Serviceline Industrial Sensors
Serviceline Explosion Protection

Extension Backplane LB9024BP24300.1

LB9024BP24300.1
  • Backplane for LB-System
  • Fieldbus type determined by base backplane
  • Max. 24 slots for I/O modules
  • 5 SIL 2 output shutdown segments
  • Redundancy (power supply)
  • Mounting in Zone 2, Class I/Div.2 or in the safe area

请注意:所有以Pepperl + Fuchs GmbH或Pepperl + Fuchs AG名义发行的产品相关文件,例如证书,合格声明等,同样适用于Pepperl + Fuchs SE。

下载PDF版完整参数表:


技术参数节选  LB9024BP24300.1

General specifications
Suitable componentsBackplane LB9022BP22320.0.E , LB9022BP22320.0.F , LB9022BP22320.1
Slots
Supply3
Output shut-down5 SIL2 output shutdown segments
slots 25 ... 29, 30 ... 34, 35 ... 39, 40 ... 44, 45 ... 48
I/O modules (single width)max. 24
I/O modules (dual width)max. 12
Supply
Maximum safe voltage Um60 V DC (SELV/PELV)
Input voltage range18 ... 32 V DC (SELV/PELV)
Redundancyyes
Fieldbus connection
Fieldbus typePROFIBUS DP/DP-V1, PROFINET or MODBUS RTU/TCP , depending on the base backplane
Redundancyyes
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionEN 60529
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F) , 70 °C (non-Ex)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing
Altitudemax. 2000 m
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20
Massapprox. 1800 g
Dimensions(W x H x D)
605 x 127 x 80 mm (23.8 x 5 x 3.15 inch) , without modules
Height127 mm
Width605 mm
Depth80 mm
Data for application in connection with hazardous areas
CertificateBVS 16 ATEX E 089 X
MarkingEx-Hexagon II 3 G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020
EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0321
IECEx approvalIECEx BVS 16.0047X
Approved forEx nA IIC T4 Gc
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001598
ETIM 8.0EC001598
ETIM 7.0EC001598
ETIM 6.0EC001598
ETIM 5.0EC001598
UNSPSC 12.139121008
Product category / 产品类的远程输入输出系统底板

Details: LB9024BP24300.1

Informative Literature: LB9024BP24300.1

选择语言:
Literature语言文件类型文件大小
Application Report - Communication Redundancy for Uninterrupted OperationENGPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesENGPDF208 KB
Application Report - Space Saving Extension for Existing PlantsENGPDF300 KB
Application Report - The Modern Whiskey DistilleryENGPDF176 KB
Application Report - Use of Remote I/O in Fluidized Bed SystemsENGPDF222 KB
Application Report - Using Remote I/O Systems for the Efficient Digitalization of PlantsENGPDF371 KB

Product Documentation: LB9024BP24300.1

选择语言:
Safety and Security Documentation语言文件类型文件大小
Instruction manual / BetriebsanleitungCHSPDF321 KB
Manuals
Hardware Manual LB-Remote-I/O-SystemENGPDF5385 KB

Design / Simulation: LB9024BP24300.1

选择语言:
CAD语言文件类型文件大小
CAD 3-D / CAD 3-DALLSTP19456 KB

Approvals: LB9024BP24300.1

选择语言:
Certificates证书号码语言文件类型文件大小
Brasil TUV Rheinland BrazilTÜV 18.0040 XALLPDF1155 KB
Bureau Veritas (Maritime) Marine22449/C0 BVALLPDF590 KB
Canada UL cULE106378 cUL (QUZW7)ALLLINK---
Canada USA UL Certificate of Compliance cULusCoC 20140904 - E106378 RepRef 20010212ALLPDF427 KB
China SITIIAS CCC Ex Certificate2021322308004225 (Mannheim)ALLPDF1155 KB
DEKRA EXAM IECEx Certificate of ConformityIECEx BVS 16.0047XALLLINK---
DNV MarineTAA0000034ALLPDF110 KB
Europe DEKRA EXAM ATEX Category 3 GBVS 16 ATEX E 089 XALLPDF1360 KB
Lloyd's Register MarineLR2003616TA-02ALLPDF557 KB
South Africa MASCMASC MS/20-8438XALLPDF730 KB
South Africa MASCMASC S/20-8434XALLPDF736 KB
USA ULE106378 UL (QUZW)ALLLINK---
USA UL Certificate of ComplianceUL-US-L106378-47733-21201002-5 RepRef E106378-20010212ALLPDF252 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF40 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-3127CALLPDF1041 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-5792ALLPDF1038 KB

配套产品: LB9024BP24300.1

Matching System Components
Backplane for LB-System, For PROFIBUS DP, PROFIBUS DP V1, PROFINET, and MODBUS RTU, Max. 22 slots for I/O modules, 5 SIL 2 output shutdown segments, Number of modules: 22, Redundancy, Fieldbus type: PROFIBUS DP/DP-V1, PROFINET or MODBUS RTU , depends on bus coupler, Redundancypa
Matching System Components
Backplane for LB-System, For PROFIBUS DP, PROFIBUS DP V1, PROFINET, and MODBUS RTU, Max. 8 slots for I/O modules, Mounting in Zone 2, Class I/Div.2 or in the safe area, Number of modules: 8, Fieldbus type: PROFIBUS DP/DP-V1, PROFINET or MODBUS RTU , depends on bus couplerpa
Backplane for LB-System, For PROFIBUS DP, PROFIBUS DP V1, PROFINET, and MODBUS RTU, Max. 16 slots for I/O modules, Mounting in Zone 2, Class I/Div.2 or in the safe area, Number of modules: 16, Fieldbus type: PROFIBUS DP/DP-V1, PROFINET or MODBUS RTU , depends on bus couplerpa
PROFINET Gateway

The new LB/FB PROFINET gateways from Pepperl+Fuchs open the door for IIoT 4.0 applications in process industries.