IO-Link converter ICA-AI-RTD-IO-V1

ICA-AI-RTD-IO-V1
  • IO-Link interface
  • IP67
  • Analog input for RTD resistance temperature sensors
  • Galvanically isolated measurement input
  • For PT100, PT200, PT500, PT1000 sensors
  • Interference frequency filter 50/60 Hz

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Stáhněte si kompletní katalogový list ve formátu PDF:


Výňatek z katalogového listu: Technická data   ICA-AI-RTD-IO-V1

Popis produktu
IO-Link converter with temperature input for RTD resistance temperature sensors
General specifications
UL File NumberE223772
Functional safety related parameters
MTTFd246 a
Indicators/operating means
LED 1Device status, diagnostics
LED 2IO-Link status
Electrical specifications
Rated operating voltage18 ... 30 V
Nominal voltage24 V DC
Nominal current230 mA
Current consumptionmax. 15 mA
Surge protectionCategory II
Interface
Interface typeIO-Link
IO-Link revision1.1
Device ID0x0F0503 (984323)
Transfer rateCOM2 (38.4 kBit/s)
Min. cycle time≥ 10 ms
Process data width16 bits / 2 bytes
SIO mode supportno
Compatible master port typeA, B
Input
Suitable sensorsPT100, PT200, PT500, PT1000
Number/Type1 analog input for RTD
Current loading capacitymax. 200 mA
Lead resistancemax. 50 Ω per conductor
ResolutionADC: 24 Bit
Input filterAverage determination of process data, parameterizable
Temperature influence20 ppm/°K
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardIEC 61131-9 / IO-Link V1.1
Emitted interferenceEN 61000-6-4
Noise immunityEN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-6
Shock resistanceEN 60068, Part 2-6, Part 2-27
Ambient conditions
Ambient temperature-30 ... 70 °C (-22 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humiditymax. 85 %
Climatic conditionsClimatic class 3K3
Altitude0 ... 2000 m
Shock and impact resistance50 g, 11 ms, all axes
Pollution degree3
Mechanical specifications
Degree of protectionIP67
ConnectionIO-Link M12, A-coded
Input M12, A-coded
Material
ContactsZinc, CuNi plated
HousingPlastic PC + PBT
Mass44 g
Dimensions
Height32.3 mm
Width16 mm
Length79.7 mm
Construction typeField housing

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-AI-RTD-IO-V1

Product Documentation: ICA-AI-RTD-IO-V1

Výběr jazyka:
Safety and Security DocumentationJazykTyp souboruVelikost souboru
Instruction manual / BetriebsanleitungALLPDF4195 KB
Manuals
Manual ICA-AI-I/U-IO-V1 and ICA-AO-I/U-IO-V1ENGPDF2677 KB
Parameter Information
Parameterdatenblatt / Parameter DatasheetENGPDF398 KB

Design / Simulation: ICA-AI-RTD-IO-V1

Výběr jazyka:
CADJazykTyp souboruVelikost souboru
CAD 3-D / CAD 3-DALLSTP1522 KB

Approvals: ICA-AI-RTD-IO-V1

Výběr jazyka:
CertificatesČíslo certifikátuJazykTyp souboruVelikost souboru
IO-Link Manufacturer DeclarationCERT-6084AALLPDF174 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-5028CCZECZEPDF339 KB

Software: ICA-AI-RTD-IO-V1

Výběr jazyka:
Device Description Files/DriversInformace o uvolněníTyp souboruVelikost souboru
IODD for ICA-AI-RTD-IO-V1 / IODD für ICA-AI-RTD-IO-V1V1.00.000 / 2023-12-14ZIP157 KB

Související produkty: ICA-AI-RTD-IO-V1

Accessory of

EtherNet/IP IO-Link master with 8 inputs/outputsfa

PROFINET IO IO-Link master with 8 inputs/outputsfa

Ethernet IO-Link module with eight IO-Link portsfa
Ethernet IO-Link module with 8 inputs/outputsfa
Ethernet IO-Link module with 8 inputs/outputsfa
EtherNet/IP IO-Link master with 8 inputs/outputs, DIN rail, screw terminalfa
PROFINET IO IO-Link master with 8 inputs/outputs, DIN rail, screw terminalfa
Ethernet IO-Link master with PROFINET S2 redundancyfa
Firmware variant from ICE3-8IOL-G65L-V1D with Modbus enabled by defaultfa
EtherNet/IP IO-Link master with 8 inputs/outputs, DIN rail, push-in connectorsfa
PROFINET IO IO-Link master with 8 inputs/outputs, DIN rail, push-in terminalsfa
EtherNet/IP and Modbus IO-Link master with 4 x IO-Link Class A and 4 x IO-Link Class B portsfa
PROFINET and Modbus IO-Link master with 4 x IO-Link Class A and 4 x IO-Link Class B portsfa
Ethernet IO-Link module with 4x Class A and 4x Class B IO-Link portsfa
Accessories
torque screwdriver (0.6 Nm)fa
plug-in cap M12fa
IO-Link master, supply via USB port or separate power supply, LED indicators, M12 plug for sensor connectionfa
Úvodní sada IIoT

Připojte senzory ve výrobních prostorech ke cloudu a začněte digitální transformaci s novými úvodními sadami IIoT.