current limit
  • Contact or logic control input
  • Entity parameter Io/Isc = 93 mA
  • Line fault detection (LFD)
  • Test pulse immunity
  • Up to SIL 3 acc. to IEC/EN 61508 (loop powered)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  HiC2877

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Systematic capability (SC)SC 3
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage20.4 ... 30 V DC loop powered
20.4 ... 30 V DC bus powered via Termination Board
Input current62 mA at 24 V, 300 Ω load
Power dissipation1 W at 24 V, 300 Ω load
Input
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-) loop powered
SL1: 10a(+), 9a(-) bus powered
Control inputexternal switch (dry contact or open collector) non isolated or logic signal input fully floating
Signal level1-signal: 15...30 V DC (current limited to 3 mA) or contact close (internal 10 kΩ pull-up)
0-signal: 0...5 V DC or contact open
Power dissipation1 W at 24 V, 300 Ω load for loop powered
Inrush current0.2 A , 15 ms loop powered
Output
Connection sidefield side
ConnectionSL2: 5a(+), 5b(-)
Internal resistorapprox. 280 Ω
Current≤ 40 mA
Voltage≥ 11.2 V
Current limit55 mA
Open loop voltageapprox. 22.5 V
Loadnominal 0.1 ... 5 kΩ
Switching frequency- bus powered: filter OFF: max. 150 Hz, filter ON: max. 15 Hz
- loop powered: max. 10 Hz
Energized/De-energized delay- bus powered: filter OFF: 1 ms, filter ON: 10 ms
- loop powered: switch-on 50 ms, switch-off 6 ms (300 Ω load)
Line fault detection
Short-circuit< 25 Ω
Open-circuit> 100 kΩ
Test current< 4 mA
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Fault current4 mA pulsing (20 ms ON, 200 ms OFF)
Fault levellead short-circuit detection at < 25 Ω
lead breakage detection at > 100 kΩ typical
Galvanic isolation
Output/power supply, inputs, and collective errorsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Factory settingbus powered, input: dry contact, line fault detection enabled
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 2 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 10 ATEX 046
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia Ga, Ex ia Da, Ex ia Ma
Voltage25.2 V
Current93 mA
Power586 mW
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
CertificateKIWA 15 ATEX 0036 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018
International approvals
FM approval
Control drawing116-0431 (cFMus)
UL approval
Control drawing116-0383 (cULus)
IECEx approval
IECEx certificateIECEx CES 10.0017
IECEx KIWA 15.0018X
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: HiC2877

Product Documentation: HiC2877

Taalkeuze:
Product informationTaalBestandstypeBestandsgrootte
Application Guideline Solenoid DriversENGPDF734 KB
Safety and Security Documentation
HandleidingHOLPDF164 KB
Functional Safety ManualENGPDF1399 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2877

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP2770 KB
CAD Portal / CAD PortalALLLINK---

Approvals: HiC2877

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
Brasil TUV Rheinland BrazilTÜV 18.3033ALLPDF501 KB
Canada FMFM 17 CA 0057XALLPDF328 KB
Europe CESI ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GCESI 10 ATEX 046ALLPDF907 KB
Europe KIWA ATEX Category 3 GKIWA 15 ATEX 0036XALLPDF97 KB
KIWA Ex ec IECEx Certificate of Conformity Zone 2IECEx KIWA 15.0018XALLLINK---
Korea KOSHA15-AV4BO-0597ALLPDF630 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC 20181016 - E106378 RepRef 20140228ALLPDF260 KB
USA FMFM 17 US 0111XALLPDF330 KB
United Arab Emirates SGS Gulf Limited ECASEx23-12-96808/E23-12-099954/NB0002ALLPDF603 KB
United Arab Emirates SGS Gulf Limited ECASEx23-12-96809/E23-12-099955/NB0002ALLPDF602 KB
Worldwide CESI IECEx Certificate of ConformityIECEx CES 10.0017ALLLINK---
exida Functional Safety AssessmentP+F 11/07-044 R034 V1R2ALLPDF577 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF88 KB
Control drawing FM / Control drawing FM   ALLPDF89 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0930CALLPDF49 KB

Aanverwante producten: HiC2877

Accessory of
System board for Yokogawa ProSafe-RS, For 16-channel DO card SDV541, For 16 modules, Recommended modules: HiC2871 (DO), HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: spring terminals, blue, Non-hazardous area: Yokogawa system connector, 50-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Yokogawa, Control system type: ProSafe-RSpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 16-channel DO cards 3604E and 3624, For 16 modules, Recommended modules: HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Triconpa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, For 32-channel (16+16) DO cards 3625 and 3664, For 32 modules, Recommended modules: HiC2873 (DO), HiC2877 (DO), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 32, Signal type: Digital Output, Manufacturer: Triconex, Control system type: Triconpa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.