General specifications |
Signal type | Digital Input |
Supply |
Connection | Power Bus or terminals 1-, 2+ |
Rated voltage | 16.8 ... 31.2 V DC |
Power dissipation | 0.6 W |
Power consumption | 1.1 W |
Input |
Connection side | field side |
NAMUR sensor | |
| Type | 2-wire |
| Connection | terminals 5+, 6 |
| Signal | acc. to EN 60947-5-6 (NAMUR) |
| Sensor supply | 8 V |
| Open-circuit | < 0.1 mA |
| Switching point | 1.2 ... 2.1 mA |
| Short-circuit | > 6 mA |
| Input impedance | 1 kΩ |
Mechanical contact | |
| Type | 2-wire |
| Connection | terminals 5+, 6 |
| Sensor supply | 15 V |
| External supply | ≤ 32 V |
| Switching point | 8 ... 10 V / 1.2 ... 2.1 mA |
| Input impedance | 4 kΩ |
SN sensor | |
| Type | 2-wire |
| Connection | terminals 5+, 6 |
| Sensor supply | 8 V |
| Open-circuit | < 0.1 mA |
| Switching point | 1.2 ... 2.1 mA |
| Short-circuit | > 6 mA |
| Input impedance | 1 kΩ |
2-wire DC sensor | |
| Type | 2-wire |
| Connection | terminals 5+, 6 |
| Signal | acc. to EN 60947-5-2 |
| Sensor supply | 16 V / 25 mA , short-circuit protected |
| External supply | ≤ 32 V |
| Switching point | 2 ... 5 mA |
| Input impedance | 1 kΩ |
S0 sensor | |
| Type | 2-wire |
| Connection | terminals 5+, 6 |
| Signal | acc. to EN 62053-31 , Type B |
| Sensor supply | 15 V |
| Switching point | 0.15 ... 2 mA |
| Input impedance | 4 kΩ |
NPN sensor | |
| Type | 3-wire |
| Connection | terminals 5+, 6, 7- |
| Signal | acc. to EN 60947-5-2 |
| Sensor supply | 16 V / 25 mA , short-circuit protected |
| External supply | ≤ 32 V |
| Switching point | 3 ... 5 V |
| Input impedance | 4 kΩ |
PNP sensor | |
| Type | 3-wire |
| Connection | terminals 5+, 6, 7- |
| Signal | acc. to EN 60947-5-2 |
| Sensor supply | 16 V / 25 mA , short-circuit protected |
| External supply | ≤ 32 V |
| Switching point | 8 ... 10 V |
| Input impedance | 4 kΩ |
AC/DC voltage source | |
| Connection | terminals 7, 8 |
| Signal | 24 V AC/DC |
| Switching point | 10 ... 15 V |
| Input impedance | > 680 kΩ |
AC/DC voltage source | |
| Connection | terminals 7, 8 |
| Signal | 115 V AC/DC |
| Switching point | 40 ... 60 V |
| Input impedance | > 680 kΩ |
AC/DC voltage source | |
| Connection | terminals 7, 8 |
| Signal | 230 V AC/DC |
| Switching point | 80 ... 115 V |
| Input impedance | > 680 kΩ |
Output |
Connection side | control side |
Connection | terminals 3, 4: |
Output | signal, relay |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/2 A/cos φ > 0.7; 30 V DC/2 A resistive load |
Minimum switch current | 2 mA / 24 V DC |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Mechanical life | 107 switching cycles |
Transfer characteristics |
Switching frequency | ≤ 10 Hz |
Galvanic isolation |
Output/power supply | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
Input/Other circuits | safe electrical isolation by reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min |
Indicators/settings |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Degree of protection | IEC 60529:2001 |
Protection against electrical shock | EN 61010-1:2010 |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Core cross section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) |
Mass | approx. 60 g |
Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) (W x H x D) , housing type S1 |
| Height | 97 mm |
| Width | 6.2 mm |
| Depth | 107 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |