Type Z & Ex pzc purge and pressurization system 7500-MTD-PMRW-01

7500-MTD-PMRW-01
  • Must be used in conjunction with an EPV-7500-* vent
  • Panel mount, rectangular panel
  • Universal power: AC or DC
  • Touch screen display with LEDs for easy visual indication
  • Easy setup with pre-set purge programs for your application
  • Automatic pressure compensation with digital manifold
  • Rugged, corrosion-resistant housing
  • Global third-party approvals for Class I, II, Div. 2 and Zone 2/22
  • Manual valve, no electrical power requirement
  • Purge and pressurization valving in one device

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

A teljes adatlap letöltése PDF formátumban:


Adatlap kivonata: Műszaki adatok  7500-MTD-PMRW-01

Termék leírása
Type Z & Ex pzc purge and pressurization system, panel mount, rectangular panel
General specifications
Equipment architecturemax. enclosure size 12.7 m3 (450 ft3)
For complete technical data, see the 7500 Control Unit and 7500-MAN-MV-01 datasheets
Operating modefully automatic (FA)
Series7500
SystemType Z Purge ; Ex pzc Purge
Hazardous environmentgas or dust
Supply
Rated voltage20 ... 30 V DC at 0.1 A
90 ... 250 V AC , 50 ... 60 Hz at 0.04 A without solenoid valve
Supply voltage can be line-to-line or line-to-neutral, single phase
OVC II
Power consumptionmax. 2.7 W / 7.3 VA without valve
Electrical specifications
Connectionscrew terminals -- see manual for specifications on wire size and torque values
Output
Output I
ConnectionK1, terminals, 1 x NO
Output typeenclosure power contacts
Contact loading5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A
Output II
ConnectionK2, terminals, 1 x NO
Output typealarm and control contacts
Contact loading5 A at 250 V AC , 5 A at 30 V DC, relays must be externally fused inrush current: 50 A
Output III
ConnectionSV1, terminals, L1 powered contact
Output typesolenoid manifold, contact
Contact loading0.5 A at 250 V AC , 0.5 A
Indicators/settings
LED indicationK1: Green - Contact K1 is energized (enclosure contacts)
K2: Amber - Contact K2 is energized (alarm/control contacts)
P/SV: Blue - Safe pressure P1 (minimum enclosure pressure)
P/SV: Amber - Solenoid manifold is energized (purging/pressure compensation)
Pneumatic parameters
Protective gas supplycompressed air or inert gas, 40 µm filter, free from oil
Pressure requirementsupply pressure: 1.4 ... 8.2 bar (20 ... 120 psig)
Safe pressureP1 for gas: 0.12 inch w.c. (0.30 mbar)
P1 for dust: 0.52 inch w.c. (1.29 mbar)
P2: 0.8 inch w.c. (1.99 mbar)
P3: 2.5 inch w.c. (6.22 mbar)
P4: 4.5 inch w.c. (11.2 mbar)

pressure sensing: ± 0.125 in wc (0.31 mbar)
Enclosure pressure0 ... 12.9 mbar (0 ... 5 in wc)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
RoHS
Directive 2011/65/EU (RoHS)EN IEC 63000:2018
Conformity
Electromagnetic compatibilityEN 61326-3-2:2008, EN 61000-6-2:2005
Emitted interferenceFCC CFR 47, part 15, subpart B: 2017 , ICES-003, Issue 6:2016, Class A ITE
Ambient conditions
Ambient temperature-40 ... 50 °C (-40 ... 122 °F) at T6
-40 ... 65 °C (-40 ... 149 °F) at T5
-40 ... 70 °C (-40 ... 158 °F) at T4
Storage temperature-40 ... 80 °C (-40 ... 176 °F)
Relative humidity5 ... 90 %, non-condensing
Altitudemax. 2000 m
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance30 g, 11 ms, all axes
Mechanical specifications
Connection typeelectrical: 2 x 1/2 inch NPTF (open from factory)
1 x M12 opening (plugged from factory)
pneumatic: high-pressure port - 1/8 in NPTF, low-pressure port - 1/8 in NPTF
Degree of protectionMounting to enclosure Type 4X / IP66
MaterialLens: Makrolon® GP-V polycarbonate
Screws: AISI 316 (1.4401), 304, or 18-8 stainless steel
Housing: A380, A356, or 6061-T6 aluminum
Mounting gasket: Bisco® HT-800 medium cellular silicone
Mounting tabs: SAE 304 stainless steel
M12 plug: 6061-T6 aluminum
Mass2.5 kg (5 lb 10 oz)
Data for application in connection with hazardous areas
Certificate
MarkingEx-Hexagon II 3 G Ex ec mc nC [pzc Gc] IIC T6...T4 Gc
Ex-Hexagon II 3 D Ex mc tc [pzc Dc] IIIC T60 °C ... T80 °C Dc
Directive conformity
Directive 2014/34/EUIEC/EN 60079-0 , IEC/EN 60079-2 , IEC/EN 60079-7 , IEC/EN 60079-15 ,
IEC/EN 60079-18 , IEC/EN 60079-31
Supplements: EN 61010-1:2010
International approvals
UL approval
cULusClass I, Division 2, Groups A, B, C, D T6 ... T4
Class II, Division 2, Groups F, G T6 ... T4
IECEx approvalEx ec mc nC [pzc Gc] IIC T6...T4 Gc
Ex mc tc [pzc Dc] IIIC T60 °C ... T80 °C Dc
General information
Supplementary informationType Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027180508
ECLASS 12.027180508
ECLASS 11.027180508
ECLASS 10.0.127180508
ECLASS 9.027180508
ECLASS 8.027180508
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121301

