General specifications |
Signal type | Analog input |
Operation time | MTBF: 1508 a acc. to SN 29500 stationary continuous operating, average ambient temperature 40 °C (104 °F) |
Supply |
Rated voltage | 2.2 ... 30 V DC , loop powered |
Power dissipation | 0.1 W |
Power consumption | 0.6 W |
Input |
Connection side | field side |
Connection | terminals 5+, 6-; 7+, 8- |
Input signal | 0/4 ... 20 mA , max. 50 mA |
Input voltage | ≥ 2.3 V + I x load , max. 30 V |
Voltage drop | ≤ 2.3 V |
Output |
Connection side | control side |
Connection | terminals 1-, 2+; 3-, 4+ |
Analog current output | 0/4 ... 20 mA, load ≤ 600 Ω |
Ripple | ≤ 10 mV eff |
Transfer characteristics |
Accuracy | max. 0.1 % of full-scale value |
Deviation | |
| Influence of load | 0.05 % of the measured value per 100 Ω |
Influence of ambient temperature | < 100 ppm/K of full-scale value |
Frequency range | 0 ... 100 Hz |
Rise time/fall time | ≤ 3.5 ms |
Galvanic isolation |
Field circuit/control circuit | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
Indicators/settings |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | EN 61010-1:2010 |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Core cross section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) |
Mass | approx. 70 g |
Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1 |
| Height | 97 mm |
| Width | 6.2 mm |
| Depth | 107 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
Certificate | DEMKO 16 ATEX 1750X |
| Marking | II 3G Ex nA IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
International approvals |
UL approval | E106378 |
IECEx approval | |
| IECEx certificate | IECEx UL 16.0116X |
| IECEx marking | Ex nA IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |