Diagnostic gateway kit with Ethernet, FF-H1 interface, I/O, for advanced diagnostics |
General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Supply | ||
Rated voltage | 19.2 ... 35 V DC SELV/PELV | |
Rated current | 210 ... 120 mA | |
Power dissipation | max. 4.2 W | |
Fieldbus connection | ||
Number of segments | 4 | |
Fieldbus type | FOUNDATION Fieldbus | |
Physical layer profile | profile type 114 | |
ITK version | 6 | |
Implementation | resource block 1x RS function block 4x MDI, 1x MDO, 1x MAI, 1x DI transducer block 16x ADM TB, 1x IO TB |
|
Firmware update | Ethernet | |
Polarity | polarity-sensitive | |
Rated voltage | 9 ... 35 V | |
Rated current | 0 mA | |
Ethernet Interface | ||
Rated voltage | max. 35 V SELV/PELV | |
Port | 100 BASE-TX | |
Protocol | TCP/IP and UDP/IP | |
Services | ICMP , DHCP , AutoIP , HTTP | |
Connection type | RJ-45 socket, 8-pin | |
Transfer rate | 100 MBit/s | |
Diagnostic Bus | ||
Connection | only for the connection to protected circuits | |
Rated voltage | max. 35 V | |
Number of Diagnostic Bus Channels | 2 | |
Number of Diagnostic Modules/Channel | 31 Using Ethernet Interface , 8 Using Fieldbus Interface | |
Termination | integrated | |
Cable length/Channel | 30 m | |
Indicators/operating means | ||
LED ERR | red: Hardware fault | |
LED PWR | green: Power on | |
Fault signal | buzzer on | |
LINK/ACT | yellow | |
CH1, CH2 | yellow: diagnostic bus activity | |
Inputs | ||
Input I, II | ||
Input type | selectable: Frequency input , NAMUR/mechanical contact | |
Frequency | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Input frequency | 0.3 Hz to 1 kHz | |
Pulse duration | min. 50 µs | |
Accuracy | ± 1 % | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short-circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input III, IV | ||
Input type | NAMUR/mechanical contact | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input V | ||
Input type | selectable: diagnostic bus CH 1 alarm input , NAMUR/mechanical contact | |
Alarm Input | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input VI | ||
Input type | selectable: diagnostic bus CH 2 alarm input , NAMUR/mechanical contact | |
Alarm Input | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short-circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Input VII, VIII | ||
Input type | selectable: Pt100 4-wire temperature input , NAMUR/mechanical contact | |
Temperature | ||
Connection | only passive load | |
Rated voltage | max. 35 V | |
Measuring range | -50 ... 90 °C (-58 ... 194 °F) | |
Accuracy | 1 K | |
Measuring current | 1 mA | |
Lead resistance | 4.2 Ω per line | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short-circuit | |
NAMUR | ||
Sensor type | NAMUR sensor according to IEC/EN 60947-5-6 | |
Connection | only passive load | |
Rated voltage | max. 35 V | |
Switching frequency | 10 Hz | |
Cable length | max. 30 m | |
Line fault detection | lead breakage , short circuit | |
Humidity | ||
Measuring range | 0 ... 95 % RH | |
Accuracy | 2 % RH | |
Resolution | 0.04 % | |
Outputs | ||
Output I | ||
Output type | selectable: diagnostic bus CH 1 , relay , NO contact | |
Contact loading | 250 V AC/ 6 A resistive load | |
Mechanical life | 1 x 105 switching cycles | |
Response time | turn-on time 7 ms , turn-off time 3 ms | |
Switching frequency | 6 min-1 full load, 1200 min-1 without load | |
Output II | ||
Output type | selectable: diagnostic bus CH 2 , relay , NO contact | |
Contact loading | 250 V AC/ 6 A resistive load | |
Mechanical life | 1 x 105 switching cycles | |
Response time | turn-on time 7 ms , turn-off time 3 ms | |
Switching frequency | 6 min-1 full load, 1200 min-1 without load | |
Output III | ||
Output type | selectable: common alarm , volt-free contact , NC contact | |
Connection | only for the connection to protected circuits | |
Voltage | 50 V DC | |
Current | max. 1 A | |
Output IV | ||
Output type | common alarm , buzzer | |
Galvanic isolation | ||
All circuits/FE | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Output I, II/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff | |
Ethernet/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Ethernet/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Fieldbus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Diagnostic Bus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Low voltage | ||
Directive 73/23/EEC | EN 61010-1:2010 | |
Standard conformity | ||
Galvanic isolation | IEC 62103 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | DIN IEC 721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ethernet | IEEE 802.3 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) hazardous area -40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting |
|
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 5 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminal , pluggable | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | 500 g | |
Dimensions | ||
Height | see dimensions | |
Width | see dimensions | |
Depth | see dimensions | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
FOUNDATION Fieldbus | ||
Connection | For connection to circuits with safe limited voltage according to IEC 60079-11:2011, type of protection "ic" | |
Voltage | max. 35 V | |
Certificate | TÜV 14 ATEX 115980 X | |
Marking | Motherboard MB-FB-GT.AD.FF.IO II 3 G Ex nA nC IIC T4 Gc , Gateway II 3 G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx TUN 14.0003X | |
Approved for | Motherboard Ex nA nC IIC T4 Gc , Gateway Ex nA IIC T4 Gc | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 27242692 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC001604 |
ETIM 8.0 | EC001604 |
ETIM 7.0 | EC001604 |
ETIM 6.0 | EC001604 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Informační služba RSS pro aktualizace systém PANOS
Buďte informováni o vydání nové aktualizace softwaruPANOS, operačního systému pro přepínače Ethernet-APL: Díky našemu informačnímu kanálu RSS obdržíte ihned po vydání aktualizace e-mailové upozornění do své e-mailové schránky.
We and our partners are using technologies like cookies and process personal data like the IP-address or browser information in order to personalize the advertising that you see. This helps us to show you more relevant ads and improves your internet experience. We also use it in order to measure results or align our website content. Because we value your privacy, we are herewith asking for your permission to use these technologies. You can always change/withdraw your consent later by clicking on the settings button on the left lower corner of the page.
Please select the group of cookies and scripts, that you consent to.