Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
PDF 파일로 된 데이타 시트 다운로드:
제품 설명 |
---|
Cabinet module 4 inputs and 4 outputs |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V3.0 | |
UL File Number | E223772 | |
MTBF | 141 a | |
Indicators/operating means | ||
LED FAULT | Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs |
|
LED INT | Internal input supply active; LED green | |
LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
|
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
LED IN | switching state (input); 4 LED yellow | |
LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
|
Electrical specifications | ||
Auxiliary voltage (input) | 12 ... 30 V DC PELV | |
Auxiliary voltage (output) | 20 ... 30 V DC PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 35 mA (without sensors) / max. 190 mA | |
Protection class | III | |
Surge protection | UEXT, UAUX, Ue: overvoltage category II, safe isolated power supplies (PELV) Overvoltage category of the power supplies (primary): III |
|
Rated insulation voltage | 92 V | |
Pulse withstand voltage | 0.8 kV | |
Input | ||
Number/Type | 4 inputs for 3-wire sensors (PNP), DC | |
Supply | from AS-Interface (switch position INT, default settings) or external UEXT (switch position EXT) | |
Voltage | 21 ... 31 V DC (INT) | |
Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) | |
Input current | ≤ 5.6 mA (max.) | |
Switching point | according to DIN EN 61131-2 (type 1) | |
0 (unattenuated) | ≤ 0.5 mA | |
1 (attenuated) | ≥ 2 mA | |
Signal delay | < 1 ms (input/AS-Interface) | |
Output | ||
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from external auxiliary voltage UAUX | |
Voltage | ≥ (UAUX - 0.5 V) | |
Current | 2 A Per output, total 4 A (TB ≤ 60 °C) 1 A Per output, total 4 A (TB ≤ 70 °C) |
|
Usage category | DC-13 | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | |
Machinery Directive | ||
Directive 2006/42/EC | EN ISO 13849-1:2008 EN ISO 13849-2:2012 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Electrical safety | IEC 61140:2009 | |
Input | EN 61131-2:2004 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 | |
Functional safety | EN ISO 13849-1:2008 EN ISO 13849-2:2012 | |
Programming instructions | ||
Profile | S-7.A.7 | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 7 | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
|
P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
|
P2 | Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings) |
|
P3 | not used | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP20 For safety applications: Installation in an enclosure with a minimum protection class of IP54 required |
|
Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2 |
|
Material | ||
Housing | PA 66-FR | |
Mass | 110 g | |
Dimensions | ||
Height | 100 mm | |
Width | 18.9 mm | |
Length | 124 mm | |
Mounting | DIN mounting rail |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
Brief Instructions | 언어 | 파일 타입 | 파일 크기 |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 1582 KB |
CAD | 언어 | 파일 타입 | 파일 크기 |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 19087 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 7518 KB |
Certificates | 인증서 번호 | 언어 | 파일 타입 | 파일 크기 |
---|---|---|---|---|
US CA UL | E223772 | ALL | LINK | --- |
Worldwide AS-International Association AS-Interface | 123702 | ALL | 119 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-1135D | ALL | 116 KB |
Software Tools | Release Info | 파일 타입 | 파일 크기 |
---|---|---|---|
SISTEMA SLB Library AS-Interface Safety / SISTEMA SLB Library AS-Interface Safety | ZIP | 622 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability
The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.