Serviceline Industrial Sensors
Serviceline Explosion Protection

HART Termination Board FI-PFH-TR-AO-380X

FI-PFH-TR-AO-380X
  • System board for Schneider Electric, Tricon series by Triconex
  • HART Termination Board (ETP) for Tricon AO module
  • For 8-channel AO card 3805E
  • 8-channel
  • Field side: pluggable screw terminals, green
  • Control side: ELCO socket, 56-pin

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

下载PDF版完整参数表:


技术参数节选  FI-PFH-TR-AO-380X

Supply
Rated voltage25 ... 28 V DC SELV/PELV
Ripplemax. 10 %
Fusing1 A
Power dissipation≤ 500 mW
Interface
Typemultiplexer connection : IDC plug, 26-pin
Redundancy
SupplyRedundancy available. The supply is monitored and fused.
Signal lines
Rated currentmax. 30 mA per channel
Indicators/settings
Display elements- LED PS-A (Termination Board power supply), green LED
- LED PS-B (Termination Board power supply), green LED
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
For further information see system description.
Degree of protectionIEC 60529:2001
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature0 ... 50 °C (32 ... 122 °F)
Storage temperature-15 ... 50 °C (5 ... 122 °F)
Relative humidity≤ 93 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Mechanical specifications
Degree of protectionIP20
Connection
Field sidepluggable screw terminals , green
Control sideELCO socket, 56-pin
HART : 2 x IDC plug, 26-pin
Supplyscrew terminals , green
Core cross section0.5 ... 2.5 mm2 (20 ... 12 AWG)
Material
HousingPVC
Massapprox. 300 g
Dimensions126 x 123 x 59 mm (5.0 x 4.9 x 2.3 inch) (W x H x D)
Height123 mm
Width126 mm
Depth59 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificatePF 11 CERT 1933 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-15:2010
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210120
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008
Product category / 产品类的HART端子板

Details: FI-PFH-TR-AO-380X

Product Documentation: FI-PFH-TR-AO-380X

选择语言:
Manuals语言文件类型文件大小
Manual KFD*-HM*-16ENGPDF8323 KB

Approvals: FI-PFH-TR-AO-380X

选择语言:
Certificates证书号码语言文件类型文件大小
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3PF11CERT1933 XALLPDF189 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-1070DALLPDF107 KB

配套产品: FI-PFH-TR-AO-380X

Matching System Components

16-channel, No external power required, HART field device input (revision 5 to 7), Used with HART MUX primary module KFD2-HMM-16, Up to SIL 3 acc. to IEC/EN 61508pa

16-channel, 24 V DC supply (Power Rail), HART field device input (revision 5 to 7), Up to 15 KFD0-HMS-16 HART MUX secondary modules can be connected, Up to SIL 3 acc. to IEC/EN 61508pa
Accessories
K-System accessory, Connection cable for KF*-HM*-16 to Termination Board, 26-pin ribbon cablepa
K-System accessory, Connection cable for KF*-HM*-16 to Termination Board, 26-pin ribbon cablepa
K-System accessory, Connection cable for KFD2-HMM-16 to up to 15 KFD0-HMS-16, 14-pin ribbon cablepa