Serviceline Industrial Sensors
Serviceline Explosion Protection

AS-Interface analog module VBA-4E-KE5-IL

VBA-4E-KE5-IL
  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Sensors supplied from the external auxiliary voltage
  • Function display for bus, external auxiliary voltage and inputs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

PDF 파일로 된 데이타 시트 다운로드:


데이타 시트 발췌: 기술 사양  VBA-4E-KE5-IL

제품 설명
Switch cabinet module
4 analog Inputs
General specifications
Node typeStandard node
AS-Interface specificationV3.0
Required gateway specification≥ V2.1
UL File NumberE223772
MTBF173 a
Indicators/operating means
LED FAULTFault indication: red LED
Red: communication error or address is 0
Red flashing: peripheral fault
LED PWRAS-Interface voltage; green LED
Green: voltage OK
Flashing green: address 0 or peripheral error
LED AUXext. auxiliary voltage UAUX; dual LED green/red
green: voltage OK
red: reverse voltage
LED INstatus of input signal; LED yellow
off: not active
on: signal within measuring range
flashing: signal outside of measuring range
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 70 mA
Protection classIII
Current consumptionIAUX ≤ 650 mA
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type4 analog inputs
Current: 0 mA ... 20 mA/4 mA ... 20 mA
SupplyFrom auxiliary voltage UAUX
Current loading capacity≤ 600 mA From auxiliary voltage UAUX ; overload and short-circuit resistant
Input resistancecurrent input: max. 70 Ω
Accuracy0.1 % of input signal range at 25 °C (298 K)
Resolution15 Bit
Temperature influence0.0025 %/K of input signal range
Output
Temperature influence1 µA/K or 0,3 mV/K
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.E
IO code7
ID code3
ID1 codeF
ID2 codeE
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P050/60 Hz filter
P0=1, enabled
P0=0, disabled
P1not used
P2Indication of the peripheral fault by exceeding measuring range
P2=1, peripheral fault is reported
P2=0, peripheral fault is not reported
P3P3=1, wire break detection active
P3=0, wire break detection disabled
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude≤ 2000 m above MSL
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20
ConnectionRemovable push-in terminals
rated connection capacity:
rigid: 0.20 mm2 ... 1.5 mm2
flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2
flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass110 g
Dimensions
Height100 mm
Width18.9 mm
Length124 mm
MountingDIN mounting rail
NoteMax. length of jumpers = 5 cm

Classifications

SystemClasscode
ECLASS 13.027242601
ECLASS 12.027242601
ECLASS 11.027242601
ECLASS 10.0.127242601
ECLASS 9.027242601
ECLASS 8.027242601
ECLASS 5.127242601
ETIM 9.0EC001596
ETIM 8.0EC001596
ETIM 7.0EC001596
ETIM 6.0EC001596
ETIM 5.0EC001596
UNSPSC 12.139121535

Details: VBA-4E-KE5-IL

Product Documentation: VBA-4E-KE5-IL

Language Selection:
Brief Instructions언어파일 타입파일 크기
Instruction leaflet / BeipackzettelALLPDF133 KB
Manuals
Manual AS-Interface Module VBA-4E-KE5-ILENGPDF1512 KB

Design / Simulation: VBA-4E-KE5-IL

Language Selection:
CAD언어파일 타입파일 크기
CAD 3-D / CAD 3-DALLSTP19087 KB

Approvals: VBA-4E-KE5-IL

Language Selection:
Certificates인증서 번호언어파일 타입파일 크기
US CA ULE223772ALLLINK---
Worldwide AS-International Association AS-Interface128902ALLPDF139 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3534AALLPDF108 KB

관련문서: VBA-4E-KE5-IL

Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.