Details: 7500-MTD-PMRW-01

Function

The 7500 series panel/external mount purge and pressurization system consists of a control unit and a 7500-MAN-MV-01 manual manifold mounted to a panel.

The control unit’s menu-driven touch screen display makes it easy to select pre-programmed and user-selected variables. The display has 4 LED indicators that allow users to determine system condition from a distance. See the 7500 control unit datasheet for technical data.

The 7500-MAN-MV-01 manifold combines in one compact housing a ball valve for purging and a needle valve for pressurizing an enclosure. The ball valve has a handle for easy actuation. To provide security and prevent tampering, the needle valve requires a slot-head screwdriver to set the enclosure pressure. See the 7500-MAN-MV-01 manifold datasheet for technical data.

The 7500 series system has NEC, CE Code, ATEX, CCC, and IECEx third-party certifications for Class I, II/Div. 2 Type Z and Zone 2/22 Ex Ppc.

Informative Literature: 7500-MTD-PMRW-01

Nyelvválasztás:
LiteratureNyelvFájltípusFájlméret
Product Information - Pepperl+Fuchs Bebco EPS® 7500 Series Type Z/Ex pzc Purge and Pressurization SystemENGPDF682 KB

Product Documentation: 7500-MTD-PMRW-01

Nyelvválasztás:
Safety and Security DocumentationNyelvFájltípusFájlméret
Használati útmutatóHUNPDF162 KB
Manuals
ManualENGPDF5689 KB

Design / Simulation: 7500-MTD-PMRW-01

Nyelvválasztás:
CADNyelvFájltípusFájlméret
CAD 2-D / CAD 2-DALLZIP963 KB
CAD 3-D / CAD 3-DALLSTP11349 KB
CAD Portal / CAD PortalALLLINK---

Approvals: 7500-MTD-PMRW-01

Nyelvválasztás:
CertificatesTanúsítvány sz.NyelvFájltípusFájlméret
Brasil TUV Rheinland BrazilTÜV 22.1423XALLPDF1303 KB
IECEx Certificate of ConformityIECEx UL 18.0022XALLLINK---
Korea KOSHA18-AV4BO-0462XALLPDF504 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-B0C4CALLPDF171 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-B0F8ALLPDF167 KB

Kapcsolódó termékek: 7500-MTD-PMRW-01

Accessories
Manifold valve used in UL certified installationpa
Manifold valve used in UL certified installationpa
Manifold valve used in UL certified installationpa
You must purchase a 7500 series control unit with this vent.pa
You must purchase a 7500 series control unit with this vent.pa
You must purchase a 7500 series control unit with this vent.pa
You must purchase a 7500 series control unit with this vent.pa
You must purchase a 7500 series control unit with this vent.pa
You must purchase a 7500 series control unit with this vent.pa
Manifold valve used in ATEX and IECEx certificated installationpa
Manifold valve used in UL certified installationpa

Ismerje meg, hogyan biztosíthatja a legokosabb módon a robbanásveszélyes helyek védelmét, és konfigurálhatja saját öblítő- és nyomásfokozó rendszerét!