Serviceline Industrial Sensors
Serviceline Explosion Protection

AS-Interface Gateway/Safety Monitor VBG-PN-K30-DMD-S32-EV

VBG-PN-K30-DMD-S32-EV
  • Gateway and safety monitor in one housing
  • Connection to PROFINET IO
  • SafeLink
  • Certified up to SIL 3 according to IEC 61508 and EN 62061 and up to PLe according to EN 13849
  • 2 AS-Interface networks
  • Six safe electronic outputs
  • Integrated data decoupling
  • Dublicate addressing detection
  • Earth fault detection
  • AS-Interface noise detection
  • Ethernet diagnostic interface

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

PDF 파일로 된 데이타 시트 다운로드:


데이타 시트 발췌: 기술 사양  VBG-PN-K30-DMD-S32-EV

제품 설명
PROFINET Gateway with integrated safety monitor, double master for 2 AS-Interface networks, power supply input with decoupling coils
General specifications
AS-Interface specificationV3.0
PLC-Functionalityactivateable
Duplicate address detectionfrom AS-Interface slaves
Earth fault detectionintegrated
EMC monitoringintegrated
Diagnostics functionExtended function via display
Data decouplingintegrated
Switch-on delay< 10 s
Response delay< 40 ms
UL File NumberE223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
MTTFd100 a
B10d2.5 E+5
Indicators/operating means
DisplayIlluminated graphical LC display for addressing and error messages
LED ETHERNETPROFINET master detected; LED green
LED AS-i ACTIVEAS-Interface operation normal; LED green
LED CONFIG ERRconfiguration error; LED red
LED PRG ENABLEautom. programming; LED green
LED POWERvoltage ON; LED green
LED PRJ MODEprojecting mode active; LED yellow
LED U AS-iAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED IN6 x LED green
LED OUTOutput circuit closed; 6 x green LEDs
Button4
Switch SETSelection and setting of a slave address
OK buttonMode selection traditional-graphical/confirmation
Button MODEMode selection PRJ-operation/save configuration/cursor
ESC buttonMode selection traditional-graphical/cancel
Electrical specifications
Insulation voltage≥ 500 V
Rated operating voltage26.5 ... 31.6 V from AS-Interface; 24 V DC
Rated operating currentapprox. 300 mA PELV
Power supplymax. 4 A per AS-Interface circuit
Interface 1
Interface typePROFINET IO device (IRT)
Physical 2 x RJ-45
ProtocolMedia Redundancy Protocol (MRP)
Transfer rate100 MBit/s
Interface 2
Interface typeRJ-45 Ethernet Diagnostic Interface
Transfer rate10 MBit/s
Interface 3
Interface typeChip card slot
Input
Number/Type6 inputs
Safety: 3 x 2 channels
Or 6 standard inputs
Output
Safety output6 semiconductor outputs
Output circuits: 6 PNP transistor outputs
Max. contact load:
1.2 ADC-13 at 30 VDC, Σ = 7.2 A in total (see derating)
Connection
PROFINETRJ-45
AS-Interfacespring terminals, removable
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2/AC:2005, EN 61000-6-4:2007+A1:2011
Machinery Directive
Directive 2006/42/ECEN 61508:2010 EN ISO 13849-1/AC:2009 EN 62061:2005+A1:2013
Standard conformity
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-4:2007/A1:2011 EN 61000-6-2/AC:2005
Shock resistanceEN 61131-2:2004
Functional safetyEN ISO 13849-1:2008/AC:2009, EN ISO 13849-2:2012 (up to PL e), EN 61508:2010 and EN 62061:2005+A1:2013 (up to SIL3)
Approvals and certificates
UL approvalAn isolated source with a secondary open circuit voltage of ≤ 30 VDC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed.
UL mark does not provide UL certification for any functional safety rating or aspects of the device.
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Material
HousingStainless steel
Mass800 g
Dimensions
Height120 mm
Width110 mm
Length120 mm
Construction typeLow profile housing

Classifications

SystemClasscode
ECLASS 13.027242607
ECLASS 12.027242607
ECLASS 11.027242607
ECLASS 10.0.127242607
ECLASS 9.027242607
ECLASS 8.027242607
ECLASS 5.127242607
ETIM 9.0EC001603
ETIM 8.0EC001603
ETIM 7.0EC001603
ETIM 6.0EC001603
ETIM 5.0EC001603
UNSPSC 12.139121004

Details: VBG-PN-K30-DMD-S32-EV

Informative Literature: VBG-PN-K30-DMD-S32-EV

Language Selection:
Literature언어파일 타입파일 크기
Application Report - Safe and Efficient AS-Interface Installation at JOTONENGPDF1990 KB

Product Documentation: VBG-PN-K30-DMD-S32-EV

Language Selection:
Brief Instructions언어파일 타입파일 크기
Mounting Instruction VBG-PN-K30-DMD-S32-EV / Montageanleitung VBG-PN-K30-DMD-S32-EVALLPDF3379 KB
Manuals
Manual Gateway with PROFINET interfaceENGPDF1221 KB
Manual SafeLink with AS-Interface SafetyENGPDF1855 KB
Manual VBG-PN*-K30-D*-S16*ENGPDF7126 KB
Manual Web-InterfaceENGPDF1407 KB

Design / Simulation: VBG-PN-K30-DMD-S32-EV

Language Selection:
CAD언어파일 타입파일 크기
CAD 3-D / CAD 3-DALLSTP6985 KB
CAD Portal / CAD PortalALLLINK---

Approvals: VBG-PN-K30-DMD-S32-EV

Language Selection:
Certificates인증서 번호언어파일 타입파일 크기
US CA ULE223772ALLLINK---

Software: VBG-PN-K30-DMD-S32-EV

Language Selection:
Device Description Files/DriversRelease Info파일 타입파일 크기
Standard GSDML for Gateway / Standard GSDML für Gateway07/2016ZIP36 KB
Software Tools
SISTEMA SLB Library AS-Interface Safety / SISTEMA SLB Library AS-Interface SafetyZIP622 KB

관련문서: VBG-PN-K30-DMD-S32-EV

Accessories
Software for configuration of K30 Master Monitors/K31 and KE4 Safety Monitorsfa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Product Range

Get to know our full range of AS-Interface products.