AS-Interface safety module VBA-2E2A-KE4-ENC/SSI-S

VBA-2E2A-KE4-ENC/SSI-S
  • SSI, Sin/Cos, TTL interface
  • Safe speed monitoring depending on the position
  • Safe position detection
  • Integrated safety logic
  • Memory card for configuration data
  • Up to SIL3 (EN 62061) and PLe (EN13849-1)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

PDF 파일로 된 데이타 시트 다운로드:


데이타 시트 발췌: 기술 사양  VBA-2E2A-KE4-ENC/SSI-S

제품 설명
KE4 control cabinet module for rotary encoders
2 safe inputs und 2 safe outputs
General specifications
Node typeA/B node
AS-Interface specificationV3.0
Required gateway specification≥ V3.0
UL File NumberE223772
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Performance level (PL)PL e
Mission Time (TM)20 a
PFHd5.08 E-9
Indicators/operating means
LED F1, F2rotational movement/halt
LED FAULTerror display; LED red
red: communication error
LED ST1, LED ST2Status of rotary encoders, 2 yellow LEDs
LED AS-iAS-Interface voltage; LED green
LED AUXext. auxiliary voltage UAUX ; LED green
LED CONFDual color-LED, yellow/red, configuration mode
LED O1, O2Stauts of outputs
Electrical specifications
Auxiliary voltage (input)18 … 30 VDC
Insulation voltage500 V AS-Interface/UAUX:
Rated operating voltage18,0 ... 31.6 V from AS-Interface
Rated operating current≤ 150 mA from AS-Interface;
≤ 1400 mA from AUX
Interface 1
Interface typeChip card slot
Input
Number/Type2 inputs for incremental/absolute rotary encoders / 2x RJ45
Voltagemax. 30 V DC , external
Signal delayDenpending on frequency, see instruction manual issue "system response time"
Signal frequencyParameterization range 1 Hz … 250 kHz
Output
Number/Type2 safe electronic outputs
Supplyfrom external auxiliary voltage UAUX
Voltage24 V
Current loading capacitymax contact load: 700 mA DC-13 at 24 V
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Electrical safetyEN 62061:2005 (up to SIL3) EN ISO 13849-1:2008 up to PL e
InputEN 61131-2:2007
AS-InterfaceEN 62026-2:2013
Programming instructions
ProfileSafe input slaves: S-7.B.E. , ID1=F
Diagnosis slaves: S-7.A.5., ID1=7 (factory default setting)
IO code7
ID codeB
ID1 codeE
Ambient conditions
Ambient temperature0 ... 55 °C (32 ... 131 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Connectionremovable terminals
rated connection capacity:
rigid/flexible (with and without wire-end ferrules): 0.25 mm2 ... 2.5 mm2
for multiple-wire connection with two wires of equal cross-section:
flexible with twin wire-end ferrules: 0.5 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Dimensions
Height99 mm
Width22.5 mm
Length113 mm
MountingDIN mounting rail

Classifications

SystemClasscode
ECLASS 13.027272603
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-2E2A-KE4-ENC/SSI-S

Product Documentation: VBA-2E2A-KE4-ENC/SSI-S

Language Selection:
Brief Instructions언어파일 타입파일 크기
Mounting Instruction VBA-2E2A-KE4-ENC/SSI-S / Montageanleitung VBA-2E2A-KE4-ENC/SSI-SALLPDF2834 KB
Safety and Security Documentation
Instruction manual VBA-2E2A-KE4-ENC/SSI-S / Betriebsanleitung VBA-2E2A-KE4-ENC/SSI-SALLPDF488 KB
Manuals
Manual VBA-2E*-KE4-ENC*ENGPDF5045 KB

Design / Simulation: VBA-2E2A-KE4-ENC/SSI-S

Language Selection:
CAD언어파일 타입파일 크기
CAD 3-D / CAD 3-DALLSTP3239 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ38 KB

관련문서: VBA-2E2A-KE4-ENC/SSI-S

Matching System Components
Safe rotary encoder, thanks to integrated functional safety, Usable up to SIL 3 acc. to IEC 61508 , TÜV certified, Suitable as motor feedback system for safe drives in accordance with IEC 61800-5-2, Incremental encoder with sin/cos interface, Enclosure type: 58 mm, Type of shaft: Solid shaft, Interface: sine / cosine, Application: Safety Function, Detection type: photoelectric sampling, Output type: sine / cosinefa
Accessories

AS-Interface Handheld with accessoryfa

Adapter cable module/hand-held programming devicefa
Combined software for configuration, diagnostics, and programming, for masters and safety monitors (type KE4, K20, K30, K31)fa
KE4 switch cabinet module for rotary encoder
Adapter for 2 rotary encoder to rotation speed monitor and control panelfa
25-point wiring link for control cabinet modules with screw terminalsfa
AS-Interface Product Range