Serviceline Industrial Sensors
Serviceline Explosion Protection

AS-Interface analog module VBA-4A-KE5-IJL/UJL

VBA-4A-KE5-IJL/UJL
  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Power supply of outputs external or from the module, as required
  • Function indicator for the bus, external auxiliary voltage, internal output voltage, and outputs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

PDF 파일로 된 데이타 시트 다운로드:


데이타 시트 발췌: 기술 사양  VBA-4A-KE5-IJL/UJL

제품 설명
Switch cabinet module
Four analog outputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
UL File NumberE223772
MTBF115 a
Indicators/operating means
LED FAULTFault indication: red LED
Red: communication error or address is 0
Red flashing: peripheral fault
LED INTInternal output voltage active; green LED
LED PWRAS-Interface voltage; green LED
Green: voltage OK
Flashing green: address 0 or peripheral error
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED OUTStatus of output signal; yellow LED
Yellow: Output value within range
Yellow flashing: lead breakage (on current output) or output value out of range
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 75 mA (without outputs) / max. 200 mA
Protection classIII
Current consumptionIAUX ≤ 650 mA
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Output
Number/Type4 analog outputs
Current: 0 ... 20 mA
Voltage: 0 ... 10 V
SupplyFrom AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX)
Loadvoltage output: min. 1 kΩ
current output: max. 600 Ω
Current loading capacity≤ 100 mA (signal current + actuator power supply) from AS-Interface; overload-proof and short-circuit proof
≤ 600 mA (signal current + actuator power supply) from external auxiliary voltage UAUX, overload-proof and short-circuit proof
ResolutionVoltage output: 3 mV
Current output: 6 µA
Accuracy0.15 % of full-scale value
Temperature influence1 µA/K or 0,3 mV/K
Short-circuit currentvoltage output: max. 22 mA
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.6
IO code7
ID code3
ID1 codeF
ID2 code6
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P0Watchdog:
P0=1 (default), watchdog active
P0=0, watchdog inactive
P1Output mode:
P1=1 (default), 4x current outputs
P1=0, 4x voltage outputs
P2Indication of peripheral fault:
P2=1 (default), peripheral fault is reported
P2=0, peripheral fault is not reported
P3Automatic mode:
P3=1 (default), manual setting of output mode
P3=0, automatic load detection (mixed mode possible)
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20
ConnectionRemovable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass110 g
Dimensions
Height100 mm
Width18.9 mm
Length124 mm
MountingDIN mounting rail
NoteMax. length of jumpers = 5 cm

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001596
ETIM 8.0EC001596
ETIM 7.0EC001596
ETIM 6.0EC001596
ETIM 5.0EC001596
UNSPSC 12.139121535

Details: VBA-4A-KE5-IJL/UJL

Product Documentation: VBA-4A-KE5-IJL/UJL

Language Selection:
Brief Instructions언어파일 타입파일 크기
Instruction leaflet / BeipackzettelALLPDF133 KB
Manuals
ManualENGPDF1983 KB

Design / Simulation: VBA-4A-KE5-IJL/UJL

Language Selection:
CAD언어파일 타입파일 크기
CAD 3-D / CAD 3-DALLSTP19087 KB

Approvals: VBA-4A-KE5-IJL/UJL

Language Selection:
Certificates인증서 번호언어파일 타입파일 크기
US CA ULE223772ALLLINK---
Worldwide AS-International Association AS-Interface129001ALLPDF149 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3534AALLPDF108 KB

관련문서: VBA-4A-KE5-IJL/UJL

Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